2017-01-24 12:09:14 | PROVISO: |
| NO REVIEW CONDUCTED UNDER THIS SUBMITTAL. IF ANY |
| CHANGES INTRODUCED SINCE PREVIOUS APPROVAL AND |
| ADDITIONAL REVIEW WILL BE NECESSARY. |
| 1. ELECTRIC CAR STATIONS SHALL BE FOR TRAIN STATION |
| GARAGE. IF FOR RESIDENTIAL GARAGE REVISED NUMBERS SHALL |
| BE PROVIDED TO CONFIRM THE PROJECT COMPLIES WITH |
| MINIMUM PARKING REQUIREMENTS. |
| ALL PROVISOS INCLUDED IN PREVIOUS APPROVAL STILL |
| REMAIN. |
| 1. PLEASE PROVIDE INFORMATION REGARDING THE SAFE |
| CIRCULATION TO ACCESS VAN ACCESSIBLE PARKING SPACE ON |
| FIRST FLOOR OF GARAGE. |
| 2. PLEASE IDENTIFY IN A SEPARATE LETTER ALL THE IT/TEL |
| , BIKE STORAGE ROOMS AND OTHER ELECTRIC ROOM WITHIN THE |
| UPPER LEVELS AND ACKOWLEDGE THEY ARE NOT TO BE USES FOR |
| HUMAN OCCUPATION DIFFERENT THAN LISTED. |
| 3. PLEASE INCLUDE A NOTE IN THE ARCHITECTURAL DRAWINGS |
| STATING THE BIKE STORAGE ROOM IS A NON-CONDITIONED |
| SPACE. |
| 4. PLEASE INDICATE THE DIMENSIONS OF EACH PARKING SPACE |
| TO CONFIRM COMPLIANCE WITH MIN DIMENSIONS WHEN ADJACENT |
| TO COLUMNS OR WALLS. |
| 5. PLEASE INDICATE THE LOCATION OF GUEST PARKING AND |
| RETAIL PARKING WHITHIN THE RESIDENTIAL PARKING AND |
| CREATE A TABLE LISTING THE NUMBER OF SPACES DEDICATED |
| FOR EACH PLUS THE AAF STATION PARKING. |
| 6. PLEASE INCLUDE A NOTE IN THE CIVIL DRAWINGS STATING |
| THAT THE SIDEWALK ELEVATION SHALL BE MAINTAINED AS IT |
| CROSSES THE GARAGE DRIVEWAY . |
| 7. PLEASE PROVIDE INFORMATION TO CONFIRM COMPLIANCE |
| WITH ALL THE TRAFFIC MITIGATION MEASURES IMPOSED BY THE |
| DAC APPROVAL. |
| 8. PLEASE SUBMIT A SEPARATE LANDSCAPE PERMIT. |
| FOR ADDITIONAL INFORMATION PLEASE CONTACT ANA MARIA |
| APONTE AT 561-822-1439. |