Date |
Text |
2016-07-27 11:13:12 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| MARSHAL, WITH THE FOLLOWING COMMENTS: |
| |
| |
| 1) SHEET LS 1.01 - CONTRUCTION TYPE/OCCUPANCY. PLEASE |
| PROVIDE INDICATIONS/ VERIFICATIONS/CLARIFICATONS AS TO |
| THE OCCUPANCY CLASSIFICATION OF THE HOTEL AND THE THE |
| PARKING GARAGE. THE PARKING GARAGE IS A PARKING |
| STRUCTURE IN ACCORDANCE OF NFPA 88A AND APPLICABLE |
| REQUIRMENTS. |
| |
| |
| 28.1.3 MULTIPLE OCCUPANCIES. |
| 28.1.3.1 MULTIPLE OCCUPANCIES SHALL BE IN ACCORDANCE |
| WITH 6.1.14. |
| |
| 6.1.14 MULTIPLE OCCUPANCIES. |
| 6.1.14.1 GENERAL. |
| 6.1.14.1.1 MULTIPLE OCCUPANCIES SHALL COMPLY WITH THE |
| REQUIREMENTS OF 6.1.14.1 AND ONE OF THE FOLLOWING: |
| (1) MIXED OCCUPANCIES ? 6.1.14.3 |
| (2) SEPARATED OCCUPANCIES ? 6.1.14.4 |
| |
| 6.1.14.2.3 SEPARATED OCCUPANCY. A MULTIPLE OCCUPANCY |
| WHERE THE OCCUPANCIES ARE SEPARATED BY FIRE RESISTANCER |
| RATED ASSEMBLIES. |
| 6.1.14.3 MIXED OCCUPANCIES. |
| 6.1.14.3.1 EACH PORTION OF THE BUILDING SHALL BE |
| CLASSIFIED AS TO ITS USE IN ACCORDANCE WITH SECTION 6.1 |
| 6.1.14.3.2* THE BUILDING SHALL COMPLY WITH THE MOST |
| RESTRICTIVE REQUIREMENTS OF THE OCCUPANCIES INVOLVED, |
| UNLESS SEPARATE SAFEGUARDS ARE APPROVED. |
| |
| PLEASE PROVIDE VERIFICATION AND THE APPLICABLE |
| REQUIRMENTS. |
| |
| |
| 2) SHEET LS 1.01 - A PARKING GARAGE IS INDICATED ON THE |
| GROUND FLOOR. IS IT AN OPEN PAKING STRUCUTRE OR CLOSED |
| PARKING STRUCTURE? |
| |
| PER NFPA 88A STANDARD FORPARKING STRUCTURES 2011 |
| EDITION- 3.3 GENERAL DEFINITIONS. 3.3.2* PARKING |
| STRUCTURE. A BUILDING, STRUCTURE, OR PORTION THEREOF |
| USED FOR THE PARKING, STORAGE, OR BOTH, OF MOTOR |
| VEHICLES. |
| 3.3.2.3 PARKING STRUCTURE, ENCLOSED. ANY PARKING |
| STRUCTURE THAT IS NOT AN OPEN PARKING STRUCTURE. |
| 3.3.2.4 PARKING STRUCTURE, OPEN. A PARKING STRUCTURE |
| THAT MEETS THE REQUIREMENTS OF SECTION 5.5. |
| |
| PLEASE PROVIDE INDICATIONS/JUSTIFICATION OF TYPE OF |
| PARKING STRUCTURE AND COMPLIANCE WITH THE REQUIRMENTS. |
| |
| |
| |
| 3) SHEET LS 1.01 & 2-5 FLOOR PLAN SHEETS. THE MEANS OF |
| EGRESS SHALL COMPLY WITH NFPA 101 CHAPTER 28, NEW |
| HOTELS AND DORMITORIE AND ALL APPLICABLE CODES. |
| EXIT FROM THE HOTEL ROOM CORRIDOR APPEARS TO BE OEPNING |
| INTO AN OPEN CORRIDOR. |
| |
| 28.2.2 MEANS OF EGRESS COMPONENTS. |
| 28.2.2.1 GENERAL. |
| 28.2.2.1.1 COMPONENTS OF MEANS OF EGRESS SHALL BE |
| LIMITED TO THE TYPES DESCRIBED IN 28.2.2.2 THROUGH |
| 28.2.2.12. |
| 28.2.2.1.2 IN BUILDINGS, OTHER THAN HIGH-RISE |
| BUILDINGS, THAT ARE PROTECTED THROUGHOUT BY AN |
| APPROVED, SUPERVISED AUTOMATIC SPRINKLER SYSTEM IN |
| ACCORDANCE WITH 28.3.5, EXIT ENCLOSURES SHALL HAVE A |
| MINIMUM 1-HOUR FIRE RESISTANCE RATING, AND DOORS SHALL |
| HAVE A MINIMUM 1-HOUR FIRE PROTECTION RATING. |
| |
| 28.2.5 ARRANGEMENT OF MEANS OF EGRESS. |
| 28.2.5.1 ACCESS TO ALL REQUIRED EXITS SHALL BE IN |
| ACCORDANCE WITH SECTION 7.5, AS MODIFIED BY 28.2.5.2. |
| |
| 7.5 ARRANGEMENT OF MEANS OF EGRESS. |
| 7.5.1 GENERAL. |
| 7.5.1.1 EXITS SHALL BE LOCATED, AND EXIT ACCESS SHALL |
| BE ARRANGED, SO THAT EXITS ARE READILY ACCESSIBLE AT |
| ALL TIMES. |
| 7.5.1.1.1* WHERE EXITS ARE NOT IMMEDIATELY ACCESSIBLE |
| FROM AN OPEN FLOOR AREA, CONTINUOUS PASSAGEWAYS, |
| AISLES, OR CORRIDORS LEADING DIRECTLY TO EVERY EXIT |
| SHALL BE MAINTAINED AND SHALL BE ARRANGED TO PROVIDE |
| ACCESS FOR EACH OCCUPANT TO NOT LESS THAN TWO EXITS BY |
| SEPARATE WAYS OF TRAVEL, UNLESS OTHERWISE PROVIDED IN |
| 7.5.1.1.3 AND 7.5.1.1.4. |
| |
| 28.3.6 CORRIDORS. |
| 28.3.6.1 WALLS. |
| 28.3.6.1.1 EXIT ACCESS CORRIDOR WALLS SHALL COMPLY WITH |
| 28.3.6.1.2 OR 28.3.6.1.3. |
| 28.3.6.1.2 IN BUILDINGS NOT COMPLYING WITH 28.3.6.1.3, |
| EXIT ACCESS CORRIDOR WALLS SHALL CONSIST OF FIRE |
| BARRIERS IN ACCORDANCE WITH SECTION 8.3 THAT HAVE NOT |
| LESS THAN A 1-HOUR FIRE RESISTANCE RATING. |
| 28.3.6.1.3 IN BUILDINGS PROTECTED THROUGHOUT BY AN |
| APPROVED, SUPERVISED AUTOMATIC SPRINKLER SYSTEM IN |
| ACCORDANCE WITH 28.3.5, CORRIDOR WALLS SHALL HAVE A |
| MINIMUM?-HOUR FIRE RESISTANCE RATING. |
| |
| THE ARRANGEMENTS OF THE EXITS ARE NOT IMMEDIATELY |
| ACCESSIBLE AND DO NOT MEET THE PROVISIONS INDICATED. |
| |
| A PROTECTED CORRIDOR IS REQUIRED OR EACH FLOOR LEVEL. |
| |
| |
| |
| 4) SHEET LS 1.01 & A 2.01B - A BASEMENT IS INDICATED |
| WITH ONLY ONE (1) EXIT. |
| |
| PER NFPA 101, CHAPTER 28, |
| |
| 28.2.4 NUMBER OF MEANS OF EGRESS. |
| 28.2.4.1 MEANS OF EGRESS SHALL COMPLY WITH ALL OF THE |
| FOLLOWING, EXCEPT AS OTHERWISE PERMITTED BY 28.2.4.2 |
| AND 28.2.4.3: |
| (1) THE NUMBER OF MEANS OF EGRESS SHALL BE IN |
| ACCORDANCE WITH SECTION 7.4. |
| (2) NOT LESS THAN TWO SEPARATE EXITS SHALL BE PROVIDED |
| ON EVERY STORY. |
| (3) NOT LESS THAN TWO SEPARATE EXITS SHALL BE |
| ACCESSIBLE FROM EVERY PART OF EVERY STORY. |
| |
| 7.4* NUMBER OF MEANS OF EGRESS. |
| 7.4.1 GENERAL. |
| 7.4.1.1 THE NUMBER OF MEANS OF EGRESS FROM ANY BALCONY, |
| MEZZANINE, STORY, OR PORTION THEREOF SHALL BE NOT LESS |
| THAN TWO, EXCEPT UNDER ONE OF THE FOLLOWING CONDITIONS: |
| (1) A SINGLE MEANS OF EGRESS SHALL BE PERMITTED WHERE |
| PERMITTED IN CHAPTERS 11 THROUGH 43. |
| (2) A SINGLE MEANS OF EGRESS SHALL BE PERMITTED FOR A |
| MEZZANINE OR BALCONY WHERE THE COMMON PATH OF TRAVEL |
| LIMITATIONS OF CHAPTERS 11 THROUGH 43 ARE MET. |
| 7.4.1.2 THE NUMBER OF MEANS OF EGRESS FROM ANY STORY OR |
| PORTION THEREOF, OTHER THAN FOR EXISTING BUILDINGS AS |
| PERMITTED IN CHAPTERS 11 THROUGH 43, SHALL BE AS |
| FOLLOWS: |
| (1) OCCUPANT LOAD MORE THAN 500 BUT NOT MORE THAN 1000 |
| ? NOT LESS THAN 3 |
| (2) OCCUPANT LOAD MORE THAN 1000 ? NOT LESS THAN 4 |
| |
| PLEASE PROVIDE A SECOND (2ND) EXIT FORM THE BASEMENT. |
| |
| |
| 5) SHEET LS 1.01 & M 1.00 - THERE IS NO INDICATIONS OF |
| SMOKE VENTING IN/FROM THE BASEMENT AREA. |
| |
| NFPA 101 CHAPTER 11 SPECIAL STRUCTURES AND HIGH-RISE |
| BUILDINGS |
| 11.7 UNDERGROUND AND LIMITED ACCESS STRUCTURES. |
| 11.7.4 ADDITIONAL PROVISIONS FOR UNDERGROUND |
| STRUCTURES. |
| 11.7.4.1 A STRUCTURE OR PORTION OF A STRUCTURE SHALL |
| NOT BE CONSIDERED AN UNDERGROUND STRUCTURE IF THE STORY |
| IS PROVIDED, ON NOT LESS THAN TWO SIDES, WITH NOT LESS |
| THAN 20 FT2 (1.9 M2) OF EMERGENCY ACCESS OPENING |
| LOCATED ENTIRELY ABOVE THE ADJOINING FINISHED GROUND |
| LEVEL IN EACH 50 LINEAL FT (15 LINEAL M) OF EXTERIOR |
| ENCLOSING WALL AREA. |
| 11.7.4.2 THE REQUIREMENTS OF 11.7.3 SHALL APPLY. |
| 11.7.4.4 THE UNDERGROUND PORTIONS OF AN UNDERGROUND |
| STRUCTURE,OTHER THAN AN EXISTING UNDERGROUND STRUCTURE, |
| SHALL BE PROVIDED WITH APPROVED AUTOMATIC SMOKE VENTING |
| IN ACCORDANCE WITH SECTION 9.3 WHERE THE UNDERGROUND |
| STRUCTURE HAS THE FOLLOWING FEATURES: |
| (1) OCCUPANT LOAD OF MORE THAN 100 PERSONS IN THE |
| UNDERGROUND PORTIONS OF THE STRUCTURE |
| (2) FLOOR LEVEL USED FOR HUMAN OCCUPANCY LOCATED MORE |
| THAN 30 FT (9.1 M) BELOW THE LOWEST LEVEL OF EXIT |
| DISCHARGE, OR MORE THAN ONE LEVEL LOCATED BELOW THE |
| LOWEST LEVEL OF EXIT DISCHARGE |
| (3) COMBUSTIBLE CONTENTS, COMBUSTIBLE INTERIOR FINISH, |
| OR COMBUSTIBLE CONSTRUCTION |
| |
| PLEASE PROVIDE SMOKE VENTING FOR THE BASEMANT AREA AS |
| REQUIRED PER (3). |
| |
| |
| |
| 6) SHEET LS 1.01 & 2-5 FLOOR PLAN SHEETS - THERE |
| APPEARS TO BE TWO(2) UNPROTECTED VERICAL OPENINGS: |
| |
| A.THE AREA ON THE WEST SIDE OPENING FROM THE PARKING |
| GARAGE UP THROUGH THE ROOF. |
| B. THE AREA LOCATED MORE NORTH INTERIOR FROM THE SECOND |
| (2ND) FLOOR THROUGH THE ROOF. |
| |
| NFPA 101, CHAPTER 28 |
| 28.3 PROTECTION. |
| 28.3.1 PROTECTION OF VERTICAL OPENINGS. |
| 28.3.1.1 VERTICAL OPENINGS SHALL COMPLY WITH 28.3.1.1.1 |
| THROUGH 28.3.1.2. |
| 28.3.1.1.1 VERTICAL OPENINGS SHALL BE ENCLOSED OR |
| PROTECTED IN ACCORDANCE WITH SECTION 8.6. |
| 28.3.1.1.2 VERTICAL OPENINGS IN ACCORDANCE WITH 8.6.9.1 |
| SHALL BE PERMITTED. |
| 28.3.1.1.3 IN BUILDINGS, OTHER THAN HIGH-RISE |
| BUILDINGS, THAT ARE PROTECTED THROUGHOUT BY AN |
| APPROVED, SUPERVISED AUTOMATIC SPRINKLER SYSTEM IN |
| ACCORDANCE WITH 28.3.5, THE WALLS ENCLOSING VERTICAL |
| OPENINGS SHALL HAVE A MINIMUM 1-HOUR FIRE RESISTANCE |
| RATING, AND DOORS SHALL HAVE A MINIMUM 1-HOUR FIRE |
| PROTECTION RATING. |
| |
| 8.6 VERTICAL OPENINGS. |
| 8.6.1 FLOOR SMOKE BARRIERS. EVERY FLOOR THAT SEPARATES |
| STORIES IN A BUILDING SHALL MEET THE FOLLOWING |
| CRITERIA: |
| (1) IT SHALL BE CONSTRUCTED AS A SMOKE BARRIER IN |
| ACCORDANCE WITH SECTION 8.5. |
| (2) IT SHALL BE PERMITTED TO HAVE OPENINGS AS DESCRIBED |
| BY 8.6.6, 8.6.7, 8.6.8, 8.6.9, OR CHAPTERS 11 THROUGH |
| 43. 8.6.2* CONTINUITY. OPENINGS THROUGH FLOORS SHALL BE |
| ENCLOSED WITH FIRE BARRIER WALLS, SHALL BE CONTINUOUS |
