2016-07-28 07:17:33INITIAL ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011
 COMMENTS:
  
 1. GENERAL NOTES TO CONSTRUCTION DOCUMENTS: PLEASE
 PROVIDE A BLOCK NOTE INDICATING THE REQUIRED SEPARATE
 PERMITS AND DATA CUT SHEET SUBMITTALS FOR ALL SITE
 LIGHTING AND ASSOCIATED EQUIPMENT, ALL LOW VOLTAGE
 SYSTEMS TO INCLUDE BUT NOT LIMITED TO FIRE ALARM,
 ACCESS CONTROLS, CCTV, PHONE AND DATA, SIGNAGE,
 WIRELESS SYSTEMS, ELEVATORS, CAR CHARGING STATIONS,
 POOLS IN UNITS, ETC. A NOTE WILL SUFFICE.
 2. SHEET E1.00- PLEASE ADD A GENERAL NOTE TO SHEET TO
 INDICATE THE REQUIREMENTS OF NEC 300.5D3 AND TABLE
 300.5 FOR MINIMUM COVER REQUIREMENTS FOR CONDUITS AND
 THE PLACEMENT OF A WARNING RIBBON FOR THE SERVICE
 LATERAL CONDUCTORS SHOWN FOR THIS PROJECT. A NOTE WILL
 SUFFICE
 3. SHEET E1.00- ADD A NOTE TO MAINTAIN ALL ELECTRICAL
 EQUIPMENT ABOVE THE BASELINE FLOOD ELEVATION PER STATE
 AND CITY REGULATORY AGENCIES.
 4. ADDRESS ALL FIRE COMMENTS RELATED TO ELECTRICAL
 DESIGN. FBC 107.3.5
 5. PER FBC ENERGY CONSERVATION 2014 C405.7 PROVIDE
 REQUIRED VOLTAGE DROP CALCULATIONS FOR FEEDERS AND
 BRANCH CIRCUIT
 6. PER NEC 110.16 ARC FLASH WARNING- SEE CODE. GENERAL
 NOTE WILL SUFFICE AT RISER DIAGRAM
 7. PER NEC 110.24A- AVAILABLE FAULT CURRENT- FIELD
 MARKINGS. ADD GENERAL NOTE INDICATING REQUIREMENTS AT
 THE SERVICE. A NOTE WILL SUFFICE
 8. PROVIDE AIC CALCULATIONS PER NEC 110.9 AND 110.10-
 SHOW AIC AT THE FPL TRANSFORMER WITH FPL LETTERHEAD
 INDICATING AVAILABLE FAULT CURRENT. FBC 107.3.5
 9. SUBMIT 1/2" DETAIL OF MAIN ELECTRICAL ROOM NOT 1/4"
 AS SHOWN. NEED TO VERIFY IF PER NEC 110.26C2
 UNOBSTRUCTED EGRESS IS MET PER DEPTH OF DISTANCE FROM
 EQUIPMENT TO DOOR PER AHJ PERMISSION.
 10. CORRECT TYPO AT RISER DIAGRAM TO SHOW ID PANEL MDPB
 NOT MDBA FOR MAIN #2.
 11. ADD A NOTE TO UNITS PER NEC 406.13- ALL GUEST UNITS
 TO HAVE TAMPER RESISTANT RECEPTACLES.
 12. PROVIDE A GENERAL NOTE TO UNITS TO INDICATE FOR NOW
 THE REQUIREMENTS OF NEC 680 POOLS EQUIPMENT LOCATION TO
 MAINTAIN DISTANCES REQUIRED FOR RECEPTACLES AND
 LIGHTING (DIMENSIONS MAY REQUIRE GFCI PROTECTION).
 SEPARATE POOL PERMITS WILL THEN BE REVIEWED PER SCOPE.
 FBC 107.3.5
 13. PLEASE CONFIRM IF PARKING AREA WILL HAVE
 VENTILATION FOR CO EXHAUST, SEE FIRE REVIEW AND ADDRESS
 ELECTRICAL SCOPE. FBC 107.3.5
 14. COMMENTS MAY FOLLOW UPON RE-REVIEW. PLEASE FEEL
 FREE TO CONTACT ME SHOULD YOU HAVE ANY QUESTIONS
 REGARDING THIS PROJECT.
  
  