2016-11-08 15:11:53 | BUILDING PLAN REVIEW |
| W. P. B. PERMIT: 16070837 |
| ADD: 309/317 N. ROSEMARY AVE. |
| CONT: TBD/ TO BE DETERMINED |
| TEL: 305-456-7252 |
| E-MAIL: [email protected] |
| |
| 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION |
| |
| 2ND REVIEW |
| DATE: TUES. NOV. 08/2016 |
| ACTION: DENIED |
| |
| 1) 2ND REQUEST. THE PERMIT APPLICATION HAS 2 DIFFERENT |
| ADDRESSES LISTED FOR THE SITE, A SITE CAN ONLY HAVE ONE |
| LEGAL ADDRESS. THE 2ND ISSUE OF UNITY OF TITLE, |
| RESPONSE INDICATES SEE ATTACHED UNITY OF TITLE, NOT |
| ATTACHED TO THE BUILDING RESPONSE DOCUMENT. NOTE A |
| WARRANTY DEED WAS SUBMITTED FOR 3 LOTS!!! |
| |
| 1ST REVIEW COMMENTS. PLEASE NOTE AN ADDRESSING PLAN |
| REVIEW STOP WILL BE ADDED TO THE PLAN REVIEW CYCLE TO |
| ASSIGN A SITE ADDRESS. IT APPEARS ON THE PALM BCH. |
| COUNTY PROPERTY APPRAISERS WEBSITE THERE ARE 3 ACTUAL |
| PROPERTIES THAT WILL BE MAKING UP THIS SITE. |
| 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION 107.2.1 INFORMATION ON CONSTRUCTION |
| DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL BE OF |
| SUFFICIENT CLARITY TO INDICATE THE LOCATION OF THE |
| PROJECT. PLEASE CONTACT MR. ORIO FOR AN SITE ADDRESS. |
| CONTACT: MICHAEL ORIO GIS SUPPORT SPECIALIST/ |
| INFORMATION TECHNOLOGY |
| TEL: 561-494-1040. |
| E-MAIL: [email protected] |
| |
| 2) PROVISO: ART IN PUBLIC PLACES. THE CITY OF WEST PALM |
| BEACH ART IN PUBLIC PLACES ORDINANCE REQUIREMENT THAT |
| APPLIES TO ANY REMODEL OR NEW CONSTRUCTION PROJECT FOR |
| WHICH THE PERMIT APPLICATION WAS SUBMITTED AFTER |
| 6/29/2014, AND THE TOTAL PROJECT CONSTRUCTION COSTS ARE |
| EQUAL TO OR GREATER THAN $750,000 |
| WILL NEED TO COMPLY WITH THIS ORDINANCE. |
| PER CITY OF WEST PALM BEACH ORDINANCE NO. 4504-14, AND |
| CITY OF WEST PALM BEACH CODE OF ORDINANCES, ARTICLE V, |
| ART IN PUBLIC PLACES, SECTION 78-123(A) AND SECTION |
| 78-126(A), THE ART ASSESSMENT IS 1% OF THE TOTAL |
| PROJECT CONSTRUCTION COST. |
| PER CITY OF WEST PALM BEACH CODE OF ORDINANCES, ARTICLE |
| V, ART IN PUBLIC PLACES, SECTION 78-122, RENOVATION AND |
| NEW CONSTRUCTION PROJECTS ARE ASSESSED CUMULATIVELY, SO |
| THE ART ASSESSMENT WILL BE APPLICABLE TO ALL FUTURE |
| PROJECTS. |
| FOR CONTACT INFORMATION PLEASE CONTACT: |
| MS. SYBILLE WELTER ART IN PUBLIC PLACES COORDINATOR |
| 822-1515 E-MAIL: [email protected] |
| |
| 3) 2ND REQUEST, THIS MAY HAVE TO WAIT UNTIL A |
| CONTRACTOR SIGNS ON AND THE PERMIT VALUES TO BE |
| SUBTRACTED WOULD BE ON THE CONTRACTORS LETTER HEAD. |
| 1ST ROUND OF COMMENTS. THIS MAIN BUILDING PERMIT WILL |
| INCLUDE THE FEES FOR THE MECHANICAL, ELECTRICAL, |
| PLUMBING & ROOFING PERMITS. WHEN THE GENERAL CONTRACTOR |
| COMES IN FOR A BUILDING PERMIT WITH THE SIGNED PERMIT |
| APPLICATION FORM BY THE QUALIFIER AND OWNER AND BRINGS |
| IN THE LISTED SUB-PERMITS M-E-P & ROOFING PERMITS |
| SIGNED BY THE QUALIFIER OF EACH COMPANY, THEIR |
| INSURANCES AND LICENSURE UP TO DATE, THE M-E-P AND |
| ROOFING PERMITS ARE FREE OF CHARGE. IF THE M-E-P & |
| ROOFING PERMITS COME IN LATER THERE WILL BE AN $80.00 |
| ADMINISTRATIVE FEE FOR EACH PERMIT. |
| |
| ALL OTHER PERMITS FIRE SPRINKLER, FIRE ALARM, EXHAUST |
| HOODS, ANSUL SYSTEMS OR ALTERNATIVE AUTOMATIC |
| FIRE-EXTINGUISHING SYSTEMS , WALK IN COOLERS & |
| FREEZERS, ALL LOW VOLTAGE PERMITS, GENERATORS & FUEL |
| TANKS, GAS PERMIT, POOL, JACUZZI AND ASSOCIATED |
| SUB-PERMITS, AWNING, CANOPY, FENCE, LANDSCAPE , |
| IRRIGATION, AUGER CAST PILE AND OR FOUNDATION OR |
| STRUCTURE ONLY PERMIT WILL BE SEPARATE REVIEWS AND |
| ASSOCIATED FEES WITH EACH PERMIT. |
| PLEASE LIST AND SUBTRACT THESE LINE ITEMS AND THEIR |
| VALUE FROM THE OVERALL BUILDING VALUE OF $4,088000.00. |
| THE REMAINING BALANCE WILL BE AFFECTIVELY THE VALUE OF |
| THE BUILDING YOU WILL BE PAYING FOR THIS PERMIT. THE |
| BUILDING DOES NOT WANT TO COLLECT TWICE FOR THE VALUE |
| OF THESE SUB-PERMITS NOT COVERED UNDER THE PRIME OR |
| MASTER PERMIT. |
| |
| 4)THIS BUILDING IS A THRESHOLD BUILDING / FL S. S. |
| 553.71(7) ?THRESHOLD BUILDING" MEANING ANY BUILDING |
| WHICH IS GREATER THAN (3) STORIES OR 50 FT. IN HEIGHT, |
| OR WHICH HAS AN ASSEMBLY OCCUPANCY CLASSIFICATION AS |
| DENIED IN THE FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 |
| SQ. FT. IN AREA AND AN OCCUPANT CONTENT OF GREATER THAN |
| 500 PERSONS. |
| |
| 4A) 2ND REQUEST. RESPONSE DOCUMENT INDICATED 3 SETS OF |
| THE THRESHOLD INSPECTION PLAN WERE SUBMITTED, ONLY IN |
| REVIEWING THE DOCUMENTS ONLY 2 SETS OF DOCUMENTS WERE |
| SUBMITTED. |
| 1ST ROUND OF COMMENTS. 109.3.6.1 THRESHOLD INSPECTION |
| PLAN. THE ENFORCING AGENCY SHALL REQUIRE A (WRITTEN/ |
| TYPED) SPECIAL INSPECTOR TO PERFORM STRUCTURAL |
| INSPECTIONS ON A THRESHOLD BUILDING PURSUANT TO A |
| STRUCTURAL INSPECTION PLAN PREPARED BY THE ENGINEER OF |
| RECORD. THE STRUCTURAL INSPECTION PLAN MUST BE |
| SUBMITTED TO THE ENFORCING AGENCY PRIOR TO THE ISSUANCE |
| OF A BUILDING PERMIT FOR THE CONSTRUCTION OF A |
| THRESHOLD BUILDING. THE PURPOSE OF THE STRUCTURAL |
| INSPECTION PLAN IS TO PROVIDE SPECIFIC INSPECTION |
| PROCEDURES AND SCHEDULES SO THAT THE BUILDING CAN BE |
| ADEQUATELY INSPECTED FOR COMPLIANCE WITH THE PERMITTED |
| DOCUMENTS. |
| |
| 4B) 2ND REQUEST. THRESHOLD INSPECTOR: WPB AMENDMENT |
| 109.3.6.2 W.P.B. CONSTRUCTION SERVICES DEPARTMENT |
| REQUEST FOR THRESHOLD BUILDINGS A SPECIAL INSPECTOR AS |
| REQUIRED BY FL S S 553.79(5) FLORIDA STATUTES TO THE |
| MINIMUM INSPECTIONS REQUIRED BY THIS CODE. THE |
| THRESHOLD INSPECTION FORMS ARE REQUIRED TO BE FILED OUT |
| BY ALL PARTIES WITH INTEREST, NOTARIZED AND RETURNED TO |
| THIS OFFICE, AND REVIEWED AND APPROVED BEFORE PERMIT |
| ISSUANCE WILL TAKE PLACE. |
| FORMS E-MAILED TO: [email protected] DATE: |
| 11/08/2016 9:08 AM |
| |
| |
| 4C) 2ND REQUEST. THRESHOLD BLDG., REQUIRED STATEMENT: |
| W.P.B. AMENDMENT 110.3.7.4.4 ALL PLANS FOR THE BUILDING |
| WHICH ARE REQUIRED TO BE SIGNED AND SEALED BY THE |
| ARCHITECT OR ENGINEER OF RECORD CONTAIN A STATEMENT |
| THAT, TO THE BEST OF THE ARCHITECT'S OR ENGINEER'S |
| KNOWLEDGE, THE PLANS AND SPECIFICATIONS COMPLY WITH THE |
| APPLICABLE FIRE-SAFETY STANDARDS AS DETERMINED BY THE |
| LOCAL AUTHORITY IN ACCORDANCE WITH THIS SECTION AND 633 |
| FLORIDA STATUTE. |
| |
| 4D) 2ND REQUEST. FOR THE SPECIAL INSPECTOR PLEASE |
| PROVIDE A RESUME' OF INSPECTION EXPERIENCE ON PREVIOUS |
| PROJECT. THE RESUME' MUST BE ACCOMPANIED BY ALL |
| CERTIFICATES AS SPECIFIED HEREIN. THE BUILDING OFFICIAL |
| OR HIS DESIGNEE WILL REVIEW THE RESUME'. AFTER THE |
| RESUME' IS REVIEWED, AN INTERVIEW WILL BE SCHEDULED. |
| UNDER NO CIRCUMSTANCES WILL AN INSPECTOR BE INTERVIEWED |
| FOR WORK WITHOUT FIRST MEETING THE ABOVE CRITERIA. |
| |
| 4E) 2ND REQUEST. THE CONTRACTOR WILL PRODUCE A JOB |
| SUMMARY OR HISTORY FOR THIS TYPE OF CONSTRUCTION. |
| |
| 4F) 2ND REQUEST. NOTE FOR PAPER PLANS 3 SETS OF |
| DOCUMENTS ARE REQUIRED. FOR DIGITAL PLANS, AFTER PERMIT |
| ISSUANCE, PLEASE E-MAIL THE PERMIT LIBRARIAN OF THE |
| PERMIT BEING ISSUED, THE PERMIT LIBRARIAN WILL THEN |
| E-MAIL YOU THE APPROVED AND BATCH STAMPED PLANS SO YOU |
| MAY PRINT YOUR PLANS, TWO SETS OF PLANS WILL NEED TO BE |
| PRINTED IN COLOR, (1) FOR THE THRESHOLD INSPECTOR, THE |
| OTHER FOR THE MEP INSPECTORS OTHER PLANS YOU WISH TO |
| PRINT MAYBE IN BLACK & WHITE.. |
| 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| CODE, CHAPTER 1, ADMINISTRATION, 110.3.7 THRESHOLD |
| BUILDINGS, GUIDELINES AND POLICIES FOR PROJECTS |
| CONCERNING SPECIAL INSPECTORS. |
| |
| 4G) 2ND REQUEST. 110.3.7.4.3 ALL SHORING AND RESHORING |
| PROCEDURES, PLANS AND DETAILS SHALL BE SUBMITTED TO THE |
| ENFORCEMENT AGENCY FOR RECORDKEEPING. EACH SHORING AND |
| RESHORING INSTALLATION SHALL BE SUPERVISED, INSPECTED |
| AND CERTIFIED TO BE IN COMPLIANCE WITH THE SHORING |
| DOCUMENTS BY THE CONTRACTOR. |
| |
| 4H) PROVISO: PLEASE CALL THE CITY OF WEST PALM BEACHS |
| AUTOMATED TELEPHONE INSPECTIONS LINE (561) 805-6700) |
| FOR ALL BUILDING INSPECTIONS FOR AUDITING OF JOBSITE |
| INSPECTIONS WITHOUT THIS THE PERMIT EXPIRES IN 6 |
| MONTHS, ABANDONMENT OF JOB, NO INSPECTION ACTIVITY. |
| |
| 4I) PROVISO: 109.3.6 THRESHOLD BUILDINGS, OPERATING |
| GUIDELINES FOR THRESHOLD INSPECTORS #26. ASSURE THAT |
