2016-08-29 10:14:161ST REVIEW FBC-2014 MECHANICAL
 PERMIT #16070916
 ROYAL PALM PLACE-, BUILDING-1
 8/29/16
  
 1) THE SUBMITTED AC CALCULATION PACKET DOES NOT INCLUDE
 THE AHU-A2/CU-2, AHU-A3/CU-3, AHU-B2/CU-2, AHU-5 (TRASH
 ROOM) AND AHU-6 (ELEVATOR VESTIBULE) SYSTEMS- PLEASE
 PROVIDE. B) THE CALCULATIONS ARE INCORRECTLY INDICATING
 MIAMI AS THE LOCATION. B) REVIEW THE AC SCHEDULE ON
 M-4.00 AS THE 4-TON SYSTEM AHU-1 SYSTEM DOES NOT MATCH
 THE AHU-1 SYSTEM SHOWN ON
  
 SHEET M-2.00 IN TERMS OF CAPACITY. B) REFER TO SECTION
 C403.2.1 FBC-14 ENERGY CONSERVATION: A COOLING AND
 HEATING CALCULATION SHALL BE SUBMITTED FOR EACH SYSTEM
 SHOWN ON THE PLAN, AND ALL SUMMARY CALCULATIONS
 SUBMITTED BY A REGISTERED ENGINEER SHALL BEAR THE
 SIGNATURE AND SEAL OF THE ENGINEER. SEE ALSO SECTION
 C407.5.2.3 IF SUBMITTING A TOTAL BUILDING PERFORMANCE
 ENERGY
  
 COMPLIANCE METHOD.
  
 2) SHEETS M-2.00, M-2.01, & M-400: THE SPLIT AC
 SCHEDULE DOES NOT INCLUDE THE AHU-2, AHU-3, AHU-B2, &
 AHU-B3 SYSTEMS.
  
 3) SHEETS M2.00 & M-2.01: THE EXCEPTION UNDER SECTION
 504.6.1 THAT ALLOWED THE USE OF DRYER BOOSTER FANS HAS
 BEEN REMOVED FROM THE FBC-14 MECHANICAL CODE. PLEASE
 SUBMIT MANUFACTURER'S SPECIFICATIONS AND EXHAUST VENT
 INSTALLATION INSTRUCTIONS.
  
 4) THE PROPOSED BUILDING SHALL BE IN COMPLIANCE WITH
 THE FBC-14 ENERGY CONSERVATION CODE. REFER TO SECTIONS
 C101.2, C101.5, AND C401.2 AND SUBMIT COMPLIANCE
 MATERIALS AND FORMS.
  
 5) PROVIDE EQUIPMENT SCHEDULES FOR THE APARTMENT
 OUTSIDE AIR FANS AND MOTORIZED DAMPERS, AND PROVIDE
 CLEARANCE DISTANCE MEASUREMENTS FOR ALL AIR INTAKES-
 SECTION 401.4
  
 6) PROVIDE TRASH ROOM AND ELECTRICAL ROOM EXHAUST
 VENTILATION CALCULATIONS, AND HOISTWAY VENTING
 CALCULATIONS.
  
 7) PROVIDE A REFRIGERANT PIPING RISER AND INCLUDE
 PIPING DETAILS- TYPES AND SIZES, TOTAL ALLOWABLE
 LENGTHS PER THE MANUFACTURER SPECIFICATIONS, AND TYPE
 AND THICKNESSES OF PIPE INSULATIONS.
  
 8) PROVIDE UL FIRESTOPPING ASSEMBLIES FOR PIPE
 PENETRATIONS.
  
 9) WIND LOAD DESIGN FOR ROOTOP MECHANICAL EQUIPMENT:
 THE CU MOUNTING DETAIL ON M-3.00 IS INDICATING AN
 INCORRECT WIND SPEED OF150 MPH. PLEASE PROVIDE CURRENT
 WIND LOAD DESIGN CRITERIA ON THE PLAN, AND SUBMIT THE
 MIAMI-DADE NOA #13-1017.09 LISTED IN THE DETAIL. PLEASE
 NOTE THE EOR SHALL PLACE HIS SHOP DRAWING APPROVAL
 STAMP AND SIGNATURE ON THE NOA AND ALL OTHER
  
 NOAS, PRODUCT APPROVALS, OR MANUFACTURER'S
 SPECIFICATIONS SUBMITTED AS PART OF THE PERMIT PACKAGE-
 INCLUDING THE GREENHECK MOTORIZED DAMPER AND LOUVER FOR
 THE HOISTWAY, AND ALL OTHER OUTSIDE AIR INTAKE AND
 EXHAUST OUTLET LOUVERS.
  
 10) REFER TO SECTION 306.5 AND PROVIDE DETAILS FOR THE
 LADDER THAT IS PROVIDING ACCESS TO THE ROOF HATCH.
  
 11) REFER TO SECTION 3006.2 FBC-14 BUILDING AND CLARIFY
 IF THERE IS AN ELEVATOR MACHINE ROOM, AND PROVIDE AN
 INDEPENDENT VENTILATION OR AIR CONDITIONING SYSTEM. THE
 PLANS SHOW AN ELEVATOR VESTIBULE BUT NO EQUIPMENT IS
 SHOWN IN THE ROOM.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER