Plan Review Notes For Permit 16070890 |
Permit Number |
16070890 |
|
Review Stop |
M |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2016-10-26 18:21:03 | PLAN | | REVIEW COMMENTS | | | | 2ND REVIEW: FBC FIFTH EDITION (2014) | | ROBERT MCDOUGAL, CBO | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | DENIED BY MECHANICAL | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | 1) FBC - 107.3.5.3 PROVIDE TWO SETS OF A MECHANICAL | | PLAN TO SHOW EQUIPMENT AND LOCATION AND DUCT SYSTEMS | | PER FBC-R M16 & BATH EXHAUST PER FBC-R M15. | | | | 2) FBC-R - M1401.3 SIZING. HEATING AND COOLING | | EQUIPMENT SHALL BE SIZED BASED ON BUILDING LOADS | | CALCULATED IN ACCORDANCE WITH ACCA MANUAL J OR OTHER | | APPROVED HEATING AND COOLING CALCULATION METHODOLOGIES. | | PROVIDE EQUIPMENT SIZING CALCULATIONS. FBC-R303.9 | | REQUIRES THE NEW HABITABLE SPACE TO BE HEATED AND THE | | USE OF PORTABLE SPACE HEATERS CAN NOT BE USED TO | | ACHIEVE COMPLIANCE WITH THIS SECTION. | | | | 3) IN ORDER TO REDUCE PLAN REVIEW TIME, PLEASE SUBMIT A | | RESPONSE LETTER INDICATING HOW EACH OF THE REVIEW | | COMMENTS HAS BEEN ADDRESSED. | | | | | | |
|