| THE DESIGNER HAS REQUIRED ON THE PLANS OR |
| SPECIFICATIONS ONE MATERIAL, APPROVED FOR FIRE STOPPING |
| PENETRATIONS, FOR WALLS AND CEILINGS. |
| |
| 5) 2ND REQUEST. PERIMETER FENCING UNDER A SEPARATE |
| PERMIT. PLEASE PROVIDE COMPLIANCE WITH: 2014 FBC-B |
| 3306.5 BARRIERS. BARRIERS SHALL BE A MINIMUM OF 8 FEET |
| (2438 MM) IN HEIGHT AND SHALL BE PLACED ON THE SIDE OF |
| THE WALKWAY NEAREST THE CONSTRUCTION. BARRIERS SHALL |
| EXTEND THE ENTIRE LENGTH OF THE CONSTRUCTION SITE. |
| |
| 6) 2ND REQUEST. 2014 FBC0B 3306.2 WALKWAYS. A WALKWAY |
| SHALL BE PROVIDED FOR PEDESTRIAN TRAVEL IN FRONT OF |
| EVERY CONSTRUCTION AND DEMOLITION SITE UNLESS THE |
| APPLICABLE GOVERNING AUTHORITY AUTHORIZES THE SIDEWALK |
| TO BE FENCED OR CLOSED. WALKWAYS SHALL BE OF SUFFICIENT |
| WIDTH TO ACCOMMODATE THE PEDESTRIAN TRAFFIC, BUT IN NO |
| CASE SHALL THEY BE LESS THAN 4 FEET (1219 MM) IN WIDTH. |
| WALKWAYS SHALL BE PROVIDED WITH A DURABLE WALKING |
| SURFACE. WALKWAYS SHALL BE ACCESSIBLE IN ACCORDANCE |
| WITH CHAPTER 11 AND SHALL BE DESIGNED TO SUPPORT ALL |
| IMPOSED LOADS AND IN NO CASE SHALL THE DESIGN LIVE LOAD |
| BE LESS THAN 150 POUNDS PER SQUARE FOOT (PSF). WILL THE |
| WALKWAYS ON THE SOUTH SIDE OF TRINITY PLACE BE CLOSED? |
| |
| 7) 2ND REQUEST. 2014 FBC-B 3306.7 COVERED WALKWAYS. |
| COVERED WALKWAYS SHALL HAVE A CLEAR HEIGHT OF NOT LESS |
| THAN 8 FEET (2438 MM) AS MEASURED FROM THE FLOOR |
| SURFACE TO THE CANOPY OVERHEAD. ADEQUATE LIGHTING SHALL |
| BE PROVIDED AT ALL TIMES. COVERED WALKWAYS SHALL BE |
| DESIGNED TO SUPPORT ALL IMPOSED LOADS. IN NO CASE SHALL |
| THE DESIGN LIVE LOAD BE LESS THAN 150 PSF FOR THE |
| ENTIRE STRUCTURE. |
| |
| 8) 2ND REQUEST. PLEASE PROVIDE COMPLIANCE WITH: |
| POLLUTION PREVENTION PLAN. 2014 FBC-B 3307.1 PROTECTION |
| REQUIRED. ADJOINING PUBLIC AND PRIVATE PROPERTY SHALL |
| BE PROTECTED FROM DAMAGE DURING CONSTRUCTION, |
| REMODELING AND DEMOLITION WORK. PROVISIONS SHALL BE |
| MADE TO CONTROL WATER RUNOFF AND EROSION DURING |
| CONSTRUCTION OR DEMOLITION ACTIVITIES. THE PERSON |
| MAKING OR CAUSING AN EXCAVATION TO BE MADE SHALL |
| PROVIDE WRITTEN NOTICE TO THE OWNERS OF ADJOINING |
| BUILDINGS ADVISING THEM THAT THE EXCAVATION IS TO BE |
| MADE AND THAT THE ADJOINING BUILDINGS SHOULD BE |
| PROTECTED. SAID NOTIFICATION SHALL BE DELIVERED NOT |
| LESS THAN 10 DAYS PRIOR TO THE SCHEDULED STARTING DATE |
| OF THE EXCAVATION. |
| |
| 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION 109.3.10 IMPACT OF CONSTRUCTION. ALL |
| CONSTRUCTION ACTIVITY REGULATED BY THIS CODE SHALL BE |
| PERFORMED IN A MANNER SO AS NOT TO ADVERSELY IMPACT THE |
| CONDITION OF ADJACENT PROPERTY, UNLESS SUCH ACTIVITY IS |
| PERMITTED TO AFFECT SAID PROPERTY PURSUANT TO CONSENT |
| BY THE APPLICABLE PROPERTY OWNER, UNDER TERMS & |
| CONDITIONS AGREEABLE TO THE APPLICABLE PROPERTY OWNER. |
| THIS INCLUDES BUT IS NOT LIMITED TO THE CONTROL OF |
| DUST, NOISE, WATER OR DRAINAGE RUN-OFF, DEBRIS, AND THE |
| STORAGE OF CONSTRUCTION MATERIALS. NEW CONSTRUCTION |
| ACTIVITY SHALL NOT ADVERSELY IMPACT HISTORIC SURFACE |
| WATER DRAINAGE FLOWS SERVING ADJACENT PROPERTIES, & MAY |
| REQUIRE SPECIAL DRAINAGE DESIGN COMPLYING WITH |
| ENGINEERING STANDARDS TO PRESERVE THE POSITIVE PATTERNS |
| OF THE AFFECTED SITES. ACCORDINGLY, DEVELOPERS, |
| CONTRACTORS, AND OWNERS OF ALL NEW RESIDENTIAL |
| DEVELOPMENT, INCLUDING ADDITIONS, POOLS, PATIOS, |
| DRIVEWAYS, DECKS, OR SIMILAR ITEMS, ON EXISTING |
| PROPERTIES RESULTING IN A DECREASE IN EXCESS OF 800SQ. |
| FT. OF PERMEABLE LAND AREA ON ANY PARCEL SHALL AS A |
| PERMIT CONDITION, PROVIDE A PROFESSIONALLY PREPARED |
| DRAINAGE PLAN CLEARLY INDICATING COMPLIANCE WITH THIS |
| PARAGRAPH. UPON COMPLETION OF THE IMPROVEMENT, A |
| CERTIFICATION FROM A LICENSED ENGINEER SHALL BE |
| SUBMITTED TO THE INSPECTOR IN ORDER TO RECEIVE APPROVAL |
| OF THE FINAL INSPECTION. |
| |
| 9) 2ND REQUEST. PLEASE PROVIDE DETAILS SHOWING HOW |
| COMPLIANCE WITH 2014 FBC-B 3306.9 ADJACENT TO |
| EXCAVATIONS. |
| EVERY EXCAVATION ON A SITE LOCATED 5 FEET (1524 MM) OR |
| LESS FROM THE STREET LOT LINE SHALL BE ENCLOSED WITH A |
