Plan Review Notes
Plan Review Notes For Permit 16070837
Permit Number 16070837
Review Stop P
Sequence Number 2
Notes
Date Text
2016-11-02 13:23:441)2ND REQUEST THE CIVIL DRAWINGS ARE NOT SIGNED AND
 SEALED BY THE DESIGN PROFESSIONAL. FL. ADMIN. CODE RULE
 61G15-23.001. IT APPEARS THE CIVIL PAGES WHERE STAMPED
 BUT THEY MUST BE PERSONALLY SIGNED AND DATED
  
  
 19) 2ND REQUEST THE SEAT IN THE ACCESSIBLE SHOWER SHALL
 COMPLY WITH THE FAC SEC. 610.3. SUBMIT DETAILS. THE
 SEAT SHALL BE OF A FOLDING TYPE.
 SEAT SHOWN AT 15" SHOW COMPLIANCE WITH FBC ACC
 610.3 SHOWER COMPARTMENT SEATS.
 WHERE A SEAT IS PROVIDED IN A STANDARD ROLL-IN SHOWER
 COMPARTMENT, IT SHALL BE A FOLDING TYPE, SHALL BE
 INSTALLED ON THE SIDE WALL ADJACENT TO THE CONTROLS,
 AND SHALL EXTEND FROM THE BACK WALL TO A POINT WITHIN 3
 INCHES (75 MM) OF THE COMPARTMENT ENTRY. WHERE A SEAT
 IS PROVIDED IN AN ALTERNATE ROLL-IN TYPE SHOWER
 COMPARTMENT, IT SHALL BE A FOLDING TYPE, SHALL BE
 INSTALLED ON THE FRONT WALL OPPOSITE THE BACK WALL, AND
 SHALL EXTEND FROM THE ADJACENT SIDE WALL TO A POINT
 WITHIN 3 INCHES (75 MM) OF THE COMPARTMENT ENTRY. IN
 TRANSFER-TYPE SHOWERS, THE SEAT SHALL EXTEND FROM THE
 BACK WALL TO A POINT WITHIN 3 INCHES (75 MM) OF THE
 COMPARTMENT ENTRY. THE TOP OF THE SEAT SHALL BE 17
 INCHES (430 MM) MINIMUM AND 19 INCHES (485 MM) MAXIMUM
 ABOVE THE BATHROOM FINISH FLOOR. SEATS SHALL COMPLY
 WITH 610.3.1 OR 610.3.2.
  
 20) 2ND REQUEST THE WET BAR/SINK IN THE HANDICAPPED
 ACCESSIBLE UNIT SHALL COMPLY WITH THE FAC SECS.212.2,
 606. NO ACCESSIBILITY SHOWN FOR SINK
  
 24) 2ND REQUEST THE SHOWER CONTROLS IN THE ACCESSIBLE
 SHOWER SHALL COMPLY WITH THE FAC SECS.608.5.3.SHOW THE
 DISTANCE OF THE CONTROLS IN RELATION TO THE SEAT, FROM
 ADJACENT WALLS, ABOVE THE FLOOR, ETC.
 608.5.2 STANDARD ROLL-IN TYPE SHOWER COMPARTMENTS.
 WHERE A SEAT IS PROVIDED, THE CONTROLS, FAUCETS, AND
 SHOWER SPRAY UNIT SHALL BE INSTALLED ON THE BACK WALL
 ADJACENT TO THE SEAT WALL AND SHALL BE LOCATED 27
 INCHES (685 MM) MAXIMUM FROM THE SEAT WALL ABOVE THE
 GRAB BAR, BUT NO HIGHER THAN 48 INCHES.
  
 26) 2ND REQUEST SHT. A8.11 DETAIL #5 REFERENCES THE
 2010 FBC /FHA. THESE DETAILS DO NOT APPLY. THE CODE IN
 EFFECT IS THE 2014 FBC-ACCESSIBILITY.
  
 29) 2ND REQUEST SPEC SUBMITTED ARE NOT FROM MANUFACTURE
 SUBMIT SPECIFICATIONS FOR THE PUMPS FOR THE LAUNDRY.
 WPB AMEND. TO FBC SEC. 107.2.1.
  
 30) 2ND REQUEST SPEC SUBMITTED ARE NOT FROM MANUFACTURE
 SUBMIT MANUF. SPECIFICATIONS /DETAILS FOR THE GAS WATER
 HEATERS. SUBMIT VENT DETAILS (SIZE, TYPE OF PIPE,
 ETC.).COMPLY WITH FGC SEC.502, 503, 504.
  
 31) 2ND REQUEST COULD NOT LOCATE ON MECHANICAL PAGES
 SUBMIT CALCULATIONS FOR COMBUSTION AIR IN ACCORDANCE
 WITH THE 2014 FBC-GAS SEC.304.
  
 32) 2ND REQUEST NOT COMPLIED SHOW THE DISTANCE OF THE
 GAS WATER HEATER VENTS FROM BUILDING OPENINGS. COMPLY
 WITH FGC SEC. 503.6.4.
  
 33) 2ND REQUEST SPEC SUBMITTED ARE NOT FROM MANUFACTURE
 SUBMIT MANUF. SPECIFICATIONS /DETAILS FOR THE DRYERS.
 SUBMIT VENT DETAILS (SIZE, TYPE OF MATERIAL,
 TERMINATION POINTS, ETC.).
  
 34) 2ND REQUEST COULD NOT LOCATE ON MECHANICAL PAGES
 CARBON MONOXIDE SENSORS ARE REQUIRED PER THE 2014 FBC
 SEC. 908.7.
  
 NEW COMMENTS:
  
 1. SHT. A7.02 THE ROLL IN SHOWER SHALL BE MIN 30" X 60"
 PER FBC ACC SEC 608.2.2
  
 2. SHT 7.02 SHOW CLEAR FLOOR SPACE FOR ROLL IN SHOWER.
 PER FBC ACC 608.2.2.1
  
 3. THE ACCESSIBLE SUITE #2 ON THE 2ND FLOOR IS SHOWN AS
 A STANDARD ROOM ON THE PLUMBING SHEETS PLEASE CLARIFY.
 PER WPB AMEND TO FBC 107.2.1
  
 4. ON THE PLUMBING SHEETS IT SHOWS A SINK INSIDE THE
 SAUNA ON SHT, A7.02 IT SHOWS A SAUNA HEATER PLEASE
 CLARIFY . PER WPB AMEND TO FBC 107.2.1
  
 5. MODEL PS-15-B LINT TRAP IS EQUIPPED WITH A 2" INLET
 AND OUTLET YOU WILL BE REQUIRED TO USE A MODEL THAT IS
 EQUIPPED WITH A 3" INLET AND OUTLET THE DRAIN FROM THE
 LAUNDRY IS REQUIRED TO-BE 3' AND YOU CAN NOT REDUCE THE
 PIPE SIZE IN THE DIRECTION OF FLOW. PER FBC PL 406.2 /
 704.2
  
 6. THE PLUMBING SCHEDULE SHOWS P-3 AS A TUB AND IT
 SHOWS P-4 AS A SHOWER ON THE FLOOR PLAN AND THE RISER
 THE SHOWER IS SHOWN AS A P-3 PLEASE CLARIFY. PER WPB
 AMEND TO FBC 107.2.1
  
 7. THE VENT FOR THE HUB DRAIN IN THE TRASH ROOM THAT IS
 TERMINATING OUT OF THE SIDE WALL SHALL COMPLY WITH FBC
 PL903.5 / 903.6
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
  
  
  
  
  
  
  
  
  
  
  
  
  