2016-10-24 12:20:052ND REVIEW FBC-2014 MECHANICAL
 PERMIT #16070837
 10/24/16
  
 1) SHEET M-100: REFER TO TABLE 6-4 ASHRAE 62.1-2010 AND
 PROVIDE EXHAUST VENTILATION AND CALCULATIONS FOR THE
 SOILED LINEN STORAGE ROOM. THIS REQUIREMENT WAS MISSED
 IN THE FIRST REVIEW DUE TO THE ROOMS NOT IDENTIFIED ON
 THE MECHANICAL PLANS. PLEASE IDENTIFY ALL ROOMS ON ALL
 FLOORS OF THE BUILDING.
  
 2) M3.01: PLEASE INCLUDE THE BOH ROOM IN THE
 VENTILATION CALCULATIONS.
  
 3) M1.01: PROVIDE A MOTORIZED DAMPER FOR THE 12X10 O/A
 INTAKE DUCT TO FCU-B.
  
 4) FCU-B HEATING CAPACITY AT 12 KW IS UNDERSIZED PER
 THE CALCS WHCIH INDICATE A 16.5 KW LOAD.
  
 5 ) PLEASE PROVIDE AN EQUIPMENT SCHEDULE FOR ALL THE
 REQUIRED WALL AND CEILING FIRE DAMPERS, AND PROVIDE
 INSTALLTION DETAILS ON THE PLANS.
  
 6) IN REFERENCE TO COMMENT #4 REQUESTING SPECS FOR THE
 DRYER, PLEASE NOTE THAT THE LENGTH OF EXHAUST RUN
 APPEARS TO EXCEED THE 35 FT. MAXIMUM LENGTH PER SECTION
 504.6.4.1. THE MANUFACTURERS SPECIFICATIONS MUST
 INDICATE THIS MAXIMUM LENGTH CAN BE EXCEEDED.
  
 7) LABEL THE ACCESS PANELS TO THE FCU'S OR PROVIDE A
 GENERAL NOTE.
  