2016-07-26 08:40:57 | ****CORRECTIONS**** |
| |
| SAMANTHA HILL |
| BUILDING PLANS EXAMINER |
| [email protected] |
| 561-805-6724 |
| |
| 1. FBC 107, PROVIDE A SITE PLAN SHOWING LOCATION OF |
| PROPOSED WORK. |
| |
| 2. PROVIDE A PLAN (DETAILS) WHICH SHOW PROPOSED WORK. |
| THE PERMIT DOCUMENTS ARE TO BE CLEAR AS TO SCOPE, |
| NATURE, LOCATION. "REMOVE THE EXISTING LINEAR CEILING |
| MATERIAL . . . " DOES NOT INCLUDE INFORMATION SUCH AS - |
| WHAT IS THE MATERIAL? IS IT SUBJECT TO WIND LOADS? IS |
| IT FIRE RATED? IF OUTDOORS, HOW WITH THE "NEW LINEAR |
| CEILING" BE FASTENED TO RESIST WIND LOADS? ENGINEERING |
| (FASTENING TO RESIST WIND LOADS) FOR A PUBLIC |
| COMMERCIAL BUILDING IS REQUIRED BY FLORIDA STATUTE TO |
| BE PREPARED BY A DESIGN PROFESSIONAL. NOT ENOUGH |
| INFORMATION HAS BEEN PROVIDED TO PROVIDE A COMPLETE |
| CHECKLIST. |
| |
| 3. THE PLAN IS TO INCLUDE ALL INFORMATION REQUIRED TO |
| DEMONSTRATE CODE COMPLIANCE, WHICH SHOULD INCLUDE: WIND |
| DESIGN CRITERIA, BUILDING TYPE (FBC CHAPTER 6), |
| BUILDING HEIGHT, GOVERNING CODE AND VERSION (SHOULD |
| INCLUDE ALL APPLICABLE CODES WHICH APPEARS TO INCLUDE |
| FBC EXISTING BUILDING AND BUILDING, PLUMBING), |
| MATERIALS EXISTING, MATERIALS PROPOSED, STRUCTURAL |
| DETAIL FOR THE "LINEAR VENEER CEILING". |
| |
| 4. IF THIS IS TYPE I OR II CONSTRUCTION, SEE ALSO FBC |
| 603. PLAN IS TO INCLUDE THE EXCEPTION AND SUPPORTING |
| DATA IS TO INCLUDE SPEC SHEETS WHICH DEMONSTRATE |
| COMPLIANCE. THE PLAN IS TO INCLUDE INFORMATION |
| REGARDING THE SPACE WHICH OPENS INTO THE PROPOSED WORK |
| AREA (APPEARS TO BE AN EXIT, AND THE PROPOSED WORK AREA |
| IS IN THE EXIT DISCHARGE). |
| |
| 5. BASED ON THE DESCRIPTION, IT IS NOT CLEAR WHETHER OR |
| NOT THE EXISTING ROOF DRAIN SYSTEM IS ADEQUATE. PROVIDE |
| MORE INFORMATION REGARDING THE DRAIN SYSTEM AND THE |
| PROPOSED ADDITION TO THE DRAIN SYSTEM, FBC 1503. |
| |
| 6. FBC 5TH EDITION EXISTING BUILDING, PLAN SHOULD |
| INCLUDE METHOD OF COMPLIANCE 301.1. |
| |
| 7. ROOF AND PLUMBING SUB PERMITS ARE REQUIRED, FS489. |
| |
| 8. THE PLAN IS TO INCLUDE ALL PERTINENT INFORMATION |
| REGARDING THE PROPOSED REROOF - ROOF PITCH, MEAN ROOF |
| HEIGHT, PARAPET INFO AND, IF APPLICABLE, PARAPET |
| HEIGHT. A PRODUCT APPROVAL WAS PROVIDED, A SYSTEM |
| HIGHLIGHTED, BUT IT DOES NOT APPEAR TO COMPLY WITH THE |
| DESIGN PRESSURES REQUIRED FOR THIS PROJECT. IT IS NOT |
| POSSIBLE TO DO A COMPLETE REVIEW WITHOUT THE |
| INFORMATION LISTED, FBC 1609. IF ENHANCED FASTENING IS |
| REQUIRED, PROVIDE AT THIS TIME (PREPARED BY A DESIGN |
| PROFESSIONAL). |
| |
| 9. IF INFORMATION REGARDING THE EXISTING BUILDING IS |
| NEEDED, A RECORDS RESEARCH REQUEST MAY BE SUBMITTED VIA |
| EMAIL TO [email protected]. |
| |
| |