2016-09-08 14:57:10 | 1ST REVIEW |
| |
| |
| |
| GEORGE JOHNSON |
| PLUMBING PLANS EXAMINER LL |
| CITY OF WEST PALM BEACH |
| DEVELOPMENT SERVICES |
| BUILDING DIVISION |
| 561-805-6711 |
| [email protected] |
| |
| |
| GAS COMMENTS: |
| |
| 1. SHOW ALL CUT SECTIONS OF PIPE AND CORRESPONDING |
| LENGTHS PER FBC-2014 FUEL GAS, SECS. 402.4.1, 402.4.2. |
| |
| 2. SUBMIT MANUFACTURER?S SPECIFICATION SHEETS FOR ALL |
| GAS EQUIPMENT TO VERIFY COMPLIANCE WITH STANDARDS NFPA |
| 54, NFPA 58, AND FBC-2014 FUEL GAS SEC. 402.2 |
| |
| 3. THE SYSTEM IS TO BE DESIGNED AND SIZED PER IFGC 2014 |
| OR FBC FG 2014 5TH EDITION. CHECK TABLE NUMBERS THEY |
| HAVE CHANGED. |
| |
| 4. PROVIDE SHUT OFF AND DRIP LEG AT EACH APPLIANCE. PER |
| FBC FG |
| 408.4 SEDIMENT TRAP. |
| WHERE A SEDIMENT TRAP IS NOT INCORPORATED AS PART OF |
| THE APPLIANCE, A SEDIMENT TRAP SHALL BE INSTALLED |
| DOWNSTREAM OF THE APPLIANCE SHUTOFF VALVE AS CLOSE TO |
| THE INLET OF THE APPLIANCE AS PRACTICAL. THE SEDIMENT |
| TRAP SHALL BE EITHER A TEE FITTING HAVING A CAPPED |
| NIPPLE OF ANY LENGTH INSTALLED VERTICALLY IN THE |
| BOTTOMMOST OPENING OF THE TEE AS ILLUSTRATED IN FIGURE |
| 408.4 OR OTHER DEVICE APPROVED AS AN EFFECTIVE SEDIMENT |
| TRAP. ILLUMINATING APPLIANCES, RANGES, CLOTHES DRYERS, |
| DECORATIVE VENTED APPLIANCES FOR INSTALLATION IN VENTED |
| FIREPLACES, GAS FIREPLACES, AND OUTDOOR GRILLS NEED NOT |
| BE SO EQUIPPED. |
| 409.5 APPLIANCE SHUTOFF VALVE. |
| EACH APPLIANCE SHALL BE PROVIDED WITH A SHUTOFF VALVE |
| IN ACCORDANCE WITH SECTION 409.5.1, 409.5.2 OR 409.5.3. |
| |
| 5. PROVIDE LENGTH AND SIZE OF PIPING TO POOL EQUIPMENT. |
| PER FBC-2014 FUEL GAS, SECS. 402.4.1, 402.4.2. |
| |