Plan Review Notes
Plan Review Notes For Permit 16070837
Permit Number 16070837
Review Stop P
Sequence Number 1
Notes
Date Text
2016-08-22 04:50:511) THE CIVIL DRAWINGS ARE NOT SIGNED AND SEALED BY THE
 DESIGN PROFESSIONAL. FL. ADMIN. CODE RULE 61G15-23.001.
 2) SEPARATE PLANS/SPECIFICATIONS AND PERMIT WILL BE
 REQUIRED FOR THE BACKFLOW PREVENTERS.
 3) THE HUB DRAIN RECEIVING THE DISCHARGE FROM THE
 ELEVATOR SUMP SHALL BE EQUIPPED WITH A FLOOR DRAIN.
 2014 FPC SEC. 1002.4.
 4) SUBMIT A CONDENSATE RISER DIAGRAM FOR REVIEW. WPB
 AMEND. TO FBC SEC. 107.2.1.
 5) SUBMIT A DETAIL FOR THE " CONCRETE SHOWER PAN" AT
 THE TERRACE REFERENCED ON THE ARCHITECTURAL SHEETS. WPB
 AMEND. TO FBC SEC. 107.2.1.
 6) SUBMIT A DETAIL FOR THE "PLENUM DRAINAGE" REFERENCED
 ON THE PLANS.
 7) SHT.A2.05 - IDENTIFY THE PARAMETERS OF THE
 INDIVIDUAL ROOF AREAS A-D.WPB AMEND. TO FBC SEC.
 107.2.1.
 8) SHT. A2.05 - CALLS OUT 8 INCH BY 4 INCH SCUPPERS AND
 SHT. P1.05 SHOWS 6 INCH BY 4 INCH. CLARIFY.
 9) ROOF DRAINS #2 & #3 APPEAR TO BE MISSING EMERGENCY
 OVERFLOW DRAINS/SCUPPERS. SHOW THE LOCATION OF THE
 OVERFLOW DRAINS ON THE PLAINS.2014 FPC SEC. 1108.
 10) SUBMIT ROOF DRAINAGE CALCULATIONS THAT SHOW THAT
 ONE-HALF THE AREA OF ALL VERTICAL WALLS THAT DIVERT
 RAINWATER TO THE ROOF HAS BEEN ADDED TO THE PROJECTED
 ROOF AREA FOR THE REQUIRED SIZING OF THE VERTICAL
 CONDUCTORS, LEADERS AND HORIZONTAL STORM DRAINAGE
 PIPING. FPC SEC.1106.4.
 11) PROVIDE OVERFLOW STORM DRAIN DETAILS FOR STAIR
 TOWERS #1 & #2. FPC SEC. 1108.
 12) SUBMIT DETAILS FOR THE SCUPPERS AND OVERFLOW
 SCUPPERS. COMPLY WITH 2014 FBC SEC.1503.4.2.
 13) SHT. A7.01 & A8.11 - AS AN FYI, FLORIDA DOES NOT
 ENFORCE THE ADA. FLORIDA HAS ITS OWN ACCESSIBILITY CODE
 AND CAN BE FOUND IN THE 2014 (5TH EDITION) OF THE
 FLORIDA BUILDING CODE, NOT THE 2010 EDITION. ALL
 HANDICAPPED ITEMS SHALL COMPLY WITH THE FBC.
 14) COAT HOOKS AND TOWEL BARS SHALL COMPLY AND BE
 LOCATED WITHIN THE REACH RANGES MANDATED IN SECS.
 213.3.7, 308.2.1, 308.3.2, 604.8.3, 603.4.
 15) GRAB BARS SHALL BE MEASURED FROM THE FINISH FLOOR
 TO THE TOP OF THE GRIPPING SURFACE PER THE FAC SEC.
 609.4.
 16) THE TOILET PAPER DISPENSER SHALL BE LOCATED IN
 ACCORDANCE WITH THE FAC SEC. 604.7.
