Plan Review Notes For Permit 16070837 |
Permit Number |
16070837 |
|
Review Stop |
FIRE |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2016-10-21 10:26:11 | THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC, | | FIRE MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | PLEASE CONSIDER THE FOLLOWING AS PROVISO: | | | | THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED | | AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE | | PROVISO COMMENTS WILL RESULT IN A FAILED FIRE | | INSPECTION. | | | | 1) PLEASE PROVIDE OFFICIAL REVISIONS FOR THE MECHANICAL | | SMOKE CONTROL/VENTILATION OF THE BASEMENT FOR APPROVAL. | | | | | | 2) PLEASE COORDINATE AN ALTERNATIVE LOCATION FOR THE | | FACP WITH BUREAU. | | | | | | | | PETER LEDUC | | FIRE MARSHAL | | 561-804-4709 | | [email protected] | | | | |
|