2016-10-11 18:51:08 | REVIEWED FOR COMPLIANCE WITH: 5TH EDITION FBC 2014 & |
| NFPA 70 2011 (NEC) |
| |
| BELOW ARE THE ELECTRICAL COMMENTS FOR THE FAILED PLAN |
| REVIEW: |
| |
| TYPICAL COMMENT: CITY OF WEST PALM BEACH AMENDMENTS TO |
| THE FBC-B SECTION 107.2.1.4 REQUIRES THAT BUILDING |
| PLANS BE DRAWN TO A MINIMUM 1/8? SCALE. THE SUBMITTED |
| DRAWINGS ARE DRAWN TO A 3/32? SCALE MAKING THEM A BIT |
| SMALLER THAN THE REQUIRED. PLEASE CORRECT ACCORDINGLY. |
| |
| SHEET E000 |
| 1. CLARIFY THE FRONT OF PANEL WHEN RECESSED IN THE |
| DISTRIBUTION EQUIPMENT BOX |
| 2. IS IT YOUR INTENT TO SHARE THESE SYMBOLS IN THE |
| LIGHTING LEGEND |
| 3. IS IT YOUR INTENT TO SHARE THIS SYMBOL IN THE POWER |
| CONNECTIONS BOX |
| 4. FIRE ALARM WORK SHALL BE UNDER SEPARATE PERMIT & |
| SUBMITTAL |
| SHEET E001 |
| 5. PLEASE TRY TO BE CONSISTENT WITH THE ABBREVIATIONS |
| THROUGHOUT THE SET. I SEE MULTIPLE SYMBOLS W/THE SAME |
| DESIGNATION. SYMBOLS NOT ALIGNED TO DESCRIPTION. |
| 6. IS IT YOUR INTENT TO SHARE THIS SYMBOL IN THE |
| DEMOLITION NOTES BOX |
| SHEET E201A |
| 7. NEC 422.31: EWH-4 REQUIRES A DISCONNECT |
| 8. NEC 210.8(B): RECEPTACLE OUTLETS IN GARAGES OR |
| INDOOR WET LOCATIONS SHALL BE GFI PROTECTED |
| 9. SEE NEC 430 FOR THE REQUIRED DISCONNECTS AND |
| ADDITIONAL CONTROLS AND SAFETY DEVICES REQUIRED, |
| TYPICAL TO ALL MOTOR LOADS |
| SHEET E202 |
| 10. HIGHLY UNLIKELY THAT THERE WILL ONLY BE 2 OUTLETS |
| IN THE MEZZANINE |
| SHEET E203 |
| 11. THE FOLLOWING MOTORS AND APPLIANCES REQUIRED |
| DISCONNECTS AS MENTIONED ABOVE AHU2-1, FCU2-2, EWH-8, |
| FCU2-1.1, FCU2-3, FCU2-1.2, EWH-4 |
| SHEET E204 |
| 12. SAME AS ABOVE FOR FCU3-1 |
| SHEET E208 |
| 13. SAME AS ABOVE FOR FCU7-1 |
| SHEET E210 |
| 14. SAME AS ABOVE FOR FCU9-3, SF9-3, AS WELL AS EVERY |
| MOTOR & HVAC EQUIPMENT ON ROOF |
| SHEET E211 |
| 15. SAME AS ABOVE FOR FCU10-1 |
| SHEET E212 |
| 16. SAME AS ABOVE FOR UNITS SF11-1, FCU12.5-1, FCU11-2 |
| & CU12.5-1 |
| SHEET E213 |
| 17. SAME AS ABOVE FOR AHU12-6, EF12-1 |
| SHEET E214 |
| 18. SAME AS ABOVE FOR ALL MOTORS AND ELECTRIC WATER |
| HEATER IN ROOM 12.508 |
| SHEET E301A |
| 19. RETAIL R02 ? LIGHTING ARRANGEMENT AS DESCRIBED DOES |
| NOT MEET THE DAYLIGHT ZONE CONTROL REQUIREMENTS OF THE |
| FBC-E405.2.2.3 |
| 20. FBC-B 1011.1 EXITS AND EXIT ACCESS SHALL BE MARKED |
| BY AN APPROVED EXIT SIGN READILY VISIBLE FROM ANY |
| DIRECTION OF EGRESS TRAVEL. THE PATH OF EGRESS SHALL BE |
| CLEARLY MARKED WHEN NOT READILY VISIBLE. THERE SHALL |
| NOT BE MORE 100? BETWEEN EXIT SIGN ALONG THE PATH OF |
| EGRESS. |
| 21. RETAIL R01 ? LIGHTING ARRANGEMENT AS DESCRIBED DOES |
| NOT MEET THE DAYLIGHT ZONE CONTROL REQUIREMENTS OF THE |
| FBC-E405.2.2.3 |
| 22. RETAIL R03 ? LIGHTING ARRANGEMENT AS DESCRIBED DOES |
| NOT MEET THE DAYLIGHT ZONE CONTROL REQUIREMENTS OF THE |
| FBC-E405.2.2.3 |
| 23. DUE TO THE LACK OF ROOM LABELS, ADDITIONAL LIGHTING |
| CONTROLS MAY BE REQUIRED |
| SHEET E303, E304, E305, E306, E307, E308, E309, E310, |
| E311, E312 |
| 24. THIS SHEET DOES NOT CLEARLY INDICATE THE LOCATION |
| OF EGRESS DOORS OR UP/DOWN RAMP, THEREFORE PROPER EXIT |
| LIGHT LOCATION IS NOT IDENTIFIABLE |
| SHEET E314 |
| 25. THIS AREA IS NOT IDENTIFIED ON THE PLANS, THEREFORE |
| EXIT LIGHTING AND LIGHTING CONTROL REQUIREMENTS CAN?T |
| BE PROPERLY DETERMINED |
| SHEET E318 |
| 26. EXIT LIGHT REQUIRED BY ROOF EXIT DOORWAY |
| SHEET E501 |
| 27. NEC 210.52(C)(4): (UNITS 6, 2, 04,) AN OUTLET IS |
| REQUIRED ON EITHER SIDE OF THIS SINK |
| 28. NEC 210.70: (UNIT 04) THE AREA LEADING TO THE |
| BEDROOM IS MISSING ILLUMINATION |
| SHEET E503 |
| 29. NEC 210.52(A)(2): WALL SPACE. ANY WALL SPACE 2 FT. |
| OR MORE IN WIDTH SHALL REQUIRE A RECEPTACLE. SEE LIVING |
| ROOM OF UNIT 20 |
| 30. NEC 210.52(C)(4): (UNITS 20 ) AN OUTLET IS REQUIRED |
| ON EITHER SIDE OF THIS SINK |
| 31. NEC 110.26(D): ILLUMINATION SHALL BE PROVIDED FOR |
| ALL WORKING SPACES ABOUT SERVICE EQUIPMENT, |
| SWITCHBOARDS, AND PANELBOARDS. THIS LIGHT SHALL NOT BE |
| CONTROLLED BY AUTOMATIC MEANS ONLY. CHECK THE SMC |
| CLOSET OF UNIT 20 |
| 32. NEC 210.52(C)(4): (UNITS 18) AN OUTLET IS REQUIRED |
| ON EITHER SIDE OF THIS SINK |
| 33. NEC 210.52 (A)(1): RECEPTACLES SHALL BE INSTALLED |
| SUCH THAT NO POINT MEASURED HORIZONTALLY ALONG THE |
| FLOOR LINE IN ANY WALL SPACE IS MORE THAN 6 FT. FROM A |
| RECEPTACLE OUTLET. THIS INCLUDES THE DISTANCE FROM THE |
| EDGE OF THE WALL. A FLOOR BOX IS REQUIRED ALONG THE |
| WALL WITH ALL THE WINDOWS IN THE LIVING ROOM OF UNIT 18 |
| 34. NEC 210.52(H): IN DWELLING UNITS, HALLWAYS OF 10 FT |
| OR MORE IN LENGTH SHALL HAVE AT LEAST ONE RECEPTACLE |
| OUTLET. SEE THE MASTER BEDROOM CORRIDOR OF UNIT 18 |
| 35. NEC 210.52(A)(2): WALL SPACE. ANY WALL SPACE 2 FT. |
| OR MORE IN WIDTH SHALL REQUIRE A RECEPTACLE. SEE WALL |
| BEHIND MASTER BEDROOM SINK OF UNIT 18 |
| 36. NEC 110.26(D): ILLUMINATION SHALL BE PROVIDED FOR |
| ALL WORKING SPACES ABOUT SERVICE EQUIPMENT, |
| SWITCHBOARDS, AND PANELBOARDS. THIS LIGHT SHALL NOT BE |
| CONTROLLED BY AUTOMATIC MEANS ONLY. SEE AREA IN FRONT |
| OF ELECTRICAL PANEL OF UNIT 18. |
