2017-01-13 15:50:45 | MECHANICAL PROVISOS: |
| PERMIT #16070715 |
| 1/13/17 |
| |
| 1) REVISE SHEETS M204, M206, M208, M502, M503, M504, |
| M505, M506, M507, & M601 TO SHOW ALL OUTSIDE AIR DUCT |
| RUNS AND REQUIRED AUTOMATIC SHUTOFF DAMPERS. |
| |
| 2) PROVIDE REFRIGERANT PIPING RISER DIAGRAMS FOR THE |
| SPLIT AC SYSTEMS |
| |
| 3) FINAL COMMISSIONING REPORT: |
| A REPORT OF TEST PROCEDURES AND RESULTS IDENTIFIED AS |
| "FINAL COMMISSIONING REPORT" SHALL BE DELIVERED TO THE |
| BUILDING OWNER AND SHALL INCLUDE: |
| 1. RESULTS OF FUNCTIONAL PERFORMANCE TESTS. |
| 2. DISPOSITION OF DEFICIENCIES FOUND DURING TESTING, |
| INCLUDING DETAILS OF CORRECTIVE MEASURES USED OR |
| PROPOSED. |
| 3. FUNCTIONAL PERFORMANCE TEST PROCEDURES USED DURING |
| THE COMMISSIONING PROCESS INCLUDING MEASURABLE CRITERIA |
| FOR TEST ACCEPTANCE, PROVIDED HEREIN FOR REPEATABILITY. |
| EXCEPTION: DEFERRED TESTS WHICH CANNOT BE PERFORMED AT |
| THE TIME OF REPORT PREPARATION DUE TO CLIMATIC |
| CONDITIONS. |
| |
| 4) PROVIDE A SIGNED AND SEALED COPY OF THE SMOKE |
| CONTROL SYSTEM RATIONAL ANALYSIS BY JAMES S. LUKE P.E. |
| COMMISSIONING OF THE SMOKE CONTROL SYSGTEMS REQUIRED AT |
| FINAL INSPECTION. |
| |
| 5) SEPARATE PERMITS ARE REQUIRED FOR FIRE SPRINKLER, |
| FIRE SUPPRESSION, KITCHEN HOOD EXHAUST SYSTEMS, AND |
| WALK-IN COOLERS AND FREEZERS. |
| |
| 6) REQUIRED SUBMITTALS: |
| A) STAIRWAY PRESSURIZATION FANS. |
| B) CORRIDOR EXHAUST FAN. |
| C) SMOKE EXHAUST DUCTWORK. |
| D) FIRE/SMOKE AND FIRE DAMPERS. |
| E) WINDLOAD ENGINEERING FOR INSTALLATION OF ALL ROOFTOP |
| MECHANICAL EQUIPMENT, CURBS, STANDS, |
| DUCTS, AND SUPPORTS |
| F) MOTORIZED DAMPERS. |
| G) OUTSIDE AIR AND EXHAUST LOUVERS AND TERMINATION |
| CAPS. |
| |
| CHRISTOPHER L. COLE |
| MECHANICAL PLANS EXAMINER |