| BARRIER NOT LESS THAN 6 FEET (1829 MM) IN HEIGHT. WHERE |
| LOCATED MORE THAN 5 FEET (1524 MM) FROM THE STREET LOT |
| LINE, A BARRIER SHALL BE ERECTED WHERE REQUIRED BY THE |
| BUILDING OFFICIAL. BARRIERS SHALL BE OF ADEQUATE |
| STRENGTH TO RESIST WIND PRESSURE AS SPECIFIED IN |
| CHAPTER 16. SHEET A2.01A & S-1 SHOW PILING RIGHT |
| ADJACENT TO THE PROPERTY LINE SEE COLUMN 1 AND ROW A . |
| |
| 10A) 2ND REQUEST. PLEASE PROVIDE DETAILS SHOWING |
| COMPLIANCE WITH 2014 FBC-B 3307.1 PROTECTION REQUIRED. |
| ADJOINING PUBLIC AND PRIVATE PROPERTY SHALL BE |
| PROTECTED FROM DAMAGE DURING CONSTRUCTION AND |
| DEMOLITION WORK. PROTECTION SHALL BE PROVIDED FOR |
| FOOTINGS, FOUNDATIONS, PARTY WALLS, CHIMNEYS, SKYLIGHTS |
| AND ROOFS. WITH THE EXCAVATION AND AUGER CAST PILE HOW |
| WILL THE BUILDING TO THE SOUTH BE PROTECTED FROM |
| SETTLEMENT? |
| SHEET A2.01A & S-1 SHOW PILING RIGHT ADJACENT TO THE |
| PROPERTY LINE SEE COLUMN 1 AND ROW A . |
| |
| 10B) 2ND REQUEST. 2014 FBC-B 3307.1 THE PERSON MAKING |
| OR CAUSING AN EXCAVATION TO BE MADE SHALL PROVIDE |
| WRITTEN NOTICE TO THE OWNERS OF ADJOINING BUILDINGS |
| ADVISING THEM THAT THE EXCAVATION IS TO BE MADE AND |
| THAT THE ADJOINING BUILDINGS SHOULD BE PROTECTED. SAID |
| NOTIFICATION SHALL BE DELIVERED NOT LESS THAN 10 DAYS |
| PRIOR TO THE SCHEDULED STARTING DATE OF THE EXCAVATION. |
| SHEET A2.01A & S-1 SHOW PILING RIGHT ADJACENT TO THE |
| PROPERTY LINE SEE COLUMN 1 AND ROW A . |
| |
| 11) 2ND REQUEST. WHEN EXCAVATING WILL THE EXCESS SOILS |
| BE STORED ON SITE? 2014 FBC-B 3304.1.2 SURCHARGE. NO |
| FILL OR OTHER SURCHARGE LOADS SHALL BE PLACED ADJACENT |
| TO ANY BUILDING OR STRUCTURE UNLESS SUCH BUILDING OR |
| STRUCTURE IS CAPABLE OF WITHSTANDING THE ADDITIONAL |
| LOADS CAUSED BY THE FILL OR SURCHARGE. EXISTING |
| FOOTINGS OR FOUNDATIONS WHICH CAN BE AFFECTED BY ANY |
| EXCAVATION SHALL BE UNDERPINNED ADEQUATELY OR OTHERWISE |
| PROTECTED AGAINST SETTLEMENT AND SHALL BE PROTECTED |
| AGAINST LATER MOVEMENT. |
| |
| 12) 2ND REQUEST. PLEASE DOCUMENT COMPLIANCE WITH: 2014 |
| FBC-B 3313.1 WHERE REQUIRED. AN APPROVED WATER SUPPLY |
| FOR FIRE PROTECTION, EITHER TEMPORARY OR PERMANENT, |
| SHALL BE MADE AVAILABLE AS SOON AS COMBUSTIBLE MATERIAL |
| ARRIVES ON THE SITE. PLEASE PROVIDE WHERE THIS |
| CONNECTION WILL BE MADE. |
| |
| 13) 2ND REQUEST. NOTICE: 2014 FBC-B [F] 3311.1 WHERE |
| REQUIRED. IN BUILDINGS REQUIRED TO HAVE STANDPIPES BY |
| SECTION 905.3.1, NOT LESS THAN ONE STANDPIPE SHALL BE |
| PROVIDED FOR USE DURING CONSTRUCTION. SUCH STANDPIPES |
| SHALL BE INSTALLED WHEN THE PROGRESS OF CONSTRUCTION IS |
| NOT MORE THAN 40 FEET (12 192 MM) IN HEIGHT ABOVE THE |
| LOWEST LEVEL OF FIRE DEPARTMENT VEHICLE ACCESS. SUCH |
| STANDPIPE SHALL BE PROVIDED WITH FIRE DEPARTMENT HOSE |
| CONNECTIONS AT ACCESSIBLE LOCATIONS ADJACENT TO USABLE |
| STAIRS. SUCH STANDPIPES SHALL BE EXTENDED AS |
| CONSTRUCTION PROGRESSES TO WITHIN ONE FLOOR OF THE |
| HIGHEST POINT OF CONSTRUCTION HAVING SECURED DECKING OR |
| FLOORING. |
| |
| 14A) 2ND REQUEST. 2014 FBC-B [F] 3309.1 WHERE REQUIRED. |
| ALL STRUCTURES UNDER CONSTRUCTION SHALL BE PROVIDED |
| WITH NOT LESS THAN ONE APPROVED PORTABLE FIRE |
| EXTINGUISHER IN ACCORDANCE WITH SECTION 906 AND SIZED |
| FOR NOT LESS THAN ORDINARY HAZARD AS FOLLOWS: |
| 1. AT EACH STAIRWAY ON ALL FLOOR LEVELS WHERE |
| COMBUSTIBLE MATERIALS HAVE ACCUMULATED. |
| 2. IN EVERY STORAGE AND CONSTRUCTION SHED. |
| 3. ADDITIONAL PORTABLE FIRE EXTINGUISHERS SHALL BE |
| PROVIDED WHERE SPECIAL HAZARDS EXIST, SUCH AS THE |
| STORAGE AND USE OF FLAMMABLE AND COMBUSTIBLE LIQUIDS. |
| |
| 14B) 2ND REQUEST. 2014 FBC-B 3309.2 FIRE HAZARDS. THE |
| PROVISIONS OF THIS CODE AND THE FLORIDA FIRE PREVENTION |
| CODE SHALL BE STRICTLY OBSERVED TO SAFEGUARD AGAINST |
| ALL FIRE HAZARDS ATTENDANT UPON CONSTRUCTION |
| OPERATIONS. |
| |
| 15) 2ND REQUEST. 2014 FLORIDA BUILDING CODE W 2014 WEST |
| PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| CHAPTER 1, ADMINISTRATION 109.3.10.1 HURRICANE |
| PROTECTION. IT SHALL BE UNLAWFUL FOR ANY PERSON TO |
| ALLOW CONSTRUCTION RELATED MATERIALS EQUIPMENT AND |
| DEBRIS TO REMAIN LOOSE OR OTHERWISE UNSECURED AT A |
