2016-08-03 10:20:51ELECTRICAL REVIEW NOTES
 REVIEWED FOR COMPLIANCE WITH:
 5TH EDITION FBC 2014 & NFPA 70 2011 (NEC)
  
 PROJECT NAME: 2836 FLAGLER
 JOB ADDRESS: 2836 FLAGLER
 DESCRIPTION: SFR ADDITION
 MASTER PERMIT:16070876
  
  
 1. PLEASE LABEL ALL SPACES ON THE ELECTRICAL FLOOR PLAN
 TO DETERMINE PROPER ELECTRICAL REQUIREMENTS.
 2. NEC 210.52(H): HALLWAYS GREATER THAN 10? SHALL HAVE
 AT LEAST 1 RECEPTACLE.
 3. NEC 210.52(A)(2): OUTLETS ARE MISSING IN THE GREAT
 ROOM. IF THERE IS NOT ENOUGH WALL SPACE TO MOUNT AN
 ELECTRICAL OUTLET, YOU SHALL INSTALL FLOOR BOXES TO
 MEET THE MINIMUM SPACING REQUIREMENTS.
 4. NEC 210.70(A)(2)(B): A LIGHT CONTROLLED BY A WALL
 SWITCH IS REQUIRED ON THE EXTERIOR DOORS AT THE CABANA
 AND REAR STORAGE.
 5. NEC 230.208: INDICATE THE SIZING OF THE PROTECTION
 DEVICE FOR THE SERVICE AT THE MDP ON THE RISER DIAGRAM.
 6. NEC 408.36: INDICATE IF PANEL ?A? IS MCB OR MLO ON
 THE RISER DIAGRAM. IF MCB INDICATE THE SIZE.
 7. NEC 250.94: YOU SHALL INCLUDE THE REQUIRED
 INTER-SYSTEM BONDING TERMINAL AT THE NEW SERVICE
 LOCATION AND SO REFLECTED ON THE RISER DIAGRAM.
 8. NEC 210.63: THOUGHT THERE IS NO ELECTRICAL SHEET
 INDICATING THE LOCATION OF THE CONDENSING UNITS MOUNTED
 ON THE ROOF, I DETERMINED FROM SHEET ?A4? THAT THERE
 MAY BE MORE THAN THE REQUIRED 25? FROM THE SERVICE
 OUTLET FOR ONE OR TWO OF THE UNITS. MAKE MENTION OF
 THIS REQUIREMENT ON THE RESPECTIVE PAGE TO AVOID
 MISSING THE REQUIREMENT.
  
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER
 (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER
 WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD
 CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID
 AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR
 COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE
 GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  