 17) WHERE ARE THE REQUIRED DRINKING FOUNTAINS ON THE
 GROUND FLOOR? COMPLY WITH THE 2014 FPC TABLE 403.1. A
 MINIMUM OF TWO DRINKING FOUNTAINS ARE REQUIRED IN
 ACCORDANCE WITH 2014 FPC TABLE 403.1, FOOTNOTE # (E)
 AND THE FAC SEC. 211.2, 602.4, 602.7.
 18) SHT. A7.02 - DETAIL #1 -THE CLEAR FLOOR SPACE FOR
 THE WATER CLOSET SHALL COMPLY WITH THE FAC SEC.604.3.
 SHOW THIS ON THE PLAN.
 19) THE SEAT IN THE ACCESSIBLE SHOWER SHALL COMPLY WITH
 THE FAC SEC. 610.3. SUBMIT DETAILS. THE SEAT SHALL BE
 OF A FOLDING TYPE.
 20) THE WET BAR/SINK IN THE HANDICAPPED ACCESSIBLE UNIT
 SHALL COMPLY WITH THE FAC SECS.212.2, 606.
 21) SUBMIT SPECIFICATIONS FOR THE "STEAM SHOWER." IS
 THIS A SAUNA ALSO? THE STEAM SHOWER IN THE ACCESSIBLE
 UNIT SHALL COMPLY WITH FAC SECS. 241, 302, 404.2 & 612.
 SUBMIT AN ENLARGED FLOOR PLAN FOR THIS SHOWER.
 22) THE POOL IN THE ACCESSIBLE SUITE SHALL COMPLY WITH
 2014 FAC SEC. 242.
 23) SHT. A7.02 - THE ACCESSIBLE LAVATORY SHALL BE
 DESIGNED FOR A FORWARD APPROACH. FAC SECS. 213.3.4 &
 606.
 24) THE SHOWER CONTROLS IN THE ACCESSIBLE SHOWER SHALL
 COMPLY WITH THE FAC SECS.608.5.3.SHOW THE DISTANCE OF
 THE CONTROLS IN RELATION TO THE SEAT, FROM ADJACENT
 WALLS, ABOVE THE FLOOR, ETC.
 25) SHT. A7.02 REFERS TO FAIR HOUSING REQS. THIS
 PROJECT DOES FALL UNDER THE PURVIEW OF THE FAIR HOUSING
 ACT. REVISE NOTE TO READ 2014 FBC-ACCESSIBILITY VOLUME.
 26) SHT. A8.11 REFERENCES THE 2010 FBC /FHA. THESE
 DETAILS DO NOT APPLY. THE CODE IN EFFECT IS THE 2014
 FBC-ACCESSIBILITY.
 27) SUBMIT FACTORY SIZING CALCULATIONS FROM SCHIER FOR
 THE LAUNDRY INTERCEPTOR. 2014 FBC SEC. 1003.2.
 28) THE CONNECTION OF THE LAUNDRY SUMP DRAIN TO THE
 SANITARY SYSTEM SHALL COMPLY WITH FPC SEC. 712.3.5.
 29) SUBMIT SPECIFICATIONS FOR THE PUMPS FOR THE
 LAUNDRY. WPB AMEND. TO FBC SEC. 107.2.1.
 30) SUBMIT MANUF. SPECIFICATIONS /DETAILS FOR THE GAS
 WATER HEATERS. SUBMIT VENT DETAILS (SIZE, TYPE OF PIPE,
 ETC.).COMPLY WITH FGC SEC.502, 503, 504.
 31) SUBMIT CALCULATIONS FOR COMBUSTION AIR IN
 ACCORDANCE WITH THE 2014 FBC-GAS SEC.304.
 32) SHOW THE DISTANCE OF THE GAS WATER HEATER VENTS
 FROM BUILDING OPENINGS. COMPLY WITH FGC SEC. 503.6.4.
 33) SUBMIT MANUF. SPECIFICATIONS /DETAILS FOR THE
 DRYERS. SUBMIT VENT DETAILS (SIZE, TYPE OF MATERIAL,
 TERMINATION POINTS, ETC.).