| CONSTRUCTION SITE FROM 24 HRS. AFTER A HURRICANE WATCH |
| HAS BEEN ISSUED UNTIL THE HURRICANE WATCH OR WARNING |
| HAS BEEN LIFTED. ALL SUCH CONSTRUCTION MATERIALS, |
| EQUIPMENT AND DEBRIS SHALL BE EITHER REMOVED FROM THE |
| CONSTRUCTION SITE OR SECURED IN SUCH A MANNER AS TO |
| MINIMIZE THE DANGER OF SUCH CONSTRUCTION MATERIALS, |
| EQUIPMENT AND DEBRIS CAUSING DAMAGE TO PERSONS OR |
| PROPERTY FROM HIGH WINDS. ANY PERSONS WHO FAILS TO |
| COMPLY TO COMPLY TO REMOVE OR SECURE THE CONSTRUCTION |
| MATERIALS EQUIPMENT AND DEBRIS WITHIN 24 HRS. AFTER A |
| HURRICANE WATCH HAS BEEN ISSUED SHALL BE SUBJECT TO A |
| FINE NOT TO EXCEED $500.00. IN ADDITION TO THE ABOVE, A |
| LICENSED CONTRACTOR WHO VIOLATES THIS SECTION SHALL BE |
| SUBJECT TO DISCIPLINE PURSUANT TO SECTION 113 OF THIS |
| CHAPTER. |
| |
| 16) SHEET L.S.101: |
| 16A) 2ND REQUEST. FIRE/ SMOKE DETECTION SYSTEM. |
| RESPONSE INDICATES THE USE OF A NFPA 13 FIRE SPRINKLER |
| SYSTEM. PLEASE REVIEW THE 2014 FBC-B 907.2.8. |
| 1ST ROUND COMMENTS. FIRE PROTECTION GENERAL NOTES # 1 |
| GC TO INSTALL FIRE/ SMOKE DETECTION SYSTEM AS |
| APPLICABLE CODES FOR USE AND OCCUPANCY. PLEASES BE |
| SPECIFIC TO THE 2014 FBC-B. |
| |
| 16-17) COMPLIED. |
| |
| 18) SHEET A2.01A. GROUND FLOOR; |
| 18A) COMPLIED. |
| |
| 18B) SEMI-COMPLIED. THE PLAN STILL SHOW THIS WALL AS A |
| 4 INCH AND 6 INCH WALL, REMOVE THE 4 INCH DIMENSION. |
| PLEASE SHOW THE MASONRY WALLS 4 INCH / 2 HR. RATED WITH |
| THE CENTER CAVITY. THE DESIGN # 906 IS FOR 6INCH BLOCK |
| EITHER HOLLOW OR SOLID BUT NOT FOR A 4 INCH BLOCK WALL. |
| 107.2.1.3 ADDITIONAL INFORMATION REQUIRED. FBC-B TABLE |
| 722.3.2 MINIMUM EQUIVALENT THICKNESS (INCHES) OF |
| BEARING OR NONBEARING CONCRETE MASONRY WALLS. |
| |
| 18C) 2ND REQUEST, THE PERIMETER OF THE PARKING GARAGE |
| IS 49+49+60+60=218 L.F. X 15 FT(H)= 3270 SQ. FT. |
| OPENINGS, 60+18= 78(W) X 15(H)= 1170 SQ. FT. THIS IS |
| ONLY 35.7 % OPEN. WILL REQUIRE MECHANICAL VENTILATION. |
| THE ALLOWABLE 40 % OPENINGS ARE FOR UNIFORMLY |
| DISTRIBUTED OPENINGS ON NO LESS THAN 2 WALLS FOR |
| ADEQUATE VENTILATION. THESE OPENINGS ARE NOT UNIFORMLY |
| DISTRIBUTED ON OPPOSITE WALLS THAT WOULD CREATE AIRFLOW |
| NOR THE REQUIRED 40 %. |
| |
| 1ST ROUND OF COMMENTS. THE L. S. SHEET NOR THE GROUND |
| FLOOR SHOW THE PARKING GARAGE AS DESIGNED OPEN OR |
| ENCLOSED. THE PLANS DO NOT APPEAR TO MAKE THE |
| REQUIREMENTS FOR AN OPEN PARKING GARAGE UNDER SECTION |
| FBC-B 406.5.2 AND WILL NEED TO MEET THE REQUIREMENTS |
| FOR 406.6.2 VENTILATION AND 406.6.3 AUTOMATIC SPRINKLER |
| SYSTEM. |
| THE M1.1 SHEET ALSO DOES NOT SHOW ANY MECHANICAL |
| EQUIPMENT FOR MECHANICAL EQUIPMENT. THERE SEAMS TO BE A |
| OPENING MISSING IN THE GARAGE CEILING (HIDDEN DASHED |
| LINE) ON THE GRID LINE C/ 5 THAT GOES VERTICALLY |
| THROUGH TO THE ROOF. IF THE DESIGNERS INTENT IS O TAKE |
| CREDIT FOR THE 3 VERTICAL OPENS IN THE CEILING AS WELL |
| AS THE ONE ON GRID LINE C/5 AS EQUAL TO CROSS |
| VENTILATION FOR AN OPEN PARKING GARAGE, THEN |
| CALCULATIONS WILL BE NEEDED TO PROVIDE CODE COMPLIANCE |
| UNDER SECTION 104.11 ALTERNATE MATERIALS, DESIGN AND |
| METHODS OF CONSTRUCTION AND EQUIPMENT. A LETTER TO THE |
| BUILDING OFFICIAL WOULD ALSO NEED TO FOLLOW ASKING THIS |
| DESIGN TO BE REVIEWED UNDER 104.11 ALTERNATE MATERIALS, |
| DESIGN AND METHODS OF CONSTRUCTION AND EQUIPMENT. |
| |
| 104.11.1 RESEARCH REPORTS. SUPPORTING DATA, WHERE |
| NECESSARY TO ASSIST IN THE APPROVAL OF MATERIALS OR |
| ASSEMBLIES NOT SPECIFICALLY PROVIDED FOR IN THIS CODE, |
| SHALL CONSIST OF VALID RESEARCH REPORTS FROM APPROVED |
| SOURCES. |
| |
| 18D-K) COMPLIED. |
| |
| 19) SHEET A2.02 THE SECOND FLOOR LEVEL: |
| |
| 19A-B) COMPLIED. |
| |
| 19C) PROVISO PROVIDE CHAIR LIFT SPECIFICATIONS. THE |
| ACCESSIBLE SUITE DOES NOT INDICATE HOW COMPLIANCE WITH |
| 242.2 ACCESSIBLE SWIMMING POOLS ARE GOING TO BE |
| ACHIEVED. SEE EXCEPTION 1 REQUIREMENT. WHERE A SWIMMING |
| POOL HAS LESS THAN 300 LINEAR FEET OF SWIMMING POOL |
| WALL, NO MORE THAN ONE ACCESSIBLE MEANS OF ENTRY SHALL |
| BE REQUIRED PROVIDED THAT THE ACCESSIBLE MEANS OF ENTRY |
