2016-07-25 05:35:361.SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS THE
 LENGTH OF ALL CUT SECTIONS OF PIPE PER 2014 FBC-FUEL
 GAS, SECS. 402.4.1, 402.4.2. OR 2014 FBC-RES SEC.
 G2413.
  
 2. IS ALL THE PIPE BEING INSTALLED SCH. 40 METAL PIPE?
 INDICATE ALL TYPE OF PIPE MATERIAL ON THE PLANS. WPB
 AMENDMENTS TO FBC SEC.107.2.1.
  
 3..SUBMIT MANUFACTURER'S SPECIFICATION SHEETS /
 INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO VERIFY
 COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND
 FBC-2014 FUEL GAS CODE SEC. 402.2, AND 301.3 OR 2014
 FBC-RES. SEC. G2404.3. GAS APPLIANCES SHALL BE LISTED
 AND LABELED. THE INSTALLATION MANUALS FOR ALL GAS
 APPLIANCES / EQUIPMENT SHALL BE ONSITE AT THE TIME OF
 INSPECTION. FGC SEC.305.1, FBC-RES. SEC.G2408.1. THE
 SUBMITTED SPECS FOR THE RANGE AND WATER HEATER DO NOT
 SSHOW THE APPLIANCES ARE LISTED AND LABELED.
  
 4. SHOW THE DISTANCE FROM THE POINT OF DELIVERY, (METER
 OR MP REGULATOR) TO THE MOST REMOTE OUTLET IN THE
 BUILDING AND / OR SYSTEM PER THE 2014 FBC-FUEL GAS
 SEC.402.4.1 OR 2014 FBC-RES. SEC. G 2413.3.
  
 5. SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE 2014
 FBC-FUEL GAS CODE SEC.304.1 OR 2014 FBC-RES. SEC. G
 2407.
  
 6. INDICATE THE DELIVERY PRESSURE (PSI) OF THE SYSTEM
 ON THE PLAN PER 2014 FBC-FUEL GAS SEC.402.2 OR FBC RES.
 SEC. G2413.2. .
  
 7. SUBMIT A DETAIL SHOWING THE TYPE, LOCATION, SIZE AND
 TERMINATION OF THE GAS VENTS PER 2014 FBC-FUEL GAS
 SECS. 502 THRU 505 OR 2014 FBC-RES. SEC.G2426.
  
 8. SUBMIT COPIES OF THE SIZING TABLES BEING USED TO
 DESIGN THE SYSTEM OR INDICATE WHICH SIZING TABLES FROM
 WHICH STANDARD ARE BEING USED TO DESIGN THE SYSTEM. WPB
 AMEND. TO FBC SEC. 107.3.5.3, FBCR SEC.G2413.3, FGC
 SEC. 402.3.
  
 9) SUBMIT A FLOOR PLAN SHOWING THE LOCATION OF ALL GAS
 APPLIANCES.WPB AMEND. TO FBC SEC. 107.2.1.
  
 10) INDICATE ON THE APPLIANCE SPECIFICATIONS THE
 SPECIFIC MODEL BEING INSTALLED ( TANKLESS WATER
 HEATER).
  
 11) SHOW THE LOCATION ON THE GAS RISER DIAGRAM AND ALSO
 ON THE REQUESTED FLOOR PLAN.WPB AMEND. TO FBC SEC.
 107.2.1.
  
 12) THERE ARE TWO PERMIT APPLICATIONS FOR THE GAS
 INSTALLATION. THE CONTRACTOR INFORMATION ON ONE OF THE
 APPLICATIONS HAS BEEN ERASED. CLARIFY.
  