2016-07-28 07:17:33 | INITIAL ELECTRICAL PLAN REVIEW |
| |
| APPLICABLE CODES IN EFFECT: |
| FLORIDA BUILDING CODE 2014 5TH EDITION |
| FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH |
| EDITION |
| NFPA 70- 2011 |
| COMMENTS: |
| |
| 1. GENERAL NOTES TO CONSTRUCTION DOCUMENTS: PLEASE |
| PROVIDE A BLOCK NOTE INDICATING THE REQUIRED SEPARATE |
| PERMITS AND DATA CUT SHEET SUBMITTALS FOR ALL SITE |
| LIGHTING AND ASSOCIATED EQUIPMENT, ALL LOW VOLTAGE |
| SYSTEMS TO INCLUDE BUT NOT LIMITED TO FIRE ALARM, |
| ACCESS CONTROLS, CCTV, PHONE AND DATA, SIGNAGE, |
| WIRELESS SYSTEMS, ELEVATORS, CAR CHARGING STATIONS, |
| POOLS IN UNITS, ETC. A NOTE WILL SUFFICE. |
| 2. SHEET E1.00- PLEASE ADD A GENERAL NOTE TO SHEET TO |
| INDICATE THE REQUIREMENTS OF NEC 300.5D3 AND TABLE |
| 300.5 FOR MINIMUM COVER REQUIREMENTS FOR CONDUITS AND |
| THE PLACEMENT OF A WARNING RIBBON FOR THE SERVICE |
| LATERAL CONDUCTORS SHOWN FOR THIS PROJECT. A NOTE WILL |
| SUFFICE |
| 3. SHEET E1.00- ADD A NOTE TO MAINTAIN ALL ELECTRICAL |
| EQUIPMENT ABOVE THE BASELINE FLOOD ELEVATION PER STATE |
| AND CITY REGULATORY AGENCIES. |
| 4. ADDRESS ALL FIRE COMMENTS RELATED TO ELECTRICAL |
| DESIGN. FBC 107.3.5 |
| 5. PER FBC ENERGY CONSERVATION 2014 C405.7 PROVIDE |
| REQUIRED VOLTAGE DROP CALCULATIONS FOR FEEDERS AND |
| BRANCH CIRCUIT |
| 6. PER NEC 110.16 ARC FLASH WARNING- SEE CODE. GENERAL |
| NOTE WILL SUFFICE AT RISER DIAGRAM |
| 7. PER NEC 110.24A- AVAILABLE FAULT CURRENT- FIELD |
| MARKINGS. ADD GENERAL NOTE INDICATING REQUIREMENTS AT |
| THE SERVICE. A NOTE WILL SUFFICE |
| 8. PROVIDE AIC CALCULATIONS PER NEC 110.9 AND 110.10- |
| SHOW AIC AT THE FPL TRANSFORMER WITH FPL LETTERHEAD |
| INDICATING AVAILABLE FAULT CURRENT. FBC 107.3.5 |
| 9. SUBMIT 1/2" DETAIL OF MAIN ELECTRICAL ROOM NOT 1/4" |
| AS SHOWN. NEED TO VERIFY IF PER NEC 110.26C2 |
| UNOBSTRUCTED EGRESS IS MET PER DEPTH OF DISTANCE FROM |
| EQUIPMENT TO DOOR PER AHJ PERMISSION. |
| 10. CORRECT TYPO AT RISER DIAGRAM TO SHOW ID PANEL MDPB |
| NOT MDBA FOR MAIN #2. |
| 11. ADD A NOTE TO UNITS PER NEC 406.13- ALL GUEST UNITS |
| TO HAVE TAMPER RESISTANT RECEPTACLES. |
| 12. PROVIDE A GENERAL NOTE TO UNITS TO INDICATE FOR NOW |
| THE REQUIREMENTS OF NEC 680 POOLS EQUIPMENT LOCATION TO |
| MAINTAIN DISTANCES REQUIRED FOR RECEPTACLES AND |
| LIGHTING (DIMENSIONS MAY REQUIRE GFCI PROTECTION). |
| SEPARATE POOL PERMITS WILL THEN BE REVIEWED PER SCOPE. |
| FBC 107.3.5 |
| 13. PLEASE CONFIRM IF PARKING AREA WILL HAVE |
| VENTILATION FOR CO EXHAUST, SEE FIRE REVIEW AND ADDRESS |
| ELECTRICAL SCOPE. FBC 107.3.5 |
| 14. COMMENTS MAY FOLLOW UPON RE-REVIEW. PLEASE FEEL |
| FREE TO CONTACT ME SHOULD YOU HAVE ANY QUESTIONS |
| REGARDING THIS PROJECT. |
| |
| |