Plan Review Notes For Permit 16070876 |
Permit Number |
16070876 |
|
Review Stop |
M |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2016-11-08 17:17:07 | PROVO: | | PLANS SHOW 1025 CFM OFSUPPLY AIR FROM SUPPLY OUTLETS. | | AS PER TRANE WEBSITE AHU SPECIFIED ON PLANS PROVIDES | | 1698 CFM ON MEDIUM SPEED. REVISE PLANS SHOWING PROPER | | AIR DISTRIBUTION AT FINAL INSPECTION. |
|