 34) CARBON MONOXIDE SENSORS ARE REQUIRED PER THE 2014
 FBC SEC. 908.7.
 35) SEPARATE PERMITS ARE REQUIRED FOR THE SWIMMING
 POOLS.
 36) SHT. P3.02 - SIZE THE IRRIGATION BRANCHES ON THE
 RISER.
 37) SHT. P3.02 - COLD WATER RISERS SHALL HAVE SHUTOFF
 VALVES PER FPC SEC.606.1. SEE RISER CW /1 WHICH
 SUPPLIES FIXTURE P-6.
 38) SHUT OFF VALVES ARE REQD. ON THE WATER SUPPLIES TO
 FIXTURE P-7 IN THE BASEMENT. FPC SEC. 606.1 (5).
 39) SHT. P3.03 - SHOWS RISER S/2 FOR FIXTURE P-4 & SHT.
 P1.02 SHOWS RISER S/2 FOR P-3. CLARIFY.
 40) SHT. P1.02 SHOWS RISER S/3 FOR FIXTURE P-4 AND SHT.
 P3.03 SHOWS FIXTURE P-3. CLARIFY.
 41) SHT. P3.04 - SIZE THE VENT FOR THE HUB DRAIN AND
 SHOW THE CONTINUATION/TERMINATION POINT OF THE VENT.
 WPB AMEND. TO FBC SEC. 107.2.1.
 42) SHT. P3.04 - SIZE THE FORCE MAIN FROM THE SANITARY
 EJECTOR ON THE RISER. WPB AMEND. TO FBC SEC. 107.2.1.
 43) SHT. P1.01 APPEARS TO SHOW A 2 INCH FORCE MAIN
 INSIDE STAIR FS-1. PENETRATIONS OTHER THAN THOSE
 NECESSARY FOR THE PURPOSE OF THE EXIT ACCESS STAIRWAY
 ENCLOSURE ARE PROHIBITED PER THE 2014 FBC
 SEC.1009.3.1.5.1.
 44) SHT. P4.01 - INDICATE THE SIZE OF THE EXPANSION FOR
 THE WATER HEATERS.
 45) SHT.P4.01 - WATER HEATER DETAIL - PAN DRAINS ARE
 REQUIRED FOR THE WATER HEATERS. DRAINS SHALL COMPLY
 WITH FPC SEC.504.7.1 & 504.7.2.
 46)SHT. P4.01 - A FULL OPEN VALVE SHALL BE INSTALLED ON
 THE WATER HEATERS. 2014 FPC SEC.606.1 (8).
 47)SHT. P3.05 SHOWS A ONE HALF-INCH DISCHARGE LINE FROM
 THE STORM SUMP. THIS IS OBVIOUSLY A TYPOGRAPHICAL
 ERROR. PLEASE CORRECT.
 48)INDICATE THE SLOPE OF THE HORIZONTAL STORM DRAINAGE
 PIPING ON THE PLANS. COMPLY WITH TABLE 1106.3 OF THE
 FPC.
 49)SHT. P3.05 - THERE ARE ROOF DRAINS THAT DO NOT SHOW
 THE SQUARE FOOTAGE BEING DRAINED. CLARIFY.
 50)SHT. P3.05 - THE SQUARE FOOTAGE BEING DRAINED BY
 EACH DRAIN IS LABELED AS ?FU?. PLEASE CORRECT.
 51)SHOW THE LOCATION OF THE POOL HEATERS ON THE PLANS.
 WPB AMEND. TO FBC SEC. 107.2.1.
 52)SHT.A.201B SHOWS A MECHANICAL ROOM. SUPPLY
 INFORMATION AS TO WHAT TYPE OF EQUIPMENT WILL BE
 LOCATED IN THIS ROOM AND PROVIDE AN EQUIPMENT SCHEDULE.
 WPB AMEND. TO FBC SEC. 107.2.1.
 53) INDICATE ON THE PLANS WHAT TYPE OF MATERIALS/ITEMS
 WILL BE PLACED IN THE STORAGE ROOM.WPB AMEND. TO FBC
 SEC. 107.2.1.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR