 PLUMBING COMMENTS: 1ST REVIEW
  
 1. SHT A-7 SANITARY RISER SIZE BRANCH TO LAUNDRY . PER
 WPB AMEND TO FBC 107.2.1
  
 2. THE STACK, P- TRAP-AND STAND PIPE FOR WASHING
 MACHINE SHALL BE MIN OF 2IN. PER FBC RES. TABLE P3201.7
  
 3. AT LEAST ONE OF THE VENTS SHALL EXTEND THROUGH ROOF
 . PER FBC RES.
 P3102.1 REQUIRED VENT EXTENSION.
 THE VENT SYSTEM SERVING EACH BUILDING DRAIN SHALL HAVE
 AT LEAST ONE VENT PIPE THAT EXTENDS TO THE OUTDOORS.
  
 4. PROVIDE CLEAN OUT OUT SIDE BUILDING PER FBC RES.
 P3005.2.7 BUILDING DRAIN AND BUILDING SEWER JUNCTION.
 THERE SHALL BE A CLEANOUT NEAR THE JUNCTION OF THE
 BUILDING DRAIN AND BUILDING SEWER. THIS CLEANOUT SHALL
 BE EITHER INSIDE OR OUTSIDE THE BUILDING WALL, PROVIDED
 THAT IT IS BROUGHT UP TO FINISH GRADE OR TO THE LOWEST
 FLOOR LEVEL. AN APPROVED TWO-WAY CLEANOUT SHALL BE
 PERMITTED TO SERVE AS THE REQUIRED CLEANOUT FOR BOTH
 THE BUILDING DRAIN AND THE BUILDING SEWER. THE CLEANOUT
 AT THE JUNCTION OF THE BUILDING DRAIN AND BUILDING
 SEWER SHALL NOT BE REQUIRED WHERE A CLEANOUT ON A
 3-INCH (76 MM) OR LARGER DIAMETER SOIL STACK IS LOCATED
 WITHIN A DEVELOPED LENGTH OF 10 FEET (3048 MM) OF THE
 BUILDING DRAIN AND BUILDING SEWER JUNCTION.
  
 5. SHOW LOCATION OF RELOCATED TANKLESS WATER HEATER ON
 ELEVATION DRAWING AND FLOOR PLAN TO SHOW COMPLIANCE
 WITH CLEARANCE TO OPENINGS IN MANUFACTURE INSTALLATION
 GUIDE. PER WPB AMEND.TO FBC 107.2.1
  
  
  