2016-08-30 10:26:32 | RESIDENTIAL (R3) ADDITION/ALTERATION BUILDING REVIEW |
| COMMENTS. |
| CODE: FBC 5TH EDITION (2014). |
| |
| 1- AFTER PLANS ARE REVISED, BRING THEM TO PALM BEACH |
| COUNTY (2300 N. JOG RD.) FOR IMPACT FEES ASSESSMENT. |
| BRING BACK COUNTY STAMPED PLANS AND COPY OF PAID |
| RECEIPT IF FEES ARE DUE. COUNTY IMPACT FEE ORDINANCE OF |
| THE UNIFIED LAND DEVELOPMENT CODE. NOTE: THIS MAY BE |
| DONE LATER WHEN THE PERMIT IS READY FOR ISSUANCE. |
| |
| 2- REVISE ENERGY CALCULATIONS SUBMITTED; |
| A) NEED TO PROVIDE CURRENT FORM. FORM 405-10 SUBMITTED |
| IS FOR THE 2010 CODE. THE CURRENT CODE IS THE 2014. |
| SEC. 553 FLORIDA STATUTE. |
| |
| B) PROVIDE COMPLETE AND CORRECT INFORMATION ON TOP OF |
| FORM, INCLUDING CORRECT OWNER NAME, NAME OF BUILDER AND |
| JURISDICTION NUMBER. SEC. R101.5.1.1.2 FBC-ENERGY |
| CONSERVATION, 5TH EDITION (2014). |
| |
| C) CONDITIONED FLOOR AREA SHOWN ON ITEM #6 DOESN'T |
| MATCH PLANS. SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION, |
| 5TH EDITION (2014). |
| |
| D) FLOOR TYPE AND INSULATION SHOWN ON ITEM #8 DOESN'T |
| MATCH PLANS. SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION, |
| 5TH EDITION (2014). |
| |
| E) WALL TYPE AND INSULATION SHOWN ON ITEM #9 DOESN'T |
| MATCH PLANS. SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION, |
| 5TH EDITION (2014). |
| |
| F) CEILING INFORMATION ON ITEM #10 NEED TO BE |
| COORDINATED WITH PLANS. NEED TO BE CLEAR IF VENTED OR |
| UNVENTED ATTIC AND INSULATION R VALUE. SEC. |
| R101.5.1.1.2 FBC-ENERGY CONSERVATION, 5TH EDITION |
| (2014). |
| |
| G) SPECIFY THE HOT WATER EFFICIENCY ON ITEM #14 AS |
| REQUIRED BY SEC. R403.4.4 FBC-ENERGY CONSERVATION, 5TH |
| EDITION (2014). |
| |
| H) PROVIDE THE NAME OF THE INDIVIDUAL COMPLETING THE |
| COMPLIANCE REPORT AS REQUIRED BY SEC. R405.4.2 |
| FBC-ENERGY CONSERVATION, 5TH EDITION (2014). |
| |
| I) OWNER/AGENT TO CERTIFY AND DATE BOTOM OF FORM AS |
| REQUIRED BY SEC. R103.1.1.2 FBC-ENERGY CONSERVATION, |
| 5TH EDITION (2014). |
| |
| J) REVISE ATTIC VENT RATION SHOWN ON PAGE 2 OF 5. SEC. |
| R806.2 FBC-RESIDENTIAL REQUIRES 1/150 RATIO NOT 1/300 |
| RATIO. REVISE AS REQUIRED OR PROVIDE COMPLETE DETAILS |
| AND SPECIFICATIONS SHOWING HOW COMPLYING WITH THE 1/300 |
| RATIO. SEE SEC. R806.2 FOR REQUIREMENTS. |
| |
| K) DOORS INFORMATION ON PAGE 3 OF 5 DOESN'T MATCH PLANS |
| AND PRODUCT APPROVALS SUBMITTED. SEC. R101.5.1.1.2 |
| FBC-ENERGY CONSERVATION, 5TH EDITION (2014). |
