Plan Review Notes
Plan Review Notes For Permit 16070876
Permit Number 16070876
Review Stop M
Sequence Number 1
Notes
Date Text
2016-09-14 17:18:37CITY OF WEST PALM BEACH LOCAL AMENDMENTS TO THE FLORIDA
 BUILDING CODE (FBC) 2010 CHAPTER 1 ADMINISTRATION
  
 107.1 GENERAL ? 107.2 CONSTRUCTION DOCUMENTS ? 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENT
  
 (1) IDENTIFY ALL AREAS, ROOMS ON THE MECHANICAL PLANS.
 (2) AIR HANDLER UNIT MODEL #TEM4A0C48S41SA IS 48000
 BTU. MAKE CORRECTION ON PLANS
 (3) PROVIDE KITCHEN EXHAUST DUCT DETAIL ON PLANS. SHOW
 TERMINATION TO EXTERIOR OF HOME.
 (4) PROVIDE ANCHORING DETAIL FOR CONDENSER STAND TO
 ROOF AND CONDENSER TO CONDENSER STAND. MUST MEET FBC
 2014 WIND LOAD REQUIREMENTS.
  
  
 FLORIDA ENERGY CODE FBC 2014
  
 (5) FORMS R405 - 2014 MUST BE SIGNED BY OWNER/AGENT.
 (6) PROVIDE TWO SETS OF HEATLOAD CALCULATIONS FOR THE
 NEW ADDITION AREA.
  
 JORGE VALIDO
 WPB MECHANICAL INSPECTOR/PLANS EXAMINER
 [email protected]
 561-805-6716
  
  