| IS A SWIMMING POOL LIFT COMPLYING WITH 1009.2 OR SLOPED |
| ENTRY COMPLYING WITH 1009.3. |
| |
| 19D) THIS TO BE A DEFERRED SUBMITTAL 107. 3.4.2. THIS |
| IS GOING TO BE A COMMENT FOR ALL UNITS NOT JUST THE |
| ACCESSIBLE UNIT. THE PLANS SHOW SLIDING GLASS DOORS |
| THAT LED FROM WITHIN THE SUITE OUT TO THE TERRACE DECK. |
| THE COMPLETE OPENING BEING 14 FOOT 10 INCHES WIDE |
| DIVIDE BY 3 EQUALS OR EACH PANEL 4 FT. 11 IINCHES |
| APPROXIMATELY. THIS SIZE DOOR CAN BE USED IN A MEANS OF |
| EGRESS WHEN THE OCCUPANT LOAD IS 10 OR LESS, 1008.1.2 |
| EXCEP. #9. THE DOOR IS 19/32 IN. LAMINATED GLASS. |
| 2014 FBC-B 1008.1.3 DOOR OPENING FORCE. THE FORCE FOR |
| PUSHING OR PULLING OPEN INTERIOR SWINGING EGRESS DOORS, |
| OTHER THAN FIRE DOORS, SHALL NOT EXCEED 5 POUNDS (22 |
| N). FOR OTHER SWINGING DOORS, AS WELL AS SLIDING AND |
| FOLDING DOORS, THE DOOR LATCH SHALL RELEASE WHEN |
| SUBJECTED TO A 15-POUND (67 N) FORCE. THE DOOR SHALL BE |
| SET IN MOTION WHEN SUBJECTED TO A 30-POUND (133 N) |
| FORCE. THE DOOR SHALL SWING TO A FULL-OPEN POSITION |
| WHEN SUBJECTED TO A 15-POUND (67 N) FORCE. |
| FOR THE ACCESSIBLE UNIT THE OPENING FORCE FOR THE |
| SLIDING GLASS DOOR WILL BE FBC-ACCESS. CODE 404.2.9 |
| DOOR AND GATE OPENING FORCE. FIRE DOORS SHALL HAVE A |
| MINIMUM OPENING FORCE ALLOWABLE BY THE APPROPRIATE |
| ADMINISTRATIVE AUTHORITY. THE FORCE FOR PUSHING OR |
| PULLING OPEN A DOOR OR GATE OTHER THAN FIRE DOORS SHALL |
| BE AS FOLLOWS: 2. SLIDING OR FOLDING DOORS: 5 POUNDS |
| (22.2 N) MAXIMUM. |
| |
| 19E) THE DESIGN PROFESSIONAL WILL NEED TO SUBMIT THE |
| LETTER FOR CONSIDERATION UNDER 104.1.1 ALTERNATE |
| MATERIALS, DESIGN AND METHODS, ONCE APPROVED PROVIDE A |
| COPY TO BE SCANNED INTO THE PERMIT RECORDS. |
| |
| THE OTHER ISSUE COMMON TO ALL UNITS WITH THE SLIDING |
| DOOR TO THE POOL DECK IS: 404.2.7 DOOR AND GATE |
| HARDWARE. HANDLES, PULLS, LATCHES, LOCKS, AND OTHER |
| OPERABLE PARTS ON DOORS AND GATES SHALL COMPLY WITH |
| 309.4. OPERABLE PARTS OF SUCH HARDWARE SHALL BE 34 |
| INCHES (865 MM) MINIMUM AND 48 INCHES (1220 MM) MAXIMUM |
| ABOVE THE FINISH FLOOR OR GROUND. WHERE SLIDING DOORS |
| ARE IN THE FULLY OPEN POSITION, OPERATING HARDWARE |
| SHALL BE EXPOSED AND USABLE FROM BOTH SIDES. |
| EXCEPTIONS: 2. ACCESS GATES IN BARRIER WALLS AND FENCES |
| PROTECTING POOLS, SPAS, AND HOT TUBS SHALL BE PERMITTED |
| TO HAVE OPERABLE PARTS OF THE RELEASE OF LATCH ON |
| SELF-LATCHING DEVICES AT 54 INCHES (1370 MM) MAXIMUM |
| ABOVE THE FINISH FLOOR OR GROUND PROVIDED THE |
| SELF-LATCHING DEVICES ARE NOT ALSO SELF-LOCKING DEVICES |
| AND OPERATED BY MEANS OF A KEY, ELECTRONIC OPENER, OR |
| INTEGRAL COMBINATION LOCK. |
| |
| THE DOORS ARE TO BE SELF-CLOSING AND SELF-LATCHING. |
| FBC-B 454.1.3.1.9 ACCESS THROUGH THE BARRIER OR FENCE |
| FROM DWELLING UNITS, SUCH AS HOMES, APARTMENTS, MOTEL |
| ROOMS AND HOTEL ROOMS, SHALL BE THROUGH SELF-CLOSING, |
| SELF-LATCHING LOCKABLE GATES OF 48 INCH (1219 MM) |
| MINIMAL HEIGHT FROM THE FLOOR OR GROUND WITH THE LATCH |
| LOCATED A MINIMUM OF 54 INCHES (1372 MM) FROM THE |
| BOTTOM OF THE GATE OR AT LEAST 3 INCHES (76 MM) BELOW |
| THE TOP OF THE GATE ON THE POOL SIDE. IF THE |
| SELF-CLOSING, SELF-LATCHING GATE IS ALSO SELF-LOCKING |
| AND IS OPERATED BY A KEY LOCK, ELECTRONIC OPENER OR |
| INTEGRAL COMBINATION LOCK, THEN THE OPERABLE PARTS OF |
| SUCH LOCKS OR OPENERS SHALL BE 34 INCHES MINIMUM (864 |
| MM) AND 48 INCHES MAXIMUM (1219 MM) ABOVE THE FINISHED |
| FLOOR OR GROUND. |
| |
| 19F) BUILDING PROVISO: PLEASE NOTE THE SLIDING GLASS |
| DOOR, THE THRESHOLD INDICATES ONLY TO BE 1/2 INCH HIGH. |
| 404.2.5 THRESHOLDS. THRESHOLDS, IF PROVIDED AT |
| DOORWAYS, SHALL BE 1/2 INCH (13 MM) HIGH MAXIMUM. |
| RAISED THRESHOLDS AND CHANGES IN LEVEL AT DOORWAYS |
| SHALL COMPLY WITH ACCESS. CODE 302 AND 303. HOW WILL |
| WATER INTRUSION BE HANDLED IN A HURRICANE? |
| |
| 19G-H) COMPLIED |
| |
| 20) THE ACCESSIBLE SUITE SHOWS A DETAIL # 1/ A7.2. THE |
| ACCESSIBLE BATHROOM: |
| |
| 20A-E)COMPLIED. |
| |
| 20F)2ND REQUEST. RESPONSE INDICATES THE STEAM SHOWER |
| REMOVED FROM THE UNIT LAYOUT. IT APPEARS THAT THE STEAM |