| FROM FLOOR TO FLOOR, OR FLOOR TO ROOF, AND SHALL BE |
| PROTECTED AS APPROPRIATE FOR THE FIRE RESISTANCE RATING |
| OF THE BARRIER. |
| |
| PLEASE PROVIDE THE REQUIRED PROTECTION AS INDICATED. |
| |
| |
| |
| 7) SHEETS A 2.02 - 2.04 - A H.K. ROOM IS INDICATED THAT |
| INCLUDES A LAUNDRY CHUTE. NO DIMENSIONS ARE INDICATED |
| OF THE SIZE OF ROOM. |
| |
| PER NFPA 101 CHAPTER 28 |
| 28.5.4 RUBBISH CHUTES, INCINERATORS, AND LAUNDRY |
| CHUTES. RUBBISH CHUTES, INCINERATORS, AND LAUNDRY |
| CHUTES SHALL COMPLY WITH THE PROVISIONS OF SECTION 9.5. |
| |
| 9.5 RUBBISH CHUTES, INCINERATORS, AND LAUNDRY CHUTES. |
| 9.5.1 ENCLOSURE. |
| 9.5.1.1 RUBBISH CHUTES AND LAUNDRY CHUTES SHALL BE |
| SEPARATELY ENCLOSED BY WALLS OR PARTITIONS IN |
| ACCORDANCE WITH THE PROVISIONS OF SECTION 8.3. |
| |
| 9.5.1.4 THE ROOM USED FOR ACCESSING THE CHUTE OPENING |
| SHALL BE SEPARATED FROM OTHER SPACES IN ACCORDANCE WITH |
| SECTION 8.7. |
| 9.5.1.5 THE REQUIREMENTS OF 9.5.1.1 THROUGH 9.5.1.4 |
| SHALL NOT APPLY WHERE OTHERWISE PERMITTED BY THE |
| FOLLOWING: |
| (1) EXISTING INSTALLATIONS HAVING PROPERLY ENCLOSED |
| SERVICE CHUTES AND PROPERLY INSTALLED AND MAINTAINED |
| SERVICE OPENINGS SHALL BE PERMITTED TO HAVE INLETS OPEN |
| TO A CORRIDOR OR NORMALLY OCCUPIED SPACE. |
| (2) RUBBISH CHUTES AND LAUNDRY CHUTES SHALL BE |
| PERMITTED TO OPEN INTO ROOMS NOT EXCEEDING 400 FT2 (37 |
| M2) THAT ARE USED FOR STORAGE, PROVIDED THAT THE ROOM |
| IS PROTECTED BY AUTOMATIC SPRINKLERS. |
| |
| THOUGH IT APPEARS TO COMPLY, PLEASE PROVIDE DIMENSIONS |
| TO ENSURE COMPLAINCE WITH THE ABOVE (2). |
| |
| |
| |
| 8) SHEETS A 2.02 - 2.04 - A H.K. ROOM IS INDICATED THAT |
| INCLUDES A LAUNDRY CHUTE. THE ROOM IS NOT INDICATED AS |
| BEING PROTECTED UNDER THE REQUIREMENTS OF THE |
| FOLLOWING. |
| |
| 9.5.1.4 THE ROOM USED FOR ACCESSING THE CHUTE OPENING |
| SHALL BE SEPARATED FROM OTHER SPACES IN ACCORDANCE WITH |
| SECTION 8.7. |
| |
| 8.7.1.2 IN NEW CONSTRUCTION, WHERE PROTECTION IS |
| PROVIDED WITH AUTOMATIC EXTINGUISHING SYSTEMS WITHOUT |
| FIRE-RESISTIVE SEPARATION, THE SPACE PROTECTED SHALL BE |
| ENCLOSED WITH SMOKE PARTITIONS IN ACCORDANCE WITH |
| SECTION 8.4, UNLESS OTHERWISE PERMITTED BY ONE OF THE |
| FOLLOWING CONDITIONS: |
| (1) WHERE MERCANTILE OCCUPANCY GENERAL STORAGE AREAS |
| AND STOCKROOMS ARE PROTECTED BY AUTOMATIC SPRINKLERS IN |
| ACCORDANCE WITH SECTION 9.7 |
| (2) WHERE HAZARDOUS AREAS IN INDUSTRIAL OCCUPANCIES ARE |
| PROTECTED BY AUTOMATIC EXTINGUISHING SYSTEMS IN |
| ACCORDANCE WITH 40.3.2 |
| (3) WHERE HAZARDOUS AREAS IN DETENTION AND CORRECTIONAL |
| OCCUPANCIES ARE PROTECTED BY AUTOMATIC SPRINKLERS IN |
| ACCORDANCE WITH 22.3.2 |
| |
| NFPA 82 INCINERATORS AND WASTE AND LINEN HANDLING |
| SYSTEMS AND EQUIPMENT |
| |
| 5.2.5 SERVICE OPENING ROOMS. |
| 5.2.5.1 GENERAL. |
| 5.2.5.1.1 EVERY SERVICE OPENING SHALL BE IN A ROOM OR |
| COMPARTMENT THAT IS SEPARATED FROM THE OTHER PARTS OF |
| THE BUILDING BY WALLS, PARTITIONS, FLOORS, AND |
| FLOOR-CEILING ASSEMBLIES HAVING A FIRE RESISTANCE |
| RATING OF NOT LESS THAN THE REQUIRED RATING OF |
| THE CHUTE ENCLOSURE. |
| 5.2.5.1.2 WHERE SERVICE OPENING ROOMS ARE PROTECTED BY |
| AUTOMATIC SPRINKLERS, THE ROOM SHALL BE ENCLOSED IN A |
| MINIMUM OF 1-HOUR CONSTRUCTION, AND OPENINGS SHALL BE |
| PROTECTED WITH 3?4-HOUR FIRE-RATED DOORS. |
| 5.2.5.1.3 OPENINGS INTO SUCH A ROOM OR COMPARTMENT |
| SHALL BE PROTECTED BY APPROVED SELF-CLOSING DOORS THAT |
| ARE APPROPRIATE FOR PROTECTING THE OPENINGS OR ARE OF |
| NOT LESS THAN A 1?HOUR PARTITION RATING WITH A 3?4-HOUR |
| FIRE-RATED DOOR. |
| 5.2.5.1.4 THE SIZE OF THE SERVICE OPENING ROOM OR |
| COMPARTMENT SHALL NOT BE LESS THAN THAT REQUIRED TO |
| MAINTAIN A MINIMUM 152.4 MM (6 IN.) CLEARANCE BETWEEN |
| THE INTAKE OPENING AND THE CLOSED SERVICE OPENING ROOM |
| DOOR. |
| |
| PLEASE PROVIDE PROTECTION AS REQUIRED FOR ALL WALLS |
| SURROUNDING THE LAUNDRY CHUTE ROOM, INCLUDING THE |
| CORRIDOR WALL AND JANITOR/MECHANICAL ROOMS. |
| |
| |
| |
| 9) SHEETS A 2.02 - 2.04 - A H.K. ROOM IS INDICATED THAT |
| INCLUDES A LAUNDRY CHUTE. THE DOOR TO THE LAUNDRY CHUTE |
| ROOM; 8, AND MECHANICAL ROOM; 10, ARE NOT INDICATED AS |
| HAVING ANY RATING OR CLSING DEVICES PER DOOR SCHEDULE |
| SHHET A 9.02. |
| |
| 9.5.1.4 THE ROOM USED FOR ACCESSING THE CHUTE OPENING |
| SHALL BE SEPARATED FROM OTHER SPACES IN ACCORDANCE WITH |
| SECTION 8.7. |
| |
| 8.7.1.3 DOORS IN BARRIERS REQUIRED TO HAVE A FIRE |
| RESISTANCE RATING SHALL HAVE A MINIMUM ?-HOUR FIRE |
| PROTECTION RATING AND SHALL BE SELF-CLOSING OR |
| AUTOMATIC-CLOSING IN ACCORDANCE WITH 7.2.1.8. |
| |
| PLEASE PROVIDE FOR THE DOOR REQUIREMENTS. |
| |
| |
| |
| 10) SHEET A 6.05 & A 2.02 - A 2.04 - THE LINEN CHUTE |
| CHASE DOES NOT INDICATE AND FIRE RATING. |
| |
| NFPA 82 INCINERATORS AND WASTE AND LINEN HANDLING |
| SYSTEMS AND EQUIPMENT |
| |
| 5.2.3 CHUTE ENCLOSURE (CHASE). |
| 5.2.3.1 GENERAL. |
| 5.2.3.1.1 VERTICAL WASTE OR LINEN CHUTES IN ALL STORIES |
| ABOVE THE STORAGE OR COMPACTING ROOM SHALL BE ENCLOSED |
| WITHIN A CONTINUOUS FIRE-RATED ENCLOSURE CONSISTENT |
| WITH THE CONSTRUCTION TYPE. |
| 5.2.3.1.2 THE WALLS OF THE ENCLOSURE SHALL HAVE A FIRE |
| RESISTANCE RATING OF NOT LESS THAN 2 HOURS IF THE |
| BUILDING IS FOUR OR MORE STORIES IN HEIGHT AND NOT LESS |
| THAN 1 HOUR IF THE BUILDING IS LESS THAN FOUR STORIES |
| IN HEIGHT. |
| 5.2.3.1.3 OPENINGS IN THE FIRE-RATED ENCLOSURE SHALL BE |
| AS FOLLOWS: |
| (1) 11?2-HOUR FIRE RESISTANCE RATING FOR 2 HOUR?RATED |
| ENCLOSURES |
| (2) 1-HOUR FIRE RESISTANCE RATING FOR 1 HOUR?RATED |
| ENCLOSURES |
| |
| PLEASE PROVIDE THE INDICATED FIRE RATED PROTECTION. |
| |
| |
| |
| 11) SHEET B - THE LAUNDRY CHUTE DISCHARPE ROOM DOES NOT |
| INDICATED AN FIRE RATING. |
| |
| NFPA 82 INCINERATORS AND WASTE AND LINEN HANDLING |
| SYSTEMS AND EQUIPMENT |
| |
| 5.2.4 CHUTE DISCHARGE ROOMS. |
| 5.2.4.1 GENERAL. |
| 5.2.4.1.1 WASTE AND LINEN CHUTES SHALL TERMINATE OR |
| DISCHARGE DIRECTLY INTO A ROOM HAVING A MINIMUM FIRE |
| RESISTANCE RATING NOT LESS THAN THAT SPECIFIED FOR THE |
| CHUTE. |
| 5.2.4.1.2 OPENINGS INTO SUCH A ROOM OR COMPARTMENT |
| SHALL BE PROTECTED BY APPROVED SELF-CLOSING FIRE DOORS |
| HAVING A MINIMUM FIRE PROTECTION RATING NOT LESS THAN |
| SPECIFIED FOR THE CHUTE. |
| |
| PLEASE PROVIDE FIRE RATING AS REQUIRED. |
| |
| |
| |
| 12) SHEETS A 2.02 - 2.03 - THE H.K. ROOM APPEARS TO |
| HAVE A TRASH RECEPTICLE LOCATED WITHIN IT. THE ROOM CAN |
| BE USED FOR STORAGE BUT IT CAN NOT BE USED AS A TRASH |
| ROOM. |
| |
| 9.5.1.4 THE ROOM USED FOR ACCESSING THE CHUTE OPENING |
| SHALL BE SEPARATED FROM OTHER SPACES IN ACCORDANCE WITH |
| SECTION 8.7. |
| 9.5.1.5 THE REQUIREMENTS OF 9.5.1.1 THROUGH 9.5.1.4 |
| SHALL NOT APPLY WHERE OTHERWISE PERMITTED BY THE |
| FOLLOWING: |
| (1) EXISTING INSTALLATIONS HAVING PROPERLY ENCLOSED |
| SERVICE CHUTES AND PROPERLY INSTALLED AND MAINTAINED |
| SERVICE OPENINGS SHALL BE PERMITTED TO HAVE INLETS OPEN |
| TO A CORRIDOR OR NORMALLY OCCUPIED SPACE. |
| (2) RUBBISH CHUTES AND LAUNDRY CHUTES SHALL BE |
| PERMITTED TO OPEN INTO ROOMS NOT EXCEEDING 400 FT2 (37 |
| M2) THAT ARE USED FOR STORAGE, PROVIDED THAT THE ROOM |
| IS PROTECTED BY AUTOMATIC SPRINKLERS. |
| |
| FOR PURPOSES OF IDENTIFYING STORAGE: |
| 3.3.188.15* STORAGE OCCUPANCY. AN OCCUPANCY USED |
| PRIMARILY FOR THE STORAGE OR SHELTERING OF GOODS, |
| MERCHANDISE, PRODUCTS, OR VEHICLES. |
| |
| PER (2), THE ROOM CAN BE USED FOR STORAGE PURPOSES. |
| TRASH IS NOT CONSIDERED AS ALLOWABLE WITHIN THIS ROOM. |
| |
| |
| |
| 13) SHEET A 2.04 - THE H.K. ROOM IS INDICATED AS HAVING |
| A MECHANICAL ROOM; SHEET E 1.03 INDICATES IT AS A |
| BOILER ROOM, WITH WHAT APPEARS TO BE WATER HEATERS. THE |
| H.K. ROOM IS DIFFERENT THAN ALL OTHER FLOORS LEVELS. |
| PLEASE CONFIRM AND PROVIDE CLARIFYING NARRATIVE. |
| |
| 9.5.1.4 THE ROOM USED FOR ACCESSING THE CHUTE OPENING |
| SHALL BE SEPARATED FROM OTHER SPACES IN ACCORDANCE WITH |
| SECTION 8.7. |
| 9.5.1.5 THE REQUIREMENTS OF 9.5.1.1 THROUGH 9.5.1.4 |
| SHALL NOT APPLY WHERE OTHERWISE PERMITTED BY THE |
| FOLLOWING: |
| (1) EXISTING INSTALLATIONS HAVING PROPERLY ENCLOSED |
| SERVICE CHUTES AND PROPERLY INSTALLED AND MAINTAINED |
| SERVICE OPENINGS SHALL BE PERMITTED TO HAVE INLETS OPEN |
| TO A CORRIDOR OR NORMALLY OCCUPIED SPACE. |
| (2) RUBBISH CHUTES AND LAUNDRY CHUTES SHALL BE |
| PERMITTED TO OPEN INTO ROOMS NOT EXCEEDING 400 FT2 (37 |
| M2) THAT ARE USED FOR STORAGE, PROVIDED THAT THE ROOM |
| IS PROTECTED BY AUTOMATIC SPRINKLERS. |
| |
| A. PER (2), THE ROOM CAN BE USED FOR STORAGE PURPOSES. |
| WATER HEATERS ARE NOT CONSIDERED AS ALLOWABLE WITHIN |
| THIS ROOM. |
| B. HOW WILL THE WATER HEATERS BE POWERED? |
| C. WHERE IS THE TRASH RECEPTICLE LOCATED ON THIS FLOOR. |
| |
| |
| |
| |
| 14) SHEETS FP 2.01 - 2.03 - THE ROOMS INDICATED AS |
| SUANA ARE NOT PROVIDED WITH FIRE SPRINKLER PROTECTION. |
| |
| CHAPTER 4 GENERAL REQUIREMENTS |
| 4.1 LEVEL OF PROTECTION. A BUILDING, WHERE PROTECTED BY |
| AN AUTOMATIC SPRINKLER SYSTEM INSTALLATION, SHALL BE |
| PROVIDED WITH SPRINKLERS IN ALL AREAS EXCEPT WHERE |
| SPECIFIC SECTIONS OF THIS STANDARD PERMIT THE OMISSION |
| OF SPRINKLERS. |
| |
| THERE IS NO OMISSION OF SPRINKLERS FOR THIS ROOM. |
| |
| PLEASE PROVIDE FOR FIRE SPRINKLER PROTECTION. |
| |
| |
| |
| |
| 15) COMMENT # 6 RESTATED FOR SHEETS FP - THE IS NO |
| INDICATIONS OF FIRE PROTECTION OF THE VERITCAL OPENINGS |
| ALONG THE WEST SIDE AND FLOORS 2-5 OPENING IN THE NORTH |
| INTRERIOR AREA. |
| |
| 28.3 PROTECTION. |
| 28.3.1 PROTECTION OF VERTICAL OPENINGS. |
| 28.3.1.1 VERTICAL OPENINGS SHALL COMPLY WITH 28.3.1.1.1 |
| THROUGH 28.3.1.2. |
| 28.3.1.1.1 VERTICAL OPENINGS SHALL BE ENCLOSED OR |
| PROTECTED IN ACCORDANCE WITH SECTION 8.6. |
| 28.3.1.1.2 VERTICAL OPENINGS IN ACCORDANCE WITH 8.6.9.1 |
| SHALL BE PERMITTED. |
| 28.3.1.1.3 IN BUILDINGS, OTHER THAN HIGH-RISE |
| BUILDINGS, THAT ARE PROTECTED THROUGHOUT BY AN |
| APPROVED, SUPERVISED AUTOMATIC SPRINKLER SYSTEM IN |
| ACCORDANCE WITH 28.3.5, THE WALLS ENCLOSING VERTICAL |
| OPENINGS SHALL HAVE A MINIMUM 1-HOUR FIRE RESISTANCE |
| RATING, AND DOORS SHALL HAVE A MINIMUM 1-HOUR FIRE |
| PROTECTION RATING. |
| |
| 8.6 VERTICAL OPENINGS. |
| 8.6.1 FLOOR SMOKE BARRIERS. EVERY FLOOR THAT SEPARATES |
| STORIES IN A BUILDING SHALL MEET THE FOLLOWING |
| CRITERIA: |
| (1) IT SHALL BE CONSTRUCTED AS A SMOKE BARRIER IN |
| ACCORDANCE WITH SECTION 8.5. |
| (2) IT SHALL BE PERMITTED TO HAVE OPENINGS AS DESCRIBED |
| BY 8.6.6, 8.6.7, 8.6.8, 8.6.9, OR CHAPTERS 11 THROUGH |
| 43. 8.6.2* CONTINUITY. OPENINGS THROUGH FLOORS SHALL BE |
| ENCLOSED WITH FIRE BARRIER WALLS, SHALL BE CONTINUOUS |
| FROM FLOOR TO FLOOR, OR FLOOR TO ROOF, AND SHALL BE |
| PROTECTED AS APPROPRIATE FOR THE FIRE RESISTANCE RATING |
| OF THE BARRIER. |
| |
| PLEASE PROVIDE THE REQUIRED PROTECTION AS INDICATED. |
| |
| |
| |
| 16) SHEET FP 1.04 - A ROOF MANIFOLD IS INDICATED ON THE |
| NORTH WEST SIDE OF THE ROOF. THE IS INSUFFICIENT AREA |
| IN FRONT OF THE MANIFOLD TO ALLOW FOR FIRE OPERATIONS. |
| |
| 13.1.3 OBSTRUCTIONS SHALL NOT BE PLACED OR KEPT NEAR |
| FIRE HYDRANTS, FIRE DEPARTMENT INLET CONNECTIONS, OR |
| FIRE PROTECTION SYSTEM CONTROL VALVES IN A MANNER THAT |
| WOULD PREVENT SUCH EQUIPMENT OR FIRE HYDRANTS FROM |
| BEING IMMEDIATELY VISIBLE AND ACCESSIBLE. |
| 13.1.4 A MINIMUM 36 IN. (91 MM) OF CLEAR SPACE SHALL BE |
| MAINTAINED TO PERMIT ACCESS TO AND OPERATION OF FIRE |
| PROTECTION EQUIPMENT, FIRE DEPARTMENT INLET |
| CONNECTIONS, OR FIRE PROTECTION SYSTEM CONTROL VALVES. |
| THE FIRE DEPARTMENT SHALL NOT BE DETERRED OR HINDERED |
