Plan Review Notes
Plan Review Notes For Permit 16070715
Permit Number 16070715
Review Stop ENG
Sequence Number 1
Notes
Date Text
2016-10-05 09:22:22PLEASE RESPOND TO COMMENTS IN WRITING.
  
 BACKFLOWS MUST BE AS CLOSE TO CITY OF WPB SOURCE AS
 POSSIBLE.
  
 IF BACKFLOWS ARE SHOWN IN THE CLOSEST LOCATION AS
 POSSIBLE, REPLY IN WRITING TO THIS COMMENT SO THAT A
 MEETING CAN BE ARRANGED WITH UTILITIES CUSTOMER SERVICE
 TO GET A VARIANCE IF THERE IS LEGITIMATE HARDSHIP. AN
 ENLARGE VIEW OF THE WATER METER AND BACLFLOWS LOCATIONS
 MAY BE ADEQUATE TO BETTER DESCRIBE THE CLEARANCES
 AROUND THESE CONSTRICTED AREAS. ENOUGH CLEARANCE SHALL
 BE (18") AROUND THE DEVICES TO ALLOW PROPER MAINTENANCE
 SPACE. BACKFLOWS JUST INSIDE BUILDING OR HARD SURFACE
 SHALL HAVE A FLOOR DRAIN TO AVOID FLOODING WHEN
 BACKFLOWS ARE NOT WORKING PROPERLY OR WHEN ROUTINE
 MAINTENANCE IS REQUIRED.
  
 SUBMIT SHOP DRAWINGS FOR DCDA AND RPPA FOR DOMESTIC,
 FIRE, IRRGIGATION. ETC./IMPORTANT MESSAGE: AS OF
 DECEMBER 20, 2015 THE CITY OF WEST PALM BEACH.
 CROSS-CONNECTION CONTROL MANUAL HAS BEEN REVISED MAKING
 KNOWN THAT "ALL BACKFLOW DEVICES MUST BE LEAD FREE."
 FOR MORE INFORMATION REFER TO THE LINK BELOW: HTTP://WP
 B.ORG/DEPARTMENTS/PUBLIC-UTILITIES/FORMS-PUBLICATIONS/B
 ACKFLOW-CROSS-CONNECTION-CONTROL-MANUAL
  
 MANUEL JULIAN GONZALEZ
 ENGINEERING PROJECT COORDINATOR
 PUBLIC WORKS DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 494-1085
 FAX: (561) 494-1116
 EMAIL: [email protected]
 HTTP://WWW.WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS
 /FORMS,-PERMITS-APPLICATIONS
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved