2016-11-27 08:14:02 | 1) SHT. P717 SHOWS( 2 )-2 1/2 INCH LINES TO THE RETAIL |
| SPACE. SHOW HOW THESE LINES CONNECT TO THE GAS MAIN. |
| WPB AMEND. TO FBC SEC. 107.3.5.1.5. FUTURE LINES SHALL |
| BE EQUIPPED WITH REGULATORS AND THE OUTLET FROM THE |
| REGULATOR SHALL HAVE A NIPPLE, VALVE AND CAP INSTALLED. |
| THE REGULATOR VENT OUTLET SHALL BE CAPPEDOR PLUGGED |
| UNTIL PUT INTO USE. |
| 2) SHOW THE APPROXIMATE DISTANCE OF THE RUN OF THE PIPE |
| TO THE RETAIL SPACE FROM THE METER.WPB AMEND. TO FBC |
| SEC. 107.2.1. |
| 3) SHT.P718 REFERS TO A DETAIL FOR THE SHUTOFF VALVE |
| FOR THE APPLIANCE AT THE AMENITIES AND ALSO FOR THE |
| SHUTOFF VALVE FOR THE POOL EQUIPMENT. SPECIFIY THE |
| SHEET WHERE THIS DETAIL CAN BE FOUND. I DID NOT FIND IT |
| ON ANY OF THE DETAIL SHEETS. |
| 4) PLACE THE TOTAL BTU LOAD FOR EACH SYSTEM IN THE |
| APPROPRIATE SYSTEM SIZING BOX ( SYSTEM #1, #2 #3 ). IT |
| IS TIME CONSUMNING ADDDING IT UP ON THE RISERS AND THIS |
| WILL AID IN THE RE-EVIEW TIME FOR THE GAS.WPB AMEND. TO |
| FBC SEC. 107.2.1. |
| 5) REFER TO THE SHEET NUMBER FOR THE CONTINUATION OF |
| THE GAS RISERS, NOT JUST THE LETTER.WPB AMEND. TO FBC |
| SEC. 107.2.1. |
| 6) SHOW THE CONNECTION POINT OF THE RISER Q-Q TO THE |
| MAIN GAS SYSTEM AND REFERENCE THE SHEET NUMBER.WPB |
| AMEND. TO FBC SEC. 107.2.1. |
| 7) SHT.P719 - THE SIZING SYSTEM BOXES REFER TO THE 2009 |
| IFC. THE FUEL GAS CODE IN EFFECT IS THE 2014 FBC-FUEL |
| GAS. |
| 8) SHT. P719 - SIZING SYSTEM #1 BOX - THE GAS TABLE |
| REFERENCED, 402.3 (3) IS FOR LESS THAN 2 PSI IN THE FBC |
| FUEL GAS BUT THE TEXT IN THE BOX STATES THE SYSTEM IS A |
| 2 PSI SYSTEM WITH A PRESSURE DROP OF 1.0 PSI. CLARIFY. |
| |
| TIM LARGE |
| CHIEF PLUMBING INSPECTOR |
| PLUMBING PLAN REVIEW |