| SHEET E504, UNIT L1 |
| 37. FBC-RE3901.4: IF THE AREA ADJACENT TO THE |
| REFRIGERATOR IS COUNTER SPACE, AN OUTLET IS REQUIRED. |
| 38. FBC-ER3901.4.1: KITCHEN RECEPTACLE REQUIRED |
| 39. ARE YOU SURE THAT YOU WANT THE SWITCH FOR THE |
| DISPOSAL THAT FAR AWAY FROM THE SINK |
| 40. FBC-RE3901.2.1: A RECEPTACLE IS REQUIRED NO MORE |
| THAN 6? FROM THE WALL EDGE OF THE KITCHEN TO THE LR. |
| 41. FBC-RE3901.2.1: THE LINEAR WALL SPACE BETWEEN THESE |
| TWO OUTLETS EXCEEDS THE 12? RULE OF THE CODE. THIS |
| APPLIES TO THE BEDROOM OUTLETS. |
| SHEET E504, UNIT L2 |
| 42. SEE UNIT L1 KITCHEN COMMENTS. |
| SHEET E504, UNIT L3 |
| 43. SEE UNIT L1 KITCHEN COMMENTS. |
| 44. SEE UNIT L1 COMMENT 41. |
| 45. SEE COMMENTS 40 & 41 FOR UNIT L1. |
| |
| SHEET E505, UNIT L4 |
| 46. SEE COMMENT 37 ABOVE FOR UNIT L1. |
| 47. SEE COMMENTS 41 ABOVE FOR UNIT L1. LOWER BEDROOM. |
| 48. PLEASE ABIDE BY THE 6 - 12 RECEPTACLE SPACING RULE |
| AND RELOCATE YOUR RECEPTACLES ACCORDINGLY. (UPSTAIRS |
| SITTING AREA). |
| 49. SEE COMMENT 41 ABOVE. UPPER BEDROOM. |
| SHEET E505, UNIT L5 |
| 50. SEE COMMENT 39 ABOVE. KITCHEN DISPOSAL |
| 51. SEE COMMENT 41 ABOVE FOR UNIT L1. LOWER BEDROOM. |
| 52. SEE COMMENT 41 ABOVE FOR UNIT L1. UPPER BEDROOM. |
| 53. SEE COMMENT 48 ABOVE FOR UNIT L4. UPPER SITTING |
| AREA. |
| SHEET E506, UNIT L6 |
| 54. FBC-RE3901.2.1SPACING. RECEPTACLES SHALL BE |
| INSTALLED SUCH THAT NO POINT MEASURED HORIZONTALLY |
| ALONG THE FLOOR LINE IN ANY WALL SPACE IS MORE THAN 6 |
| FT. FROM A RECEPTACLE OUTLET. THIS INCLUDES THE |
| DISTANCE FROM THE EDGE OF THE WALL. LOWER BEDROOM |
| 55. FBC-RE3903.4 STORAGE OR EQUIPMENT SPACES. AT LEAST |
| ONE LIGHTING OUTLET CONTAINING A SWITCH OR CONTROLLED |
| BY A WALL SWITCH SHALL BE INSTALLED WHERE THESE SPACES |
| ARE USED FOR STORAGE OR CONTAIN EQUIPMENT REQUIRING |
| SERVICING. THE LIGHTING OUTLET SHALL BE PROVIDED AT OR |
| NEAR THE EQUIPMENT REQUIRING SERVICING. EWH CLOSET |
| 56. CAREFUL NOT TO PLACE THIS SWITCH BEHIND THE DOOR TO |
| THIS BEDROOM. DOOR TO ROOM NOT DRAWN PLAN. UPPER |
| BEDROOM. |
| 57. FBC-RE3901.2.1: RELOCATE THIS OUTLET TO MEET CODE |
| SPACING REQUIREMENTS. UPPER SITTING AREA. |
| 58. SEE NOTE 54 ABOVE. UPPER BEDROOM. |
| SHEET E506, UNIT L7 |
| 59. SEE COMMENT 55 ABOVE. EWH CLOSET |
| 60. FBC-ER3901.4.4/NEC 210.52(C)(4) COUNTERTOP SPACES |
| SEPARATED BY RANGETOPS, REFRIGERATORS, OR SINKS SHALL |
| BE CONSIDERED AS SEPARATE COUNTERTOP SPACES IN APPLYING |
| THE REQUIREMENTS OF 210.52(C)(1). THEREFORE AN OUTLET |
| IS MISSING FROM THIS END OF THE PENINSULA. |
| 61. SEE COMMENT 57 ABOVE. |
| |
| 62. SHEET E506, UNIT L8 |
| 63. SEE COMMENT 55 ABOVE. |
| 64. SEE COMMENT 57 ABOVE. BEDROOM & LIVING ROOM |
| SHEET E506, UNIT L9 |
| 65. SEE COMMENT 55 ABOVE |
| 66. SEE COMMENT 57 ABOVE. BEDROOM & LIVING ROOM |
| SHEET E507, PENTHOUSE |
| 67. THIS IS AN INTERIOR BATHROOM AND IT REQUIRES AN |
| EXHAUST FAN. IF A NON-CONTINUOUS UNIT IS USED, IT SHALL |
| BE CONTROLLED WITH THE LIGHT SWITCH. HALF BATH |
| 68. ADJUST OUTLETS ALONG THESE WALLS TO MEET CODE |
| COMPLIANCE. CURTAIN WALL LIVING ROOM & DINING ROOM. |
| 69. IN THE INTEREST OF LIFE SAFETY, CONVENIENCE AND |
| ENERGY CONSERVATION THESE LIGHTS SHOULD BE ON A 3 WAY |
| SWITCH. |
| SHEET E507, UNIT 8B |
| 70. SEE COMMENT 55 ABOVE. |
| 71. FBC-RE3901.2.2: ANY WALL SPACE 2 FT. OR MORE IN |
| WIDTH SHALL REQUIRE A RECEPTACLE. ROOM ADJACENT TO |
| KITCHEN |
| SHEET E601, E602, E610, APPROVED W/PROVISO |
| 72. NEC110.26 (D) ILLUMINATION: ILLUMINATION SHALL BE |
| PROVIDED FOR ALL WORKING SPACES ABOUT ELECTRICAL |
| SERVICE EQUIPMENT INSTALLED INDOORS AND SHALL NOT BE |
| CONTROLLED BY AUTOMATIC MEANS ONLY. THIS APPLIES TO ALL |
| ROOMS ENLARGED ON THIS SHEET. |
| SHEET E701 |
| 73. NEC 110.24: ALL SERVICE EQUIPMENT SHALL BE LEGIBLY |
| MARKED IN THE FIELD WITH THE MAXIMUM AVAILABLE FAULT |
| CURRENT. THE FIELD MARKING(S) SHALL INCLUDE THE DATE |
| THE FAULT CURRENT CALCULATION WAS PERFORMED AND BE OF |
| SUFFICIENT DURABILITY TO WITHSTAND THE ENVIRONMENT |
| INVOLVED. |
| 74. CLARIFY FEEDER LABELED AS E702D'S DESTINATION. I |
| CAN?T FIND IT ON SHEET E702. |
| SHEET E703, APPROVED W/PROVISO |
| 75. FIRE ALARM WORK UNDER SEPARATE PERMIT |
| SHEET E1401 |
| 76. THE PANEL SCHEDULE OF N1MSBHA DOES NOT MATCH THE |
| RISER DIAGRAM OF SHEET E701. |
| 77. CORRECT CKT. 17, 19. 21 OF LS1DPH TO MATCH SHEET |
| E702 (LS21HA) |
| 78. PANEL SCHEDULE OF E1DPH DOES NOT MATCH RISER |
| DIAGRAM OF SHEET E702 |
| SHEET E1406 |
| 79. OCP FOR UNIT PENT PANEL DOES NOT MATCH WHAT IS |
| REFLECTED ON RISER OF SHEET E701 |
| |
| WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR |
| RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER |
| (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER |
| WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD |
| CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID |
| AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR |
| COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE |
| GREATLY APPRECIATED. |
| |
| IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO |
| CONTACT ME DIRECTLY. |