2016-10-26 18:21:03PLAN
 REVIEW COMMENTS
  
 2ND REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY MECHANICAL
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) FBC - 107.3.5.3 PROVIDE TWO SETS OF A MECHANICAL
 PLAN TO SHOW EQUIPMENT AND LOCATION AND DUCT SYSTEMS
 PER FBC-R M16 & BATH EXHAUST PER FBC-R M15.
  
 2) FBC-R - M1401.3 SIZING. HEATING AND COOLING
 EQUIPMENT SHALL BE SIZED BASED ON BUILDING LOADS
 CALCULATED IN ACCORDANCE WITH ACCA MANUAL J OR OTHER
 APPROVED HEATING AND COOLING CALCULATION METHODOLOGIES.
 PROVIDE EQUIPMENT SIZING CALCULATIONS. FBC-R303.9
 REQUIRES THE NEW HABITABLE SPACE TO BE HEATED AND THE
 USE OF PORTABLE SPACE HEATERS CAN NOT BE USED TO
 ACHIEVE COMPLIANCE WITH THIS SECTION.
  
 3) IN ORDER TO REDUCE PLAN REVIEW TIME, PLEASE SUBMIT A
 RESPONSE LETTER INDICATING HOW EACH OF THE REVIEW
 COMMENTS HAS BEEN ADDRESSED.
  
  
  