Plan Review Notes For Permit 16070916 |
Permit Number |
16070916 |
|
Review Stop |
M |
Sequence Number |
4 |
|
Notes |
Date |
Text |
2017-07-20 14:24:28 | MECHANICAL PROVISOS | | PERMIT #16070916 | | BUILDING #1 | | 7/20/2017 | | | | 1) PROVIDE A ELECTRONICALLY SIGNED AND SEALED COVER | | SHEET AND INDEX FOR ALL THE OF AC SYSTEM SIZING | | CALCULATIONS. | | | | 2) THE TRASH ROOM EXHAUST FAN CAPACITY MUST INCREASE TO | | PROVIDE A MINIMUM EXHAUST RATE OF 1.00 CFMS PER SQ. FT | | PER ASHRAE 62.1. PLEASE REVISE THE FAN SCHEDULE AND | | EXHAUST CALCULATIONS ON THE PLAN. | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL 33401 | | 561-805-6719 | | [email protected] | | |
|