2016-07-29 15:53:221ST REVIEW MECHANICAL- FBC-2014
 PERMIT #16070837
 7/29/16
  
 1) SHEETS A2.01A & M1.01: THE PLANS APPEAR TO INDICATE
 AN ENCLOSED PARKING GARAGE WHICH IS REQUIRED TO HAVE AN
 EXHAUST VENTILATION SYSTEM PER SECTION 406.6.2 FBC-14
 BUILDING. PROVIDE A SYSTEM DESIGNED IN ACCORDANCE WITH
 SECTION 404.1, 404.2, & 404.3.FBC-14 MECHANICAL.
  
 2) A2.01A: PROVIDE AN EXHAUST SYSTEM FOR THE TRASH ROOM
 PER TABLE 6-4 ASHRAE 62.1-2010.
  
 3) A2.01B: THE PLAN INDICATES A MECHANICAL ROOM IN THE
 BASEMENT. PLEASE SHOW ALL EQUIPMENT AND PROVIDE
 EQUIPMENT LISTS AND SCHEDULES.
  
 4) M-1.00: SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE
 DRYER WITH REVIEW SIGNATURE BY THE ENGINEER OF RECORD.
  
 5) M-1.00 & M-1.01: CLARIFY WHERE THE AIR INLET OPENING
 IS LOCATED FOR THE FCU-A OUTDOOR AIR DUCT.
  
 6) M-1.01: A DUCT SMOKE DETECTOR IS REQUIRED IN THE
 RETURN AIR SYSTEM OF FCU-B- SECTION 606.2.1.
  
 7) M-1.01: THE 24X48 RETURN GRILL APPEARS UNDERSIZED
 FOR THE 3440 CFMS (ADJUSTED TO 2992 CFMS USING
 PERCENTAGE OF OUTDOOR AIR) OF SUPPLY AIR SHOWN ON THE
 PLAN. THE INDUSTRY STANDARD IS TYPICALLY 200 SQ. INCHES
 PER TON.
  
 8) M-3.01: REFER TO SECTION C404.2.2 FBC-14 ENERGY
 CONSERVATION: THE COOLING AND HEATING OUTPUT CAPACITIES
 OF FCU-B EXCEED THE SYSTEM SUMMARY LOADS CALCULATED BY
 THE EOR.
  
 9) M-3.01:THE COOLING AND HEATING CAPACITIES OF FCU-1 &
 FCU-2 EXCEED THE SYSTEM SUMMARY LOADS CALCULATED FOR
 2ND, 3RD, AND 4TH FLOOR SUITES. A) THE HEATING
 CAPACITIES OF FCU-1 & FCU-2 EXCEED THE SYSTEM SUMMARY
 LOADS CALCULATED FOR THE 5TH FLOOR SUITES- SECTION
 C404.2.2.
  
 10) M-3.01: THE AC UNIT SCHEDULE DOES NOT LIST THE
 TOTAL CFMS OF SUPPLY AIR FOR FCU-1 & FCU-2.
  
 11 ) M-2.01: PLEASE LABEL THE AC SYSTEMS AS EITHER
 FCU-1 OR 2.
  
 12) M-2.01: THE RETURN AIR GRILLS APPEAR UNDERSIZED FOR
 THE AMOUNT OF SUPPLY AIR FOR EACH SYSTEM, WITH
 ADJUSTMENT FACTOR FOR OUTDOOR AIR. THE INDUSTRY
 STANDARD IS TYPICALLY 200 SQ. INCHES PER TON.
  
 13) M-2.01: MOTORIZED DAMPERS ARE REQUIRED FOR THE
 OUTDOOR AIR SUPPLY TO THE GUEST SUITE SYSTEMS- SECTION
 C403.2.4.4.
  
 14) M-3.01: PROVIDE EXHAUST VENTILATION CALCULATIONS
 FOR THE JANITOR AND STORAGE ROOMS- TABLE 403.3.
  
 15) M-3.01: A VENTILATION RATE OF 0.48 CFMS PER SQ. FT.
 IS REQUIRED FOR SWIMMING POOLS AND POOL DECK AREAS PER
 TABLE 403.3, HOWEVER IT APPEARS THAT THE POOLS ARE OPEN
 PARTIALLY ON ONE SIDE TO THE OUTDOORS. PLEASE PROVIDE A
 CALCULATION FOR NATURAL VENTILATION IF APPLICABLE.
  
 16) M-4.01, REFRIGERANT PIPING RISERS: PLEASE INDICATE
 THE TYPE OF PIPING, PIPE SIZES, AND THE LENGTHS OF THE
 PIPING RUNS. VERIFY COMPLIANCE WITH MANUFACTURER'S
 SPECIFICATIONS AND INSTALLATION INSTRUCTIONS.
  
 17) M-4.02: PROVIDE SITE SPECIFIC WIND LOAD ENGINEERING
 FOR ALL ROOFTOP MECHANICAL EQUIPMENT INCLUDING CU-A & B
 WHICH ARE NOT SHOWN IN THE DRAWING- SECTION 301.15.
 SUBMIT NOA #15-0902.05 WITH SHOP DRAWING APPROVAL
 SIGNATURE BY THE EOR.
  
 18) PROVIDE A SUBMITTAL PACKAGE FOR MECHANICAL
 EQUIPMENT THAT INCLUDING BUT NOT LIMITED TO THE AC
 SYSTEMS, MOTORIZED DAMPERS, DUCT SMOKE DETECTORS, FIRE
 DAMPERS, THE WATER HEATERS AND FLUE EXHAUST/AIR INTAKE
 DUCTS, LOUVERS ETC. PLEASE NOTE A FLORIDA PRODUCT
 APPROVAL AND/OR A MIAMI-DADE NOA MUST BE SUBMITTED FOR
 THE LOUVERS SHOWN AT THE JANITOR'S CLOSETS.
  
 19) PLEASE INDICATE THE LOCATIONS OF THE POOL HEATERS
 AND PROVIDE EQUIPMENT SCHEDULES AND MANUFACTURER'S
 SPECIFICATIONS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER