Plan Review Notes
Plan Review Notes For Permit 16070830
Permit Number 16070830
Review Stop G
Sequence Number 2
Notes
Date Text
2016-08-08 06:27:441) THERE ARE TWO DIFFERENT SETS OF PLANS THAT ARE IN
 THE PERMIT FILE. WHICH PLANS ARE BEING SUBMITTED FOR
 PERMIT? THE CONTRACTOR NEEDS TO COME IN AND STRAIGHTEN
 OUT THIS SUBMITTAL AND SUBMIT TWO COMPLETE SETS OF
 PLANS FOR REVIEW. WPB AMEND. TO FBC SEC. 107.1.
 2) INDICATE ON THE APPLIANCE SPECIFICATIONS THE
 SPECIFIC MODEL BEING INSTALLED ( TANKLESS WATER
 HEATER).2ND REQUEST.
 3) THERE ARE THREE PERMIT APPLICATIONS FOR THE GAS
 INSTALLATION. THE CONTRACTOR INFORMATION ON ONE OF THE
 APPLICATIONS HAS BEEN ERASED. CLARIFY. 2ND REQUEST.
 4) INFORMATION HAS BEEN SUBMITTED THAT INDICATES THIS
 IS LESS THAN 2 PSI SYSTEM YET ONE SET OF GAS RISER
 DIAGRAMS SHOWS A REGULATOR AT EACH APPLIANCE. THIS
 MAKES ABSOLUTELY NO SENSE. CLARIFY.
 5) THE SPECIFICATION SHEETS FOR THE SAMSUNG GAS
 EQUIPMENT DOES NOT SHOW THAT THE EQUIPMENT IS LISTED
 AND LABELED PER 2014 FUEL GAS CODE SEC. 301.3.SUBMIT
 SPEC SHEETS THAT SHOWS THE APPLIANCES ARE LISTED AND
 LABELED.2ND REQUEST.
 6) INDICATE THE DELIVERY PRESSURE OF THE SYSTEM.
 7) THE DRYER SHALL BE PROVIDED WITH COMBUSTION AIR
 SINCE IT IS IN A ROOM WHERE THE DOOR CAN BE SHUT. 2014
 FGC SEC.304.1, 614.5.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  
  