| SHOWER HAS BEEN MOVED INTO THE ACCESSIBLE BATHROOM. |
| THE STEAM SHOWER IN THE ACCESSIBLE GUEST UNIT WILL ALSO |
| NEED TO SHOW COMPLIANCE WITH THE 2014 FBC-ACCESS. CODE |
| ; |
| 20F)(1) 612.2 BENCH. WHERE SEATING IS PROVIDED IN |
| SAUNAS AND STEAM ROOMS, AT LEAST ONE BENCH SHALL COMPLY |
| WITH 903. DOORS SHALL NOT SWING INTO THE CLEAR FLOOR |
| SPACE REQUIRED BY 903.2. EXCEPTION: A READILY REMOVABLE |
| BENCH SHALL BE PERMITTED TO OBSTRUCT THE TURNING SPACE |
| REQUIRED BY 612.3 AND THE CLEAR FLOOR OR GROUND SPACE |
| REQUIRED BY 903.2. |
| |
| 20F)(2) 612.3 TURNING SPACE. A TURNING SPACE COMPLYING |
| WITH 304 SHALL BE PROVIDED WITHIN SAUNAS AND STEAM |
| ROOMS. |
| |
| 21) SHEET A2.07 THESE COMMENTS WILL BE COMMON TO ALL |
| FLOORS 2-5; |
| |
| 21A) 2ND REQUEST. RESPONSE INDICATES SEE SPECS FOR |
| VERSA DECK SYSTEM, NOT SUBMITTED. |
| 1ST ROUND COMMENTS. NOTE # 14 INDICATES THE USE OF TREX |
| DECK TERRACE AND CEILING. THERE IS NO PRODUCT |
| INFORMATION FOR THE TREX DECK SYSTEM. PLEASE PROVIDE |
| THE MANUFACTURERS SPECIFICATION, IF THIS IS A |
| COMBUSTIBLE PRODUCT AND IF SO THE FLAME SPREAD AND TO |
| WHAT STANDARD THE PRODUCT WAS TESTED TOO? SEE FBC-B |
| SECTION 603 COMBUSTIBLE MATERIAL IN TYPE I AND II |
| CONSTRUCTION. 603.1 ALLOWABLE MATERIALS. |
| |
| 21B) 2ND REQUEST. RESPONSE INDICATES SEE SPECS FOR |
| VERSA DECK SYSTEM, NOT SUBMITTED. |
| 1ST ROUND OF COMMENTS. THERE ARE NO PLANS FOR THE TREX |
| DECK DROP CEILING ASSEMBLY. TYPE OF FRAMING, MATERIAL, |
| SPACING, SIZE OF FRAMING MEMBERS, ANCHORAGE TO THE DECK |
| ABOVE IF STIFF BACKS ARE REQUIRED. 107.3.5 MINIMUM PLAN |
| REVIEW CRITERIA FOR BUILDINGS. 107.3.5.1 COMMERCIAL |
| BUILDINGS: DROPPED EXTERIOR CEILING ASSEMBLIES. |
| |
| 21C) 2ND REQUEST SHEET A2.07 SHOWS OVER THE BATHROOMS A |
| MECHANICAL PLENUM. DETAILS 3 & 4 BOTH INDICATE THE USE |
| OF INSULATION IN BOTH THE MECHANICAL PLENUM AS WELL AS |
| THE DROPPED CEILING WITHIN THE TYPICAL SUITE. THE PLANS |
| DOES NOT DECLARE WHAT TYPE OF INSULATION IS GOING TO BE |
| INSTALLED? IS THIS INSULATION GOING TO BE FOR BOTH |
| SOUND AND THERMAL VALUES? SEE FBC-B 720.1 & 720.2. |
| |
| 21D) 2ND REQUEST, PLEASE PROVIDE CODE COMPLIANCE. |
| DETAILS 3 & 4 WITHIN THE SUITE SHOW A DROPPED CEILING |
| ASSEMBLY, FASTENED TO THE CONCRETE DECK ABOVE AS WELL |
| AS A DROPPED CEILING ASSEMBLY WITH WHAT MAYBE A LIGHT |
| TROUGH. THE INSULATION ABOVE WOULD STILL BE WITHIN THE |
| ROOM PROPER. PLEASE PROVIDE ADDITIONAL DETAILS AS TO |
| THE TYPE OF FRAMING MATERIALS, ANCHORAGE TO THE DECK |
| ABOVE, SIZE OF FRAMING MEMBERS, SPACING OF FRAMING |
| MEMBERS THE TYPE OF INSULATION, THE THICKNESS AND TYPE |
| OF FINISH MATERIAL FOR THE DROPPED CEILING. . 107.3.5 |
| MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS. 107.3.5.1 |
| COMMERCIAL BUILDINGS: DROPPED EXTERIOR CEILING |
| ASSEMBLIES. |
| FBC-B 720.3 EXPOSED INSTALLATION. INSULATING MATERIALS, |
| WHERE EXPOSED AS INSTALLED IN BUILDINGS OF ANY TYPE OF |
| CONSTRUCTION, SHALL HAVE A FLAME SPREAD INDEX OF NOT |
| MORE THAN 25 AND A SMOKE-DEVELOPED INDEX OF NOT MORE |
| THAN 450. |
| FBC-B 803.11.2 SET-OUT CONSTRUCTION. WHERE WALLS AND |
| CEILINGS ARE REQUIRED TO BE OF FIRE-RESISTANCE-RATED OR |
| NONCOMBUSTIBLE CONSTRUCTION AND WALLS ARE SET OUT OR |
| CEILINGS ARE DROPPED DISTANCES GREATER THAN SPECIFIED |
| IN SECTION 803.11.1, CLASS A FINISH MATERIALS, IN |
| ACCORDANCE WITH SECTION 803.1.1 OR 803.1.2, SHALL BE |
| USED. |
| |
| 21E-F) COMPLIED. |
| |
| 21G) BUILDING PROVISO: POOLS AND ASSOCIATED EQUIPMENT |
| WILL BE UNDER SEPARATE PERMITS FOR EACH UNIT FOR THE |
| RECORDING OF INSPECTIONS. 105.1. PERMITS REQUIRED. |
| |
| 22) BUILDING PROVISO: SHEET A3.03 THE GREEN SCREEN |
| SYSTEM PANELS CAN BE A SUBMITTAL THAT COULD QUALIFY AS |
| A DEFERRED SUBMITTAL, PLEASE PROVIDE THE WIND DESIGN |
| PARAMETERS FOR THE SPECIALTY ENGINEERS CAN DESIGN TO |
| THE PROPER WIND SPEED. 107.3.4.2 DEFERRED SUBMITTALS. |
| 2014 FBC-B 1603.1.4 WIND DESIGN DATA. |
| |
| 23) SHEET A2.05 ROOF PLAN. |
| |
| 23A) COMPLIED. |
| 23B) 2ND REQUEST. STAIR TOWER 1 & 2 BOTH SHOW OVERFLOW |
| SCUPPERS BUT NO SECONDARY (EMERGENCY OVERFLOW) DRAINS |
