Plan Review Notes For Permit 16070884 |
Permit Number |
16070884 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2016-08-11 17:27:47 | 1ST REVIEW FBC-2014 MECHANICAL | | PERMIT #16070884 | | 8/11/16 | | | | 1) SUBMIT MECHANICAL PLANS FOR THE PROPOSED TENANT | | REMODEL INCLUDING BUT NOT LIMITED TO: | | | | A) SCOPE OF WORK FOR MECHANICAL DEMOLITION AND | | ALTERATIONS. | | | | B) EXISTING AND NEW HVAC EQUIPMENT SCHEDULES. | | | | C) DUCT LAYOUT PLAN INDICATING NEW, EXISTING, AND | | RELOCATED DUCTS, DIFFUSERS AND RETURN GRILLS. | | | | D) MINIMUM VENTILATION CALCULATIONS FOR ALL ROOMS AND | | SPACES. | | | | E) AIR DISTRIBUTION AND DEVICE SCHEDULES. | | | | 2) PLEASE NOTE AC LOAD CALCULATIONS MAY BE REQUIRED FOR | | NEW AC SYSTEMS, AND ADDITIONAL COMMENTS MAY OCCUR | | PENDING REVIEW OF CORRECTED PLANS. | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 561-805-6719 | | [email protected] | | |
|