| FROM GAINING IMMEDIATE ACCESS TO FIRE PROTECTION |
| EQUIPMENT. |
| 13.1.4.1 AN APPROVED CLEAR AND UNOBSTRUCTED PATH SHALL |
| BE PROVIDED AND MAINTAINED FOR ACCESS TO THE FIRE |
| DEPARTMENT INLET CONNECTIONS. |
| |
| PLEASE PROVIDE FOR THE MINMIMUM REQUIREMENT BY |
| REPOSITIONING, TURNING, RELOCATION OTHER OTHER SIMILAR |
| REMEDY. |
| |
| |
| |
| 17) ROOF SHEETS - THE ROOF IS INDICATED WITH A SPACE |
| THAT IS OPEN TO THE 2ND FLLOR BELOW. FOR FIREFIGHTER |
| FIRE OPERATIONAL SAFETY, THOUGH THIS OPENING APPEARS TO |
| HAVE A PARAPET WALL, PLEASE PROVIDE REFLECTIVE SIGNAGE |
| ON ALL FOUR SIDES "DANGER, OPENING THROUGH TO 2ND |
| FLOOR" OR SIMILAR. |
| |
| |
| |
| 18) ROOF SHEETS - THERE IS A PARAPET WALL INDICATED ON |
| THE EAST AND WEST SIDES WITH OPEN TRELLIS CONSTRUCTION |
| ON THE OTHER SIDE. FOR FIREFIGHTER FIRE OPERATIONAL |
| SAFETY, PLEASE PROVIDE REFLECTIVE SIGNAGE, "DANGER, |
| OPEN TRELLS BEAMS ON OTHER SIDE" OR SIMILAR IN MULTIPLE |
| LOCATIONS. |
| |
| |
| |
| 19) SHEET A 2.01A & A 9.02 - GATE DOORS AND GATES ARE |
| INDICATED ON THE PERIMETER OF THE BUILDING SITE. THESE |
| GATES ARE LOCATED IN THE EGRESS PATH OF TRAVEL. THE |
| DOOR SCHEDULE INDICATES THERE ARE LOCKED. THESE GATES |
| SHALL IMPEDE EGRESS AND SHALL COMPLY WITH NFPA |
| 101,CHAPTER 28 & CHAPTER 7, MEANS OF EGRESS |
| |
| 28.2.2.2 DOORS. |
| 28.2.2.2.1 DOORS COMPLYING WITH 7.2.1 SHALL BE |
| PERMITTED. |
| 28.2.2.2.2 DOOR-LOCKING ARRANGEMENTS SHALL COMPLY WITH |
| 28.2.2.2.2.1, 28.2.2.2.2.2, 28.2.2.2.2.3, OR |
| 28.2.2.2.2.4. |
| 28.2.2.2.2.1 NO DOOR IN ANY MEANS OF EGRESS SHALL BE |
| LOCKED AGAINST EGRESS WHEN THE BUILDING IS OCCUPIED. |
| |
| 7.2.1.5 LOCKS, LATCHES, AND ALARM DEVICES. |
| 7.2.1.5.1 DOOR LEAVES SHALL BE ARRANGED TO BE OPENED |
| READILY FROM THE EGRESS SIDE WHENEVER THE BUILDING IS |
| OCCUPIED. |
| 7.2.1.5.2* THE REQUIREMENT OF 7.2.1.5.1 SHALL NOT APPLY |
| TO DOOR LEAVES OF LISTED FIRE DOOR ASSEMBLIES AFTER |
| EXPOSURE TO ELEVATED TEMPERATURE IN ACCORDANCE WITH THE |
| LISTING, BASED ON LABORATORY FIRE TEST PROCEDURES. |
| 7.2.1.5.3 LOCKS, IF PROVIDED, SHALL NOT REQUIRE THE USE |
| OF A KEY, A TOOL, OR SPECIAL KNOWLEDGE OR EFFORT FOR |
| OPERATION FROM THE EGRESS SIDE. |
| 7.2.1.5.4 THE REQUIREMENTS OF 7.2.1.5.1 AND 7.2.1.5.3 |
| SHALL NOT APPLY WHERE OTHERWISE PROVIDED IN CHAPTERS 18 |
| THROUGH 23. |
| |
| PLEASE PROVIDE LOCKS/LATCHES IN COMPLIANCE WITH THE |
| REQUIRMENT. |
| |
| |
| |
| 20) SHEET A 8.02 - A GREEN SCREEN PANEL IS INDICATED ON |
| THE WEST OUTSIDE WALL ATTACHED TO AN ALUMINUM |
| STRUCTURE. |
| |
| PLEASE PROVIDE THE SCREEN FABRIC SPECIFICATION SHEET |
| THAT INDICATES ANY FLAME AND SMOKE SPREAD RATING, FIRE |
| RATINGS, FIRE PROTECTION FEATURES, ETC. |
| |
| |
| |
| 21) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| RE-SUBMITTAL OF THE ABOVE. |
| |
| |
| |
| PETER LEDUC |
| FIRE MARSHAL |
| 561-804-4709 |
| [email protected] |
| |
| |