| OR SCUPPERS. FBC-B 1503.4.1. |
| |
| 23C) SEMI-COMPLIED. THE DETAIL SHOW AN OVERFLOW SCUPPER |
| 4 INCHES OF THE FINISH ROOF BUT NOT A SCUPPER WHICH |
| SHOULD BE FLUSH WITH THE ROOF. PLEASE PROVIDE DETAILS |
| FOR SCUPPERS AND OVERFLOW SCUPPERS, THE BOTTOM OF EACH |
| UNIT IN RELATIONSHIP WITH THE ROOF. FBC-B 1503.4.2 |
| SCUPPERS. OVERFLOW SCUPPERS ARE SHOWN. |
| |
| 23D-E) PROVISO: DEFERRED SUBMITTAL 107.3.4.2. ROOF TOP |
| A/C STANDS. CONTRACTOR IS TO PROVIDE APPROVED SIGNED |
| AND SEALED SHOP DRAWINGS FOR REVIEW AND APPROVAL BY THE |
| ENGINEER OF RECORD. |
| |
| |
| 23F-G) PROVISO/ DEFERRED SUBMITTAL 107.3.4.2. ROOFTOP |
| SKYLIGHTS. SECTION 603 COMBUSTIBLE MATERIAL IN TYPE I |
| AND II CONSTRUCTION. 603.1 ALLOWABLE MATERIALS. 15. |
| LIGHT-TRANSMITTING PLASTICS AS PERMITTED BY CHAPTER 26. |
| PLEASE PROVIDE COMPLIANCE WITH: 2609.4 AREA |
| LIMITATIONS. ROOF PANELS SHALL BE LIMITED IN AREA AND |
| THE AGGREGATE AREA OF PANELS SHALL BE LIMITED BY A |
| PERCENTAGE OF THE FLOOR AREA OF THE ROOM OR SPACE |
| SHELTERED IN ACCORDANCE WITH TABLE 2609.4. CC1 OR CC2? |
| |
| 23H) NOT APPLICABLE/ NO ACTION NEEDED. |
| |
| 24) COMPLIED. FBC-B 3002.4 ELEVATOR CAR TO ACCOMMODATE |
| AMBULANCE STRETCHER |
| |
| 25-28) COMPLIED. |
| |
| 29) PROVISO/ DEFERRED SUBMITTAL 107.3.4.2. FOR THE |
| PRODUCT APPROVALS WITH GLAZED OPENINGS AND MULLIONS , |
| PLEASE IDENTIFY THE OPENING WIDTH & HEIGHT, TYPE OF |
| GLAZING, MULLION INFORMATION IF REQUIRED, ATTACHMENTS |
| AND ASSOCIATE PRESSURES FOR EACH OPENING SIZE THE |
| SUBMITTED PRODUCT APPROVALS THERE ARE TO MANY VARIABLE, |
| CIRCLE TO IDENTIFY EACH COMPONENT. COMPONENTS & |
| CLADDING. |
| |
| 30) PROVISO/ DEFERRED SUBMITTAL 107.3.4.2. THE NOA |
| 15-0731.06 MIAMI ROLLING DOOR SUBMITTED REPORT GOOD FOR |
| +/- 65 SHEET S-18 SHOWS PRESSURES OF -87, VASD OR VULT |
| NOT GIVEN ON THE SHEET. ALL PRODUCT APPROVALS ARE IN |
| VASD. 1609.3.1 WIND SPEED CONVERSION VULT TO VASD. |
| |
| 31) .(2) PROVISO/ DEFERRED SUBMITTAL 107.3.4.2. ROOFING |
| APPROVALS WERE SUBMITTED FOR THIS REVIEW. |
| CARLISLE MIRASEAL FLUID APPLIED WATERPROOFING MEMBRANE |
| NOA 13-0129.22 |
| CARLISLE CCW-500-R HOT APPLIED LIQUID MEMBRANE NOA |
| 12-0801.01 |
| IN BOTH APPROVALS THERE ARE MULTIPLE SUB-SYSTEMS AND |
| ASSOCIATED PRESSURES. IN NEITHER REPORT WAS A |
| SUB-SYSTEM AND ASSOCIATED PRESSURES INDICATED. ALSO IN |
| BOTH REPORTS LIMITATION # 9 IS INDICATED NO ENHANCED |
| FASTENING CAN OCCUR. THE PLANS DO NOT INDICATE ROOF TOP |
| PRESSURES FOR ZONES 1,2 & 3. PLEASE PROVIDE PRESSURES |
| IN VASD SINCE THE PRODUCT APPROVALS ARE IN VASD. 2014 |
| FBC- B 1603.1.4 WIND DESIGN DATA. |
| |
| 32) PROVISO/ DEFERRED SUBMITTAL 107.3.4.2. 2014 FBC-B |
| 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.4.1 |
| COMPONENTS & CLADDING |
| |
| FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. |
| 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION |
| SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS: |
| (31)(A) EXTERIOR DOORS. |
| (B) WINDOWS |
| (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL |
| LOUVERS, EFIS SYSTEMS, |
| (D) ROOFING PRODUCTS AND ASSEMBLIES |
| (F) SKYLIGHTS |
| (G) PRE-ENGINEERED A/C STANDS |
| |
| 33) SOILS REPORTS ONLY ONE SIGNED AND SEALED DOCUMENT |
| WAS SUBMITTED, 3 REQUIRED. THRESHOLD BUILDING. |
| |
| 34) PLEASE PROVIDE WHAT AGENCY WILL BE MONITORING OF |
| THE TEST PILING AS WELL AS THE PRODUCTION PILE. NOTE |
| THE TEST PILE IS UNDER SEPARATE PERMIT. |
| |
| 35) 2ND REQUEST. BEFORE A PERMIT TO CONSTRUCT, MAY BE |
| ISSUED, IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY. |
| THE ACTUAL PERMIT SET OF PLANS MUST BE STAMPED BY THAT |
| OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED TO THE |
| PERMIT APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| INFORMATION. |
| |
| 36) WHEN RESUBMITTING PLANS PLEASE INDICATE THE |
| REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES |
| AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |
| A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A |
| RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| THIS REVIEW. |
| |