Plan Review Notes
Plan Review Notes For Permit 16070916
Permit Number 16070916
Review Stop P
Sequence Number 1
Notes
Date Text
2016-09-26 09:10:49NOTE: NOT ALL OF THESE COMMENTS APPLY TO EACH BUILDING.
  
  
 1) SHT.A-0.01 - PROJECT DATA - THE PLAN REFERS TO THE
 2010 FBC. THE CODE IN EFFECT IS THE 5TH EDITION (2014)
 VERSION OF THE FBC. REVISE THE NOTE.
 2) SHT. A0.01 - PROJECT DATA - COMPLIANCE NOTE -
 FLORIDA DOES NOT ENFORCE THE ADA. FLORIDA HAS IT'S OWN
 ACCESSIBILITY CODE UNDER THE 2014 FLORIDA BUILDING
 CODE. REVISE THE NOTE TO READ 2014 FBC-ACCESSIBILITY
 VOLUME.
 3) INDICATION THE DESIGN OPTION OF THE FAIR HOUSING ACT
 (SPECIFICATION "A" OR SPECIFICATION "B" ) FOR THE
 DWELLING UNITS. IF THERE IS A MIX OF SPECIFICATION A OR
 B, INDICATE WHICH SPECIFICATION APPLIES TO WHICH UNITS.
 WPB AMENDMENTS TO FBC SEC. 107.2.1.
 4) THE W/S DRAWINGS HAVE NOT BEEN DIGITALLY SIGNED AND
 SEALED AS REQUIRED BY FL. ADMIN. CODE 61G15-23.001.
 5) SHT. A1.01 - DETAIL #1 SHOWS A DRAIN IN THE DUMPSTER
 AREA. PROVIDE DETAILS AS TO THE TERMINATION POINT OF
 THIS DRAIN. I DID NOT SEE ANY THING ON THE SITE
 PLAN/CIVIL DRAWINGS FOR THIS DRAIN.
 6) SHT. A9.0 - DETAIL #1 - THE SIZING OF GUTTERS SHALL
 COMPLY WITH 2014 FPC TABLE 1106.6. INDICATE THE SLOPE
 OF THE GUTTERS AND THE SQUARE FOOTAGE OF THE ROOF
 DRAINING INTO THE GUTTERS.
 7) SHT. A5.08 - ACCESSIBLE RESTROOM FIXTURE LEGEND -
 THE TOILET PAPER DISPENSER SHALL BE LOCATED 7-9 INCHES
 FROM THE FRONT OF THE WATER CLOSET TO THE CENTERLINE OF
 THE DISPENSER. FAC SEC. 604.7.
 8) SHT. A5.08 - SHOW THE DIMENSIONS (LXW) OF THE
 REQUIRED CLEAR FLOOR SPACES FOR THE ACCESSIBLE
 FIXTURES. COMPLY WITH FAC SECS. 305, 602, 604.3, 606.2,
 9) THE MAXIMUM DEPTH OF LAVATORY VANITIES IN THE
 DWELLING UNITS SHALL BE 24 INCHES IN ACCORDANCE WITH
 THE FHA GUIDELINES REQ. #7. SEE SHT. A6.14.
 10) SHT. A6.11 - DETAIL A & B - SHOW THE REQUIRED
 CLEARANCE BETWEEN OPPOSING BASE CABINETS, COUNTERTOPS,
 AND APPLIANCES PER REQUIREMENT #7 OF THE FHA
 GUIDELINES.
 11) SHT. A6.15 - USABLE BATHROOM FIGURES - IDENTIFY
 WHICH BATHROOMS ARE DESIGN SPECIFICATION A AND B.
 12) THE BUILDINGS HAVE TRASH ROOMS, MAINTENANCE ROOMS,
 ETC. SANITARY FACILITIES FOR THE MAINTENANCE WORKERS
 SHALL BE PROVIDED WITHIN 500 FEET OF THESE SPACES OF
 THE BUILDINGS. 2014 FL. PLBG. CODE SEC.403.3.3.
 13) SHT. P1.00 SHOWS A 4 INCH DOMESTIC WATER SERVICE
 LINE TO NOWHERE IN THE NE CORNER OF THE SHEET (BLDG.
 #2) . CLARIFY.
 14) THE PLUMBING SHEETS REFER TO CIVIL DRAWINGS FOR THE
 CONTINUATION OF PLUMBING LINES. INDICATE THE SPECIFIC
 CIVIL SHEET WHERE THE LINE CAN BE LOCATED. WPB AMEND.
 TO FBC SEC. 107.2.1.
 15) THE PLUMBING PLANS REFER TO "SHEET DRAWINGS" FOR
 THE CATCH BASINS. CLARIFY.
 16) THE POINT OF COMPASS ON THE PLUMBING DRAWINGS DOES
 NOT INDICATE "NORTH", OR IT IS SO LIGHT ON THE PLANS
 THAT A DETERMINATION CANNOT BE MADE. CLEARLY SHOW
 "NORTH" ON THE PLANS.WPB AMEND, TO FBC SEC. 107.2.1.
 17) SHT. P-1.00 - IF POSSIBLE, IDENTIFY THE BUILDINGS
 ON THE PLAN. WPB AMEND. TO FBC SEC. 107.2.1.
 18) SHT. P-2.00 - PROVIDE A REFERENCE NOTE LEGEND FOR
 THIS PAGE AND ANY OTHER PAGES WHERE IT IS MISSING. WPB
 AMEND. TO FBC SEC. 107.2.1.
 19) SHT.P-2.00 - THERE ARE STORM DRAIN LINES, RAIN
 WATER LEADER LINES, SANITARY LINES AND DOMESTIC WATER
 LINES EXITING THE BUILDINGS WITH NO CONTINUATION POINT
 SHOWN OR REFERENCED, PLEASE REFERENCE THE DRAWING
 /SHEET NUMBER FOR CONTINUATION AND AVOID GENERAL NOTES
 SUCH AS "SEE CIVIL DRAWINGS FOR CONTINUATION".WPB
 AMEND. TO FBC SEC. 107.2.1.
 20) SUBMIT MANUFACTURER'S SPECIFICATIONS/INSTALLATION
 MANUAL FOR THE OIL SMART PUMP SYSTEM IN THE ELEVATOR
 SHAFT.WPB AMEND. TO FBC SEC. 107.2.1.
 21) THE HUB DRAINS FOR THE ELEVATOR SUMP DRAIN SHALL BE
 EQUIPPED WITH TRAP PRIMERS PER THE 2014 FPC SEC.1002.4.
 22) SUBMIT CALCULATIONS AS TO HOW YOU ARRIVED AT THE
 SIZE OF THE SCHIER LAUNDRY INTERCEPTOR.FPC SEC. 1003.2.
 23) SHT. P-2.05 REFERS TO AN ENLARGED FLOOR PLAN OF THE
 LAUNDRY, RESTROOMS ETC. ON THE SAME SHEET. THERE IS NO
 SUCH PLAN ON THE SHEET. REFER TO SHEET P-2.05 B. REVISE
 NOTE TO REFER TO CORRECT SHEET.
 24) THE PLUMBING DRAWINGS SHOW STACKS IN THE WALLS WITH
 IDENTIFICATION TAGS FOR THE RISERS BUT AN ARROW IS
 INDICATING A DIFFERENT RISER THAN WHAT IS IDENTIFIED.
 CLARIFY.
 25) SUBMIT A DETAIL OF THE DRYWELL.WPB AMEND. TO FBC
 SEC. 107.2.1
 26) ACCESS SHALL BE PROVIDED TO WATER SUPPLY VALVES FOR
 THE STACKED WASHERS/DRYERS. 2014 FPC SEC.606.3.
 27) SHT. P-2.00 SHOWS RISER S/16 IN UNIT B1 ( #115 )
 BUT THIS RISER IS NOT ON THE COLLECTION SYSTEM ON
 SHT.P-4.01 - CLARIFY.
 28) SHT. P-4.01 - RISER S/8 - UNIT A1 - (# 114 ) -
 THERE ARE TWO RISERS WITH THE IDENTIFICATION TAG S/8 ON
 THE COLLECTION ISOMETRIC BUT ONLY ONE S/8 RISER ON THE
 PLAN VIEW ON SHT. P-2.00. CLARIFY.
 29) SHT. P-4.01 - THE ELEVATOR SUMP DRAINS ARE NOT
 SHOWN ON THE COLLECTION ISOMETRIC. CLARIFY.
 30) SHT. P-4.03 - INDICATE THE RAINFALL RATE USED IN
 SIZING THE STORM DRAIN SYSTEM.THE RAINFALL RATE USED
 FOR THE SIZING OF THE SYSTEM SHALL BE 5 INCHES PER
 HOUR. 2014 FPC SEC.1106.1.
 31) INDICATE ON THE PLANS THE SLOPE OF THE PIPE FOR THE
 STORM DRAINAGE SYSTEM. COMPLY WITH 2014 FPC SEC. 1106.2
 & 1106.3.
 32) SHT. P-4.05 - A URINAL IS NOT PERMITTED ON A WET
 VENT PER FPC SEC. 912.1, 912.1.1. ONLY THE FIXTURES IN
 THE BATHROOM GROUP ARE PERMITTED TO DISCHARGE INTO THE
 WET VENT. REFER TO THE DEFINITION OF "BATHROOM GROUP"
 IN THE DEFINITIONS (SEC. 202) OF THE 2014 FPC.
 33) SHT. P-2.05 B - THE MEN'S AND WOMEN'S RESTROOMS ARE
 MISLABELED.
 34) THE LOCATION OF RISERS S/24 AND RISER S/25 ON SHT.
 P2.05 B ARE REVERSED AS TO THE LAYOUT ON SHT. P-4.05.
 SEE BUILDING #2 - UNIT B1 ( UNIT #115 ).
 35) SHT. P-4.05 - THE WASHING MACHINE STACKS SHALL BE A
 MINIMUM OF 3 INCHES PER THE 2014 FPC SEC.406.2.
 36) SHT. P-4.05 - THE DRAINS FOR THE ELEVATOR SUMP ARE
 NOT SHOWN ON THE RISER DIAGRAM. SHOW ALL PIPING ON THE
 SANITARY RISER. WPB AMEND. TO FBC SEC. 107.3.5.1.3.
 37) THE LOCATION OF SANITARY RISERS S/24 AND S/25 ON
 SHT.P-2.05 A DOES NOT CORRELATE WITH THE LOCATION OF
 THE RISERS ON SHT. P-4.05. THE RISERS ARE REVERSED. THE
 LOCATION OF RISER S/32 ON THE PLAN VIEW ON SHT.P-2.05 (
 A) DOES NOT CORRELATE WITH THE LOCATION ON THE SANITARY
 COLLECTION ISOMETRIC ON SHT. P-4.05.
 38) SHT. P-4.05 - THERE ARE TWO SANITARY RISERS LABELED
 S/23 AND ONLY ONE ON THE PLAN VIEW ON SHT,P-2.05 (A).
 SEE UNIT B1 (#100).
 39) SHT. P-2.05 A - RISER S/22 IS SHOWN ON THE PLAN
 VIEW BUT NOT ON THE SANITARY COLLECTION ISOMETRIC ON
 SHT.P-4.05. REFER TO WALL BETWEEN UNIT B1 ( UNIT #100 )
 AND UNIT A1 ( UNIT # 101 ). THIS IS NOT MISLABELED AS
 THERE IS A RISER S/23 FURTHER UPSTREAM.
 40) SHT. P- 5.00 - WASHING MACHINE BOX DETAIL - ACCESS
 IS REQD. FOR THE UNION & REMOVEABLE TRAP SHOWN ON THE
 DETAIL PER THE 2014 FPC SEC.405.8.
 41) SHT. P-5.00 - CHUTE DETAIL - A WATER HAMMER
 ARRESTOR IS REQUIRED ON THIS WATER LINE FOR THE WASH
 DOWN AS IT HAS A SOLENOID VALVE AND IS CCONSIDERED A
 QUICK CLOSING VALVE. 2014 FPC SEC. 604.9.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW