2017-07-17 09:53:073RD REVIEW FBC-2014 MECHANICAL
 PERMIT #16070916
 BUILDING #1
 7/17/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 MANY OF THE COMMENTS FROM THE 1ST AND 2ND REVIEW STILL
 EXISTS. I AM REPRINTING THOSE COMMENT BELOW- PLEASE
 COMPLY.
  
 2ND REVIEW FBC-2014 MECHANICAL
 PERMIT #16070916
 6/8/17
  
 RESULTS: DENIED.
  
 1) THE UPLOADED MECHANICAL RESPONSE NARRATIVE WAS
 COPIED FROM THE BUILDING-4 REVIEW (PERMIT #16070880)
 AND DID NOT ADDRESS COMMENTS #6-11.
  
 2) SHEET M-2.00: THE DRYER EXHAUST DUCTS IN UNITS A1,
 A1 ACCESSIBLE, AND A3 ARE NOT PERMITTED TO RUN THROUGH
 THE MECHANICAL CLOSETS PER SECTION 504.4.
  
 4) THE COMPLIANCE DATA FOR AHU-6 WAS NOT INCLUDED IN
 THE ENERGYGAUGETOTAL BUILDING PERFORMANCE SUBMITTAL
 FORM.
  
 5) PLEASE CORRECT OR REVISE THE PLANS IN ACCORDANCE
 WITH 1ST REVIEW COMMENTS #1, 6, 7, 9, & 11 REPRINTED
 BELOW:
  
 1ST REVIEW COMMENTS.
 8/29/16
  
 1) THE SUBMITTED AC CALCULATION PACKET DOES NOT INCLUDE
 THE AHU-A2/CU-2, AHU-A3/CU-3, AHU-B2/CU-2, AHU-5 (TRASH
 ROOM) AND AHU-6 (ELEVATOR VESTIBULE) SYSTEMS- PLEASE
 PROVIDE. A) THE CALCULATIONS ARE INCORRECTLY INDICATING
 MIAMI AS THE LOCATION. B) REVIEW THE AC SCHEDULE ON
 M-4.00 AS THE 4-TON SYSTEM AHU-1 SYSTEM DOES NOT MATCH
 THE AHU-1 SYSTEM SHOWN ON
  
 SHEET M-2.00 IN TERMS OF CAPACITY. B) REFER TO SECTION
 C403.2.1 FBC-14 ENERGY CONSERVATION: A COOLING AND
 HEATING CALCULATION SHALL BE SUBMITTED FOR EACH SYSTEM
 SHOWN ON THE PLAN, AND ALL SUMMARY CALCULATIONS
 SUBMITTED BY A REGISTERED ENGINEER SHALL BEAR THE
 SIGNATURE AND SEAL OF THE ENGINEER.
  
 6) PROVIDE TRASH ROOM AND ELECTRICAL ROOM EXHAUST
 VENTILATION CALCULATIONS, AND HOISTWAY VENTING
 CALCULATIONS.
  
 7) PROVIDE A REFRIGERANT PIPING RISER AND INCLUDE
 PIPING DETAILS- TYPES AND SIZES, TOTAL ALLOWABLE
 LENGTHS PER THE MANUFACTURER SPECIFICATIONS, AND TYPE
 AND THICKNESSES OF PIPE INSULATIONS.
  
 9) WIND LOAD DESIGN FOR ROOTOP MECHANICAL EQUIPMENT:
 THE CU MOUNTING DETAIL ON M-3.00 IS INDICATING AN
 INCORRECT WIND SPEED OF150 MPH. PLEASE PROVIDE CURRENT
 WIND LOAD DESIGN CRITERIA ON THE PLAN, AND SUBMIT THE
 MIAMI-DADE NOA #13-1017.09 LISTED IN THE DETAIL. PLEASE
 NOTE THE EOR SHALL PLACE HIS SHOP DRAWING APPROVAL
 STAMP AND SIGNATURE ON THE NOA AND ALL OTHER
  
 NOAS, PRODUCT APPROVALS, OR MANUFACTURER'S
 SPECIFICATIONS SUBMITTED AS PART OF THE PERMIT PACKAGE-
 INCLUDING THE GREENHECK MOTORIZED DAMPER AND LOUVER FOR
 THE HOISTWAY, AND ALL OTHER OUTSIDE AIR INTAKE AND
 EXHAUST OUTLET LOUVERS.
  
 11) REFER TO SECTION 3006.2 FBC-14 BUILDING AND CLARIFY
 IF THERE IS AN ELEVATOR MACHINE ROOM, AND PROVIDE AN
 INDEPENDENT VENTILATION OR AIR CONDITIONING SYSTEM. THE
 PLANS SHOW AN ELEVATOR VESTIBULE BUT NO EQUIPMENT IS
 SHOWN IN THE ROOM.
  