| |
| L) WINDOWS INFORMATION SHOWN ON PAGE 3 OF 5 DOESN'T |
| MATCH PLANS. REVISE THE BUILDING ORIENTATION AND GLASS |
| AREA TO MATCH PLANS AND PRODUCT APPROVALS SUBMITTED. |
| SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION, 5TH EDITION |
| (2014). |
| |
| M) COMPLETE THE INSPECTION CHECKLIST AS REQUIRED BY |
| SEC. R405.4.2 FBC-ENERGY CONSERVATION, 5TH EDITION |
| (2014). |
| |
| N) COMPLETE THE EPL DISPLAY CARD AS REQUIRED BY SEC. |
| R405.4.3 FBC-ENERGY CONSERVATION, 5TH EDITION (2014). |
| |
| 3- ENGINEER OF RECORD TO CLEARLY SPECIFIED ON DRAWINGS |
| IF DESIGNING AN UNVENTED OR VENTED ATTIC. SEE SEC. R806 |
| FBC-RESIDENTIAL. PROVIDE COMPLETE DETAILS AND |
| SPECIFICATIONS FOR EITHER OPTION. AND, COORDINATE WITH |
| THE ENERGY CALCULATIONS. SEE ITEM # 2(F) ABOVE. |
| |
| 4- SHEET A1: |
| A) REVISE THE DESIGN CERTIFICATION FOR BUILDING CODE |
| COMPLIANCE: |
| (1) THE CORRECT CODE IS THE 2014 EDITION NOT 2010. SEC. |
| 553 FL. ST. |
| (2) SPECIFY ALL ROOF AND FLOOR DEAD LOADS AND LIVE |
| LOADS, INCLUDING THE ATTIC LIVE LOAD AS REQUIRED BY |
| TABLE R301.5 FBC-RESIDENTIAL. NOTE: CLARIFY WHAT IS THE |
| ROOF DEAD LOAD OF 5PSF FOR? SEC. R301.1 |
| FBC-RESIDENTIAL. ALSO, COORDINATE DESIGN CRITERIA WITH |
| INFORMATION SHOWN ON SHEET S3. |
| (3) SPECIFY THE BUILDING EXPOSURE AS REQUIRED BY SEC. |
| R301.2.1.4 FBC-RESIDENTIAL. |
| |
| 5- SHEET A4: |
| A) INFORMATION ABOUT THE TYPE "B" WINDOWS IS NOT CLEAR. |
| NOT CLEAR IF REPLACING OR RESTORING THESE WINDOWS. SEE |
| PROPOSED DOOR AND WINDOW SCHEDULE ON SHEET A4 AND NOTE |
| AT THE BOTTOM OF SHEET A3. ALSO, SIZE SHOWN ON SHEET A2 |
| DOESN'T MATCH SIZE SHOWN ON SHEET A4. REVISE ALL THE |
| INFORMATION AS REQUIRED TO MATCH. SEC. 107.2.1 CITY |
| AMENDMENTS. |
| |
| B) REVISE FLOOR LANDING AT THE REAR ADDITION TO SHOW |
| COMPLIANCE WITH SEC. R311.3 FBC-RESIDENTIAL. NEED MIN. |
| 36" LANDING. |
| |
| C) NEED TO PROVIDE HANDRAILS FOR THE REAR STEPS AS |
| REQUIRED BY SEC. R311.7.8 FBC-RESIDENTIAL. PROVIDE |
| COMPLETE DETAILS AND SPECIFICATIONS. SEE TABLE R301.5 |
| FOR REQUIRED LIVE LOADS. |
| |
| D) PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE |
| CONSTRUCTION OF THE REAR STEPS SHOWING COMPLIANCE WITH |
| SEC. TABLE R301.5 AND SEC. R311.7.5 FBC-RESIDENTIAL. |
| |
| E) PROVIDE COMPLETE DETAILS AND SPECIFICATIONS SHOWING |
| COMPLIANCE WITH THE ADDITION VENTILATION FOR UNDER |
| FLOOR SPACE AS REQUIRED BY SEC. R408 FBC-RESIDENTIAL. |
