Plan Review Notes For Permit 16070876 |
Permit Number |
16070876 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2016-09-14 17:18:37 | CITY OF WEST PALM BEACH LOCAL AMENDMENTS TO THE FLORIDA | | BUILDING CODE (FBC) 2010 CHAPTER 1 ADMINISTRATION | | | | 107.1 GENERAL ? 107.2 CONSTRUCTION DOCUMENTS ? 107.2.1 | | INFORMATION ON CONSTRUCTION DOCUMENT | | | | (1) IDENTIFY ALL AREAS, ROOMS ON THE MECHANICAL PLANS. | | (2) AIR HANDLER UNIT MODEL #TEM4A0C48S41SA IS 48000 | | BTU. MAKE CORRECTION ON PLANS | | (3) PROVIDE KITCHEN EXHAUST DUCT DETAIL ON PLANS. SHOW | | TERMINATION TO EXTERIOR OF HOME. | | (4) PROVIDE ANCHORING DETAIL FOR CONDENSER STAND TO | | ROOF AND CONDENSER TO CONDENSER STAND. MUST MEET FBC | | 2014 WIND LOAD REQUIREMENTS. | | | | | | FLORIDA ENERGY CODE FBC 2014 | | | | (5) FORMS R405 - 2014 MUST BE SIGNED BY OWNER/AGENT. | | (6) PROVIDE TWO SETS OF HEATLOAD CALCULATIONS FOR THE | | NEW ADDITION AREA. | | | | JORGE VALIDO | | WPB MECHANICAL INSPECTOR/PLANS EXAMINER | | [email protected] | | 561-805-6716 | | | | |
|