2016-08-08 14:14:26JOB PERMIT NUMBER: 16070884
 JOB ADDRESS: 770 NORTHPOINT PARKWAY
 WEST PALM BEACH FLORIDA SUITE # 102
 DATE: AUGUST 8, 2016
  ELECTRICAL PLAN REVIEW COMMENTS
  
 THE PLANS FOR THE ABOVE MENTIONED PERMIT APPLICATION
 HAVE BEEN REVIEWED FOR COMPLIANCE WITH THE EDITION OF
 THE NEC, (NATIONAL ELECTRICAL CODE) AND THE FBC,
 (FLORIDA BUILDING CODE) AS WELL AS THE CITY OF WEST
 PALM BEACH AMENDMENTS IN EFFECT AT THE TIME OF
 SUBMITTAL. BELOW IS A LIST OF THE DEFICIENCIES NOTED.
  
 1) CLARIFY IF ELECTRICAL POLES FOR CUBICLES ARE
 EXISTING? IF NOT PROVIDE MANUFACTURE SPECS. FBC 107
 MINIMUM PLAN REVIEW
 2) IF HAND DRYER OUTLET IS CORD AND PLUG CONNECTED THE
 RECEPTACLE SHALL BE GFCI PROTECTED. NEC 210(B)(1)
 3) ADD EMERGENCY LIGHTING TO CUBICLE AREA FBC-1006.2.
 ILLUMINATION FOR THE MEANS OF EGRESS SHALL NOT BE LESS
 THAN 1' CANDLE AT THE WALKING SURFACE.
 4) NEC 700.12 (F) (4) ? EMERGENCY/EXIT LIGHTING SHALL
 BE FED BY LIGHTING CIRCUIT OF SAME LOCAL AREA. *IF 3 OR
 MORE LIGHTING CIRCUITS SUPPLY THE AREA, EM LIGHTS MAY
 BE ON OWN CIRCUIT.
 5) PROVIDE MANDATORY LIGHTING CONTROLS FOR CUBICLE AREA
 FBC-E SECTION C405.2
 5A) FBC-E SECTION C405.2.1.2 LIGHTING REDUCTION
 5B) FBC-E SECTION C405.2.2.1 AUTOMATIC TIME SWITCH
 5C) FBC-E SECTION C405.2.2.3 DAYLIGHT ZONE CONTROL
 5D) FBC-E SECTION C405.3 TANDEM WIRING
 6) NEC 410.36(B) SUSPENDED CEILING SHALL BE SECURELY
 ATTACHED TO THE BUILDING STRUCTURE AND LUMINAIRES
 FASTENED TO THE CEILING GRID FRAMING MEMBERS BY
 MECHANICAL MEANS, PLEASE VERIFY ANSI STANDARDS FOR FIRE
 RATED ASSEMBLY LOAD CAPACITY. PROVIDE A SUPPORTING
 DETAIL OR ADD A BLOCK NOTE.
 7) FBC-E C405.7 AT THE LEAST 50% OF ALL 125-VOLT, 15-
 AND 20-AMPERE RECEPTACLES SHALL BE AUTOMATICALLY
 CONTROLLED WHERE INSTALLED IN PRIVATE OFFICES, OPEN
 OFFICES, AND COMPUTER CLASSROOMS. THIS INCLUDES THOSE
 INSTALLED IN MODULAR PARTITIONS.
  
 PLEASE REVISE YOUR DRAWINGS TO REFLECT THE ABOVE
 MENTIONED DEFICIENCIES. WHEN RESUBMITTING, FOR A
 QUICKER RETURN ON YOUR RE-SUBMITTAL, YOU ARE REQUIRED
 TO PROVIDE A RESPONSE LETTER (NARRATIVE) ADDRESSING
 EACH ITEM ALONG WITH THE STANDARD CITY RE-SUBMITTAL
 FORM.
 THE NARRATIVE SHOULD INCLUDE THE PLAN REVIEWER'S
 COMMENTS AND YOUR RESPONSE OR ACTION TO SAME.
 ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO THE
 SUBMITTAL AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR
 COMPARISON.
 CLOUDING THE CHANGES WILL BE GREATLY APPRECIATED. IF
 YOU HAVE FURTHER QUESTIONS, PLEASE DON'T HESITATE TO
 CONTACT ME DIRECTLY.
  
 FBC 2014 5TH ED. NEC 2011