| SPECIFY LOCATION AND SIZE OF OPENINGS. ALSO, SPECIFY |
| ACCESS SIZE AND LOCATION. |
| |
| F) CLARIFY WHY THE DESIGN PRESSURES FOR WINDOWS "F" AND |
| "G" ARE SO LOW COMPARE TO THE OTHERS. SEC. R301.1 |
| FBC-RESIDENTIAL. |
| |
| G) PROVIDE COMPLETE FRAMING DETAILS AND SPECIFICATIONS |
| FOR THE NEW WINDOWS IN THE ENCLOSED PORCH THAT ARE |
| REPLACING EXISTING SCREEN LOUVERS. SPECIFY ALL FRAMING |
| MEMBERS AND CONNECTORS. IF INSTALLING ALUMINUM WINDOWS, |
| THEN SPECIFY SIZES. SEC. R301.1 FBC-RESIDENTIAL. |
| |
| 6- SHEET A-5: REVISE STEPS LANDING AND RISERS AND |
| TREADS DIMENSIONS. COORDINATE WITH ITEM # 5(B), #5(C) |
| AND #5(D) ABOVE. NOTE: REVISE BOTH ELEVATIONS. |
| |
| 7) SHEET A6: |
| A) PROVIDE COMPLETE ROOF FRAMING PLAN. SPECIFY ALL |
| FRAMING MEMBERS AND CONNECTORS. SEC. R301.1 |
| FBC-RESIDENTIAL. |
| |
| B) PROVIDE DOORS AND WINDOWS COMPLETE FRAMING DETAILS. |
| SPECIFY ALL FRAMING MEMBERS AND CONNECTORS. SEC. R301.1 |
| FBC-RESIDENTIAL. |
| |
| C) SPECIFY ROOF SHEATHING TYPE OF NAIL AND SPACING. |
| NOTE: SEE SEC. R803.2.3.1 FBC-RESIDENTIAL FOR MIN. TYPE |
| AND OF NAIL AND SPACING TO BE USED. |
| |
| D) SPECIFY WALL SHEATHING FASTENING. SEC. R301.1 |
| FBC-RESIDENTIAL. |
| |
| E)FOOTING NEEDS TO BE AT LEAST 12" BELOW GRADE AS |
| REQUIRED BY SEC. R403.1.4 FBC-RESIDENTIAL. REVISE AS |
| REQUIRED. |
| |
| F) THE FOUNDATION NEEDS TO BE AT LEAST 6" ABOVE THE |
| FINISHED GRADE AS REQUIRED BY SEC. R404.1.6 |
| FBC-RESIDENTIAL. REVISE AS REQUIRED. |
| |
| G) PROVIDE COMPLETE DETAIL/SECTION SHOWING HOW THE |
| SIMPSON ST-22 IS INSTALLED AROUND THE BOTTOM PLATE AS |
| SPECIFIED ON THE SHED STRUCTURAL DETAILS SECTION. NOTE: |
| THIS IS A TENSION STRAP AND IS NOT DESIGNED TO BE |
| BENDED. SEC. R301.1 FBC-RESIDENTIAL. |
| |
| H) PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE |
| 1 HOUR FIRE RATING ASSEMBLY REQUIRED ON THE UNDERSIDE |
| OF THE ROOF PROJECTION ON THE NORTH AND EAST SIDE AS |
| REQUIRED BY TABLE R302.1(1) FBC-RESIDENTIAL. THE |
| PROJECTION IS LESS THAN 5'-0" FROM THE PROPERTY LINE. |
| |
| 8- SHEET S1: |
| A) DETAIL 3/S1: SPECIFY HOW IS THE NEW 2 X 6 STUB STUDS |
| CONNECTED TO THE FLOOR FRAMING AND BOTTOM PLATE. SEC. |
| R301.1 FBC-RESIDENTIAL. |
| |
| B) THE YEAR SPECIFIED FOR THE ACI STANDARDS IS TOO OLD. |
| UPDATE THE YEAR OF THE ACI STANDARDS SPECIFIED ON THE |
| CONCRETE NOTES. SEE CHAPTER 46 OF FBC-RESIDENTIAL FOR |
| ADOPTED YEAR AND UPDATE ALL STANDARDS AS REQUIRED. |
| |
