2016-07-20 08:06:12 | BUILDING PLAN REVIEW |
| W.P.B. REVISION: 16070728 |
| W. P. B. PERMIT: 15090101 |
| ADD: 1301 SUMMIT BLVD. PANTHER HOLDING/ OTTER HOLDING |
| CONT: GAST CONSTRUCTION |
| TEL: 561-281-1001 |
| E-MAIL: [email protected] |
| |
| 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION |
| |
| 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| FLORIDA BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE: WED. JULY 20/ 2016 |
| ACTION: DENIED |
| |
| 1) THE STRUCTURAL SHEET S3.0 AND ARCHITECTURAL SHEET |
| A-300 WILL NEED TO BE CORRELATED ONCE THE OPTIONS ON |
| SHEET A-300 ARE KNOWN. UNKNOWNS ARE: 1A) TRUSSES FOR |
| THE PANTHER HOLDING ENCLOSURE BEING BUILT WILL BE |
| CONSTRUCTED USING EITHER FIRE RETARDANT TREATED WOOD OR |
| METAL TRUSSES. |
| 1B) THE ROOFING NOTE FOUND ON SHEET A-300 NOTE # 1 |
| INDICATES THE INSTALLATION OF V CRIMP ANODIZED ALUMINUM |
| METAL ROOFING OVER PEEL AND STICK UNDERLAYMENT MEMBRANE |
| ON 2 INCH RIGID ROOF INSULATION BOARD MECHANICALLY |
| FASTENED TO THE ROUGH SAWN BOARD INSTALLED PER THE |
| MANUFACTURERS INSTRUCTIONS. SEE STRUCTURAL DRAWINGS. |
| THE STRUCTURAL DRAWINGS INDICATE THE USE OF 5/8 INCH |
| PLYWOOD DECKING. |
| |
| 2) PLEASE CORELATE ALL OF THE MATERIALS TO BE INSTALLED |
| AND SHOW ON THE ARCHITECTURAL & STRUCTURAL SHEETS. |
| PLEASE BEGIN WITH THE TYPE OF TRUSS FIRE RETARDANT |
| TREATED WOOD OR METAL, THE TYPE OF DECKING, THE 2 INCH |
| INSULATION AND ALL ROOFING MEMBRANE MATERIALS. SUBMITED |
| IS A PEAL AND STICK UNDERLAYMENT TU-MAX AND THE ROOFING |
| REPORT SUBMITTED POLYGLASS MODIFIED BITUMEN ROOF SYSTEM |
| W-106 PAGE 18 IS FOR NEW CONSTRUCTION SYSTEM E: |
| NON-INSULATED WOOD DECK, EITHER THE PLANS NEED REVISED |
| OR THE PRODUCT APPROVAL, PLEASE ALSO BE ADVISED THE FL. |
| APPROVAL FL 14645 THE DECK NAILING WILL NEED TO BE |
| REVIEWED SINCE THERE IS SHOWN TO BE 2 INCHES OF |
| INSULATION !!!!!!!!! |
| |
| A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A |
| RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| THIS REVIEW. |
| |