Plan Review Notes
Plan Review Notes For Permit 16070715
Permit Number 16070715
Review Stop M
Sequence Number 3
Notes
Date Text
2017-01-13 15:50:45MECHANICAL PROVISOS:
 PERMIT #16070715
 1/13/17
  
 1) REVISE SHEETS M204, M206, M208, M502, M503, M504,
 M505, M506, M507, & M601 TO SHOW ALL OUTSIDE AIR DUCT
 RUNS AND REQUIRED AUTOMATIC SHUTOFF DAMPERS.
  
 2) PROVIDE REFRIGERANT PIPING RISER DIAGRAMS FOR THE
 SPLIT AC SYSTEMS
  
 3) FINAL COMMISSIONING REPORT:
 A REPORT OF TEST PROCEDURES AND RESULTS IDENTIFIED AS
 "FINAL COMMISSIONING REPORT" SHALL BE DELIVERED TO THE
 BUILDING OWNER AND SHALL INCLUDE:
 1. RESULTS OF FUNCTIONAL PERFORMANCE TESTS.
 2. DISPOSITION OF DEFICIENCIES FOUND DURING TESTING,
 INCLUDING DETAILS OF CORRECTIVE MEASURES USED OR
 PROPOSED.
 3. FUNCTIONAL PERFORMANCE TEST PROCEDURES USED DURING
 THE COMMISSIONING PROCESS INCLUDING MEASURABLE CRITERIA
 FOR TEST ACCEPTANCE, PROVIDED HEREIN FOR REPEATABILITY.
 EXCEPTION: DEFERRED TESTS WHICH CANNOT BE PERFORMED AT
 THE TIME OF REPORT PREPARATION DUE TO CLIMATIC
 CONDITIONS.
  
 4) PROVIDE A SIGNED AND SEALED COPY OF THE SMOKE
 CONTROL SYSTEM RATIONAL ANALYSIS BY JAMES S. LUKE P.E.
 COMMISSIONING OF THE SMOKE CONTROL SYSGTEMS REQUIRED AT
 FINAL INSPECTION.
  
 5) SEPARATE PERMITS ARE REQUIRED FOR FIRE SPRINKLER,
 FIRE SUPPRESSION, KITCHEN HOOD EXHAUST SYSTEMS, AND
 WALK-IN COOLERS AND FREEZERS.
  
 6) REQUIRED SUBMITTALS:
 A) STAIRWAY PRESSURIZATION FANS.
 B) CORRIDOR EXHAUST FAN.
 C) SMOKE EXHAUST DUCTWORK.
 D) FIRE/SMOKE AND FIRE DAMPERS.
 E) WINDLOAD ENGINEERING FOR INSTALLATION OF ALL ROOFTOP
 MECHANICAL EQUIPMENT, CURBS, STANDS,
 DUCTS, AND SUPPORTS
 F) MOTORIZED DAMPERS.
 G) OUTSIDE AIR AND EXHAUST LOUVERS AND TERMINATION
 CAPS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  
  
  