2016-07-29 07:34:27 | BUILDING PLAN REVIEW |
| W. P. B. REVISION: 16070875 |
| W. P. B. PERMIT: 16020642 |
| ADD: 421 BELVEDERE RD. |
| CONT: L B ROWE |
| TEL: 835-1499 |
| E-MAIL: ???????????? |
| |
| 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION |
| |
| 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| FLORIDA BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE: FRI. JULY 29/2016 |
| ACTION: DENIED |
| |
| 1) SHEET 1.0A DETAIL WALL FAN INFILE, THE PLANS |
| INDICATE TO REMOVE THE 2 WINDOWS AND INSTALLING 2 |
| THROUGH THE WALL FANS. |
| |
| PLEASE REVIEW THE 2014 FBC-M 501.3.1 501.3.2 EXHAUST |
| OPENING PROTECTION. EXHAUST OPENINGS THAT TERMINATE |
| OUTDOORS SHALL BE PROTECTED WITH CORROSION-RESISTANT |
| SCREENS, LOUVERS OR GRILLES. OPENINGS IN SCREENS, |
| LOUVERS AND GRILLES SHALL BE SIZED NOT LESS THAN 1/4 |
| INCH (6 MM) AND NOT LARGER THAN 1/2 INCH (13 MM). |
| OPENINGS SHALL BE PROTECTED AGAINST LOCAL WEATHER |
| CONDITIONS. LOUVERS THAT PROTECT EXHAUST OPENINGS IN |
| STRUCTURES LOCATED IN HURRICANE-PRONE REGIONS, AS |
| DEFINED IN THE FLORIDA BUILDING CODE, BUILDING, SHALL |
| COMPLY WITH AMCA STANDARD 550. OUTDOOR OPENINGS LOCATED |
| IN EXTERIOR WALLS SHALL MEET THE PROVISIONS FOR |
| EXTERIOR WALL OPENING PROTECTIVES IN ACCORDANCE WITH |
| THE FLORIDA BUILDING CODE, BUILDING. |
| |
| 1609.6.4.4.1 COMPONENTS & CLADDING |
| |
| FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. |
| 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION |
| SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS: |
| (31)(B) WINDOWS |
| (C) PANEL WALLS: WALL LOUVERS, |
| (E) SHUTTERS |
| |
| 2) PLEASE PROVIDE THE VASD PRESSURES FOR THESE 2 |
| OPENINGS. 2014 FBC-B 1603.1.4 WIND DESIGN DATA (5) |
| COMPONENTS AND CLADDING PRESURES. |
| |
| 3) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |