Plan Review Notes For Permit 16070875
Permit Number 16070875
Review Stop M
Sequence Number 1
Notes
Date Text
2016-07-26 14:16:161ST REVIEW MECHANICAL
 PERMIT #16070875
 7/26/16
  
 1) THE MECHANICAL PLAN SHOWN ON SHEET 3.0P MUST BE
 REVISED TO SHOW THE NEW WALL FAN AND FAN EQUIPMENT
 SCHEDULE.
  
 2) CLARIFY THE PURPOSE OF THE FAN AND PROVIDE SIZING
 CALCULATIONS.
  
 3) INDICATE A SEQUENCE OF OPERATION FOR THE FAN.
  
 4) PROVIDE OPENING PROTECTION FOR THE FAN AS REQUIRED
 BY SECTIONS 401.4 AND 501.3.2
  
 5) SUBMIT MANUIFACTURER'S SPECIFICATIONS FOR THE GAS
 DRYERS REVIEWED AND APPROVED WITH SIGNATURE BY THE
 ENGINEER OF RECORD. IF THEY ARE EXISTING PLEASE LABEL
 THEM EXISTING ON THE PLANS.
  
 6) INDICATE HOW COMBUSTION AIR IS BEING PROVIDED FOR
 THE DRYERS AND PROVIDE CALCULATIONS- SEE SECTION 304
 FBC-14 FUEL GAS.
  
 7) PROVIDE DETAILS FOR THE DRYER EXHAUST DUCTS- TYPE
 AND SIZE OF DUCTS, AND DUCT SUPPORTS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  