2016-11-27 08:14:021) SHT. P717 SHOWS( 2 )-2 1/2 INCH LINES TO THE RETAIL
 SPACE. SHOW HOW THESE LINES CONNECT TO THE GAS MAIN.
 WPB AMEND. TO FBC SEC. 107.3.5.1.5. FUTURE LINES SHALL
 BE EQUIPPED WITH REGULATORS AND THE OUTLET FROM THE
 REGULATOR SHALL HAVE A NIPPLE, VALVE AND CAP INSTALLED.
 THE REGULATOR VENT OUTLET SHALL BE CAPPEDOR PLUGGED
 UNTIL PUT INTO USE.
 2) SHOW THE APPROXIMATE DISTANCE OF THE RUN OF THE PIPE
 TO THE RETAIL SPACE FROM THE METER.WPB AMEND. TO FBC
 SEC. 107.2.1.
 3) SHT.P718 REFERS TO A DETAIL FOR THE SHUTOFF VALVE
 FOR THE APPLIANCE AT THE AMENITIES AND ALSO FOR THE
 SHUTOFF VALVE FOR THE POOL EQUIPMENT. SPECIFIY THE
 SHEET WHERE THIS DETAIL CAN BE FOUND. I DID NOT FIND IT
 ON ANY OF THE DETAIL SHEETS.
 4) PLACE THE TOTAL BTU LOAD FOR EACH SYSTEM IN THE
 APPROPRIATE SYSTEM SIZING BOX ( SYSTEM #1, #2 #3 ). IT
 IS TIME CONSUMNING ADDDING IT UP ON THE RISERS AND THIS
 WILL AID IN THE RE-EVIEW TIME FOR THE GAS.WPB AMEND. TO
 FBC SEC. 107.2.1.
 5) REFER TO THE SHEET NUMBER FOR THE CONTINUATION OF
 THE GAS RISERS, NOT JUST THE LETTER.WPB AMEND. TO FBC
 SEC. 107.2.1.
 6) SHOW THE CONNECTION POINT OF THE RISER Q-Q TO THE
 MAIN GAS SYSTEM AND REFERENCE THE SHEET NUMBER.WPB
 AMEND. TO FBC SEC. 107.2.1.
 7) SHT.P719 - THE SIZING SYSTEM BOXES REFER TO THE 2009
 IFC. THE FUEL GAS CODE IN EFFECT IS THE 2014 FBC-FUEL
 GAS.
 8) SHT. P719 - SIZING SYSTEM #1 BOX - THE GAS TABLE
 REFERENCED, 402.3 (3) IS FOR LESS THAN 2 PSI IN THE FBC
 FUEL GAS BUT THE TEXT IN THE BOX STATES THE SYSTEM IS A
 2 PSI SYSTEM WITH A PRESSURE DROP OF 1.0 PSI. CLARIFY.
  