Plan Review Notes
Plan Review Notes For Permit 16070715
Permit Number 16070715
Review Stop B
Sequence Number 3
Notes
Date Text
2017-06-26 12:42:3416070715 - BUILDING DATA FOR C.O. AND REPORTING
 USC-404 TYPE 105 - NEW:RES FIVE OR MORE UNITS
 SQUARE FEET - 641051
  
 CONSTRUCTION TYPE: 14-1-A
 UNITS: 290
 FLOORS: 25
 BEDROOMS: 391
 ROOMS: 3101
 SQ FT LIVABLE: 641051
 SQ FT FOOTPRINT: 38078
 SQ FT ROOF: 38078
  
 SETBACKS FRONT (USE THIS TO ENTER VERTICAL DATUM IF
 KNOWN):
 SETBACKS BACK (USE THIS TO ENTER FIRST FLOOR IF KNOWN):
 XX.XX
 SETBACKS LEFT (USE THIS TO ENTER SECOND FLOOR IF KNOWN:
 XX.XX
 OCC LOAD: 4837
 PROP USE: GAR/R2/M/A
 SPRINKLER SYS? Y
 SPRK REQ'D? Y
 BATHRMS: 391
  
 BLDG CODE: FL 2014
 OCC CLASS: 5TH ED R-2
2017-01-17 14:43:45****PROVISOS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 A. PROVISO: TCO AT EACH PHASE IS SUBJECT TO APPROVAL OF
 THE BUILDING OFFICIAL (OR HIS REPRESENTATIVE) AND FIRE
 DEPARTMENT, AND MAY INCLUDE ITEMS NOT WITHIN THE SCOPE
 OF THIS REVIEW. A TCO REQUEST FORM AND FEE WILL BE
 REQUIRED. THIS FORM IS AVAILABLE UPON REQUEST BY EMAIL.
  
 C. SEPARATE PERMITS (APPLICATION, PLANS, REVIEWS, AND
 FEES) REQUIRED FOR ALL ITEMS OTHER THAN MECHANICAL,
 ELECTRICAL, AND PLUMBING FOR THE BUILDING AS SHOWN ON
 THE PLANS. THIS INCLUDES SIGNS, FIRE ALARM, FIRE
 SPRINKLERS, LANDSCAPING.
  
 SUB PERMITS (APPLICATION, SUB PERMIT FEE) ARE REQUIRED
 FOR MECHANICAL, ELECTRICAL, AND PLUMBING PRIOR TO
 COMMENCEMENT OF WORK.
  
 A ROOFING SUB PERMIT IS REQUIRED PRIOR TO COMMENCEMENT
 OF ROOFING WORK. AS ROOF DOCUMENTS HAVE NOT BEEN
 PROVIDED, THIS IS A DEFERRED SUBMITTAL. PRODUCT
 APPROVALS REVIEWED BY DESIGNER OF RECORD, SELECTED
 ASSEMBLY, ENGINEERING IF APPLICABLE ARE TO BE SUBMITTED
 AS A REVISION WITH A ROOF PERMIT APPLICATION.
  
 D. COMPONENTS AND CLADDING PRODUCT APPROVALS ARE TO BE
 REVIEWED BY DESIGNER OF RECORD AND SUBMITTED PRIOR TO
 INSTALLATION.
  
 E. PROVISO, THIS STUCTURE SERVES A BUILDING WHICH HAS
 NOT BEEN REVIEWED BY THIS DEPARTMENT (TRAIN STATION).
 ACCESSIBLE ROUTE IN COMPLIANCE WITH FBC 5TH EDITION
 ACCESSIBILITY IS REQUIRED AND WILL BE VERIFIED IN THE
 FIELD.
  
 F. PROVISO, THE PROJECT MANUAL HAS NOT BEEN REVIEWED.
 DOOR HARDWARE TO COMPLY WITH FBC BUILDING, FBC
 ACCESSIBILITY.
 G. PROVISO, ALL DOORS AND GATES IN THE MEANS OF EGRESS
 FOR ASSEMBLY OCCUPANCY ARE TO INCLUDE PANIC DEVICES OR
 FIRE EXIT HARDWARE, FBC 1008.
 H. PROVISO, PRODUCT APPROVALS FOR COMPONENTS AND
 CLADDING HAVE NOT BEEN SUBMITTED. THEY MAY BE
 SUBMITTED, PRIOR TO INSTALLATION, AS A REVISION, PRIOR
 TO INSTALLATION.
  
 I. PROVISO, FLOORING UNDERLAYMENT IS TO COMPLY WITH FBC
 1207.2, 1207.3, AND 603.1. THIS MAY BE A DEFERRED
 SUBMITTAL. IF DEFERRED, THE TEST REPORTS ARE TO BE
 SUBMITTED AS A REVISION PRIOR TO INSTALLATION. AS
 STRUCTURAL PLANS SHOW AN 8 INCH SLAB, PRODUCTS TESTED
 WITH EITHER A 6 INCH OR AN 8 INCH SLAB ARE ACCEPTABLE.
  
 1. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR
 BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90.
 THE TEST REPORT CANNOT INCLUDE A DROPPED GYPSUM
 CEILING. PROVIDE A COPY OF THE TEST REPORT.
  
 2. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN
 DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC
 OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN
 IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN
 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH
 ASTM E 492. THE TEST REPORT CANNOT INCLUDE A DROPPED
 GYPSUM CEILING. PROVIDE A COPY OF THE TEST REPORT.
  
 3. FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE
 BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE
 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84
 OR UL 723.
  
 J. FBC ACCESSIBILITY 207, MEANS OF EGRESS SHALL COMPLY
 WITH IBC 2000 WITH 2001 SUPPLEMENT 1003.2.13 OR IBC
 2003 1007.
  
 PER ARCHITECT, BOTH BANKS OF ELEVATORS (EAST SIDE AND
 WEST SIDE) WILL HAVE A MINIMUM OF ONE ELEVATOR OPERABLE
 ON STANDBY POWER.
  
 K. STANDBY POWER, FBC 403.4.8, EMERGENCY POWER 403.4.9
 REQUIRED.
  
 L. FBC ACCESSIBILITY 208.3.1(2) ADVISORY, EV SPACE WITH
 AN ACCESS AISLE, LOCATED ON AN ACCESSIBLE ROUTE, IS
 REQUIRED. A REVISION IS TO BE SUBMITTED, REVIEWED AND
 ISSUED PRIOR TO C.O.
  