| C) REVISE THE SHED FOUNDATION PLAN. SEE ITEM #7 ABOVE. |
| |
| 9- SHEET S2: |
| A) DETAIL 1/S2: PROVIDE COMPLETE DETAIL/SECTION SHOWING |
| HOW THE SIMPSON ST-22 IS INSTALLED AROUND THE BOTTOM |
| PLATE AS SPECIFIED. NOTE: THIS IS A TENSION STRAP AND |
| IS NOT DESIGNED TO BE BENDED. SEC. R301.1 |
| FBC-RESIDENTIAL. |
| |
| B) SEC. R803.2.3.1 FBC-RESIDENTIAL REQUIRES ROOF |
| SHEATHING TO BE NAILED WITH 8D RING SHANK NAILS MIN. |
| REVISE "NAILING AND FASTENERS AND ANCHORS" NOTES AS |
| REQUIRED. |
| |
| C) NUMBER OF FRAMING MEMBERS SPECIFIED ON THE WOOD |
| JAMBS NOTE ON THE "NAILING AND FASTENERS AND ANCHORS" |
| DOESN'T MATCH NUMBER OF FRAMING MEMBERS SHOWN ON THE |
| WOOD FRAMING DETAILS ON SHEET S3. REVISE AS REQUIRED. |
| SEC. R301.1 FBC-RESIDENTIAL. |
| |
| D) REVISE THE BUILDING CODE EDITION AND EXPOSURE |
| CATEGORY SHOWN ON THE WIND LOAD DESIGN & ANALYSIS NOTE |
| ON THE "NAILING AND FASTENERS AND ANCHORS". THE CURRENT |
| CODE IS 2014 AND THE BUILDING EXPOSURE IS "C". SEE SEC. |
| R301.2.1.4 FBC-RESIDENTIAL. |
| |
| 10- SHEET S3: SEC. R803.2.3.1 FBC-RESIDENTIAL REQUIRES |
| ROOF SHEATHING TO BE NAILED WITH 8D RING SHANK NAILS |
| MIN. REVISE ROOF SHEATHING NOTES AS REQUIRED. |
| |
| 11- SPECIFY CARBON MONOXIDE ALARMS WITHIN EACH BEDROOM |
| AS REQUIRED BY SEC. R315 FBC-RESIDENTIAL. |
| |
| 12- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| FAC 61G20-3.002(33) FOR: |
| A) HARDIE PLANK SIDING SPECIFIED ON PLANS. |
| |
| B) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON PLANS |
| AND DETAILS. PROVIDE ONLY THE FLORIDA PRODUCT APPROVAL |
| COVER PAGE AND PAGE SHOWING THE SPECIFIED CONNECTOR OR |
| LIST THE CURRENT FLORIDA PRODUCT APPROVAL NUMBER NEXT |
| TO EACH SPECIFIED CONNECTOR. |
| |
| C) WINDOW MULLIONS, IF SPECIFIED ON PLANS FOR NEW |
| ENCLOSED PORCH WINDOWS. |
| |
| D) SINGLE HUNG WINDOWS. NOA 12-0118.18 SUBMITTED |
| EXPIRED ON DECEMBER 01 OF 2015. NEED CURRENT NOA. |
| |
| E) ROOF SHINGLES SPECIFIED ON PLANS. |
| |
| 13- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS |
| REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS. |
| |
| 14- VALUATION DECLARED IN THE PERMIT APPLICATION IS TTO |
| LOW. VALUATION TO INCLUDE ALL LABOR, MATERIALS, |
| CONTRACTOR'S OVERHEAD AND PROFIT AND ALL DESIGN |
| PROFESSIONAL FEES AS REQUIRED BY SEC. 109.3 CITY |
| AMENDMENTS. REVISE VALUATION TO INCLUDE ALL THE SCOPE |
| OF WORK SHOWN ON PLANS AND SPECIFICATIONS AND THE |
| DESIGN PROFESSIONAL FEES. |
| |