2016-08-03 10:20:51 | ELECTRICAL REVIEW NOTES |
| REVIEWED FOR COMPLIANCE WITH: |
| 5TH EDITION FBC 2014 & NFPA 70 2011 (NEC) |
| |
| PROJECT NAME: 2836 FLAGLER |
| JOB ADDRESS: 2836 FLAGLER |
| DESCRIPTION: SFR ADDITION |
| MASTER PERMIT:16070876 |
| |
| |
| 1. PLEASE LABEL ALL SPACES ON THE ELECTRICAL FLOOR PLAN |
| TO DETERMINE PROPER ELECTRICAL REQUIREMENTS. |
| 2. NEC 210.52(H): HALLWAYS GREATER THAN 10? SHALL HAVE |
| AT LEAST 1 RECEPTACLE. |
| 3. NEC 210.52(A)(2): OUTLETS ARE MISSING IN THE GREAT |
| ROOM. IF THERE IS NOT ENOUGH WALL SPACE TO MOUNT AN |
| ELECTRICAL OUTLET, YOU SHALL INSTALL FLOOR BOXES TO |
| MEET THE MINIMUM SPACING REQUIREMENTS. |
| 4. NEC 210.70(A)(2)(B): A LIGHT CONTROLLED BY A WALL |
| SWITCH IS REQUIRED ON THE EXTERIOR DOORS AT THE CABANA |
| AND REAR STORAGE. |
| 5. NEC 230.208: INDICATE THE SIZING OF THE PROTECTION |
| DEVICE FOR THE SERVICE AT THE MDP ON THE RISER DIAGRAM. |
| 6. NEC 408.36: INDICATE IF PANEL ?A? IS MCB OR MLO ON |
| THE RISER DIAGRAM. IF MCB INDICATE THE SIZE. |
| 7. NEC 250.94: YOU SHALL INCLUDE THE REQUIRED |
| INTER-SYSTEM BONDING TERMINAL AT THE NEW SERVICE |
| LOCATION AND SO REFLECTED ON THE RISER DIAGRAM. |
| 8. NEC 210.63: THOUGHT THERE IS NO ELECTRICAL SHEET |
| INDICATING THE LOCATION OF THE CONDENSING UNITS MOUNTED |
| ON THE ROOF, I DETERMINED FROM SHEET ?A4? THAT THERE |
| MAY BE MORE THAN THE REQUIRED 25? FROM THE SERVICE |
| OUTLET FOR ONE OR TWO OF THE UNITS. MAKE MENTION OF |
| THIS REQUIREMENT ON THE RESPECTIVE PAGE TO AVOID |
| MISSING THE REQUIREMENT. |
| |
| WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR |
| RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER |
| (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER |
| WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD |
| CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID |
| AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR |
| COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE |
| GREATLY APPRECIATED. |
| |
| IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO |
| CONTACT ME DIRECTLY. |
| |