2017-07-05 12:48:16 | PERMIT #16070916 906 17TH STREET - 68 UNITS (BUILDING |
| 1) |
| PERMIT #16071059 808 17TH STREET - 45 UNITS (BUILDING |
| 2) |
| PERMIT #16071058 811 15TH STREET - 6 UNITS (BUILDING 3) |
| PERMIT #16070880 805 15TH STREET - 6 UNITS (BUILDING 4) |
| |
| REVIEW COMMENTS - FIRE DEPARTMENT |
| |
| **VERY IMPORTANT** GENERAL: PER NFPA 241 SECTION |
| 8.7.2.3, WHERE UNDERGROUND WATER MAINS AND HYDRANTS ARE |
| TO BE PROVIDED, THEY SHALL BE INSTALLED, COMPLETED, AND |
| IN SERVICE PRIOR TO CONSTRUCTION WORK. |
| |
| GENERAL: INDICATE IF ANY TEMPORARY CONSTRUCTION |
| TRAILERS ARE INTEDED TO OCCUPY THE SITE: PER NFPA 241 |
| SECTION 4.2.2: DETACHMENT BETWEEN TEMPORARY STRUCTURES, |
| ADEQUATE TEMPORARY FIXED FIRE PROTECTION SYSTEMS, AND |
| PORTABLE EQUIPMENT SHALL BE PROVIDED AS REQUIRED BY THE |
| AUTHORITY HAVING JURISDICTION. |
| PER NFPA 241- STANDARD FOR SAFEGUARDING CONSTRUCTION, |
| ALTERATION, AND DEMOLITION OPERATIONS, SECTION 4.2: |
| TEMPORARY OFFICES, TRAILERS, AND OTHER FACILITIES OF |
| COMBUSTIBLE CONSTRUCTION OR HOUSING COMBUSTIBLE |
| CONTENTS SHALL BE SEPARATED FROM ADJACENT BUILDINGS, |
| TRAILERS OR STRUCTURES IN ACCORDANCE WITH TABLE 4.2.1. |
| PER TABLE 4.2.1: |
| 1) 20 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM |
| ADJACENT STRUCTURES BY AT LEAST 30 FEET |
| 2) 30 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM |
| ADJACENT STRUCTURES BY AT LEAST 35 FEET |
| 3) 40 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM |
| ADJACENT STRUCTURES BY AT LEAST 40 FEET |
| 4) 50 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM |
| ADJACENT STRUCTURES BY AT LEAST 45 FEET |
| 5) 60 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM |
| ADJACENT STRUCTURES BY AT LEAST 50 FEET |
| 6) GREATER THAN 60 FEET EXPOSED LENGTH SHALL BE |
| SEPARATED FROM ADJACENT STRUCTURES BY AT LEAST 60 FEET |
| **A 75 PERCENT REDUCTION IN SEPARATION DISTANCES SHALL |
| BE PERMITTED TO BE APPLIED, PROVIDED AUTOMATIC |
| SPRINKLER PROTECTION IS USED IN THE EXPOSING STRUCTURE. |
| |
| REPEAT COMMENT - SHEET WS-2: NO FIRE DEPARTMENT |
| CONNECTIONS PROVIDED FOR BUILDING #3 OR #4. |
| |
| REPEAT COMMENT - SHEET FA-1.00A: ALL OF THE CODES AND |
| STANDARDS REFERENCED IN NOTE #34 ARE OUT OF DATE. |
| |
| DISCLAIMER: FBC SECTION 105.4.1 PERMIT INTENT: A PERMIT |
| ISSUED SHALL BE CONSTRUED TO BE A LICENSE TO PROCEED |
| WITH THE WORK AND NOT AS AUTHORITY TO VIOLATE, CANCEL, |
| ALTER OR SET ASIDE ANY OF THE PROVISIONS OF THE |
| TECHNICAL CODES, NOR SHALL ISSUANCE OF A PERMIT PREVENT |
| THE BUILDING OFFICIAL FROM THEREAFTER REQUIRING A |
| CORRECTION OF ERRORS IN PLANS, CONSTRUCTION OR |
| VIOLATIONS OF THIS CODE. REVIEW AND APPROVAL BY THE AHJ |
| SHALL NOT RELIEVE THE OWNER, CONTRACTOR, ETC. OF THE |
| RESPONSIBILITY OF COMPLIANCE WITH CODE (NFPA 1, SECTION |
| 1.14.4). |
| |
| NOTE: SEPARATE PERMITS ISSUED FROM THE BUILDING DEPT. |
| ARE REQUIRED FOR THE FIRE SPRINKLER, FIRE ALARM, AND |
| PRIVATE UNDERGROUND FIRE MAINS. |
| |