Plan Review Notes
Plan Review Notes For Permit 16070715
Permit Number 16070715
Review Stop E
Sequence Number 1
Notes
Date Text
2016-10-11 18:51:08REVIEWED FOR COMPLIANCE WITH: 5TH EDITION FBC 2014 &
 NFPA 70 2011 (NEC)
  
 BELOW ARE THE ELECTRICAL COMMENTS FOR THE FAILED PLAN
 REVIEW:
  
 TYPICAL COMMENT: CITY OF WEST PALM BEACH AMENDMENTS TO
 THE FBC-B SECTION 107.2.1.4 REQUIRES THAT BUILDING
 PLANS BE DRAWN TO A MINIMUM 1/8? SCALE. THE SUBMITTED
 DRAWINGS ARE DRAWN TO A 3/32? SCALE MAKING THEM A BIT
 SMALLER THAN THE REQUIRED. PLEASE CORRECT ACCORDINGLY.
  
 SHEET E000
 1. CLARIFY THE FRONT OF PANEL WHEN RECESSED IN THE
 DISTRIBUTION EQUIPMENT BOX
 2. IS IT YOUR INTENT TO SHARE THESE SYMBOLS IN THE
 LIGHTING LEGEND
 3. IS IT YOUR INTENT TO SHARE THIS SYMBOL IN THE POWER
 CONNECTIONS BOX
 4. FIRE ALARM WORK SHALL BE UNDER SEPARATE PERMIT &
 SUBMITTAL
 SHEET E001
 5. PLEASE TRY TO BE CONSISTENT WITH THE ABBREVIATIONS
 THROUGHOUT THE SET. I SEE MULTIPLE SYMBOLS W/THE SAME
 DESIGNATION. SYMBOLS NOT ALIGNED TO DESCRIPTION.
 6. IS IT YOUR INTENT TO SHARE THIS SYMBOL IN THE
 DEMOLITION NOTES BOX
 SHEET E201A
 7. NEC 422.31: EWH-4 REQUIRES A DISCONNECT
 8. NEC 210.8(B): RECEPTACLE OUTLETS IN GARAGES OR
 INDOOR WET LOCATIONS SHALL BE GFI PROTECTED
 9. SEE NEC 430 FOR THE REQUIRED DISCONNECTS AND
 ADDITIONAL CONTROLS AND SAFETY DEVICES REQUIRED,
 TYPICAL TO ALL MOTOR LOADS
 SHEET E202
 10. HIGHLY UNLIKELY THAT THERE WILL ONLY BE 2 OUTLETS
 IN THE MEZZANINE
 SHEET E203
 11. THE FOLLOWING MOTORS AND APPLIANCES REQUIRED
 DISCONNECTS AS MENTIONED ABOVE AHU2-1, FCU2-2, EWH-8,
 FCU2-1.1, FCU2-3, FCU2-1.2, EWH-4
 SHEET E204
 12. SAME AS ABOVE FOR FCU3-1
 SHEET E208
 13. SAME AS ABOVE FOR FCU7-1
 SHEET E210
 14. SAME AS ABOVE FOR FCU9-3, SF9-3, AS WELL AS EVERY
 MOTOR & HVAC EQUIPMENT ON ROOF
 SHEET E211
 15. SAME AS ABOVE FOR FCU10-1
 SHEET E212
 16. SAME AS ABOVE FOR UNITS SF11-1, FCU12.5-1, FCU11-2
 & CU12.5-1
 SHEET E213
 17. SAME AS ABOVE FOR AHU12-6, EF12-1
 SHEET E214
 18. SAME AS ABOVE FOR ALL MOTORS AND ELECTRIC WATER
 HEATER IN ROOM 12.508
 SHEET E301A
 19. RETAIL R02 ? LIGHTING ARRANGEMENT AS DESCRIBED DOES
 NOT MEET THE DAYLIGHT ZONE CONTROL REQUIREMENTS OF THE
 FBC-E405.2.2.3
 20. FBC-B 1011.1 EXITS AND EXIT ACCESS SHALL BE MARKED
 BY AN APPROVED EXIT SIGN READILY VISIBLE FROM ANY
 DIRECTION OF EGRESS TRAVEL. THE PATH OF EGRESS SHALL BE
 CLEARLY MARKED WHEN NOT READILY VISIBLE. THERE SHALL
 NOT BE MORE 100? BETWEEN EXIT SIGN ALONG THE PATH OF
 EGRESS.
 21. RETAIL R01 ? LIGHTING ARRANGEMENT AS DESCRIBED DOES
 NOT MEET THE DAYLIGHT ZONE CONTROL REQUIREMENTS OF THE
 FBC-E405.2.2.3
 22. RETAIL R03 ? LIGHTING ARRANGEMENT AS DESCRIBED DOES
 NOT MEET THE DAYLIGHT ZONE CONTROL REQUIREMENTS OF THE
 FBC-E405.2.2.3
 23. DUE TO THE LACK OF ROOM LABELS, ADDITIONAL LIGHTING
 CONTROLS MAY BE REQUIRED
 SHEET E303, E304, E305, E306, E307, E308, E309, E310,
 E311, E312
 24. THIS SHEET DOES NOT CLEARLY INDICATE THE LOCATION
 OF EGRESS DOORS OR UP/DOWN RAMP, THEREFORE PROPER EXIT
 LIGHT LOCATION IS NOT IDENTIFIABLE
 SHEET E314
 25. THIS AREA IS NOT IDENTIFIED ON THE PLANS, THEREFORE
 EXIT LIGHTING AND LIGHTING CONTROL REQUIREMENTS CAN?T
 BE PROPERLY DETERMINED
 SHEET E318
 26. EXIT LIGHT REQUIRED BY ROOF EXIT DOORWAY
 SHEET E501
 27. NEC 210.52(C)(4): (UNITS 6, 2, 04,) AN OUTLET IS
 REQUIRED ON EITHER SIDE OF THIS SINK
 28. NEC 210.70: (UNIT 04) THE AREA LEADING TO THE
 BEDROOM IS MISSING ILLUMINATION
 SHEET E503
 29. NEC 210.52(A)(2): WALL SPACE. ANY WALL SPACE 2 FT.
 OR MORE IN WIDTH SHALL REQUIRE A RECEPTACLE. SEE LIVING
 ROOM OF UNIT 20
 30. NEC 210.52(C)(4): (UNITS 20 ) AN OUTLET IS REQUIRED
 ON EITHER SIDE OF THIS SINK
 31. NEC 110.26(D): ILLUMINATION SHALL BE PROVIDED FOR
 ALL WORKING SPACES ABOUT SERVICE EQUIPMENT,
 SWITCHBOARDS, AND PANELBOARDS. THIS LIGHT SHALL NOT BE
 CONTROLLED BY AUTOMATIC MEANS ONLY. CHECK THE SMC
 CLOSET OF UNIT 20
 32. NEC 210.52(C)(4): (UNITS 18) AN OUTLET IS REQUIRED
 ON EITHER SIDE OF THIS SINK
 33. NEC 210.52 (A)(1): RECEPTACLES SHALL BE INSTALLED
 SUCH THAT NO POINT MEASURED HORIZONTALLY ALONG THE
 FLOOR LINE IN ANY WALL SPACE IS MORE THAN 6 FT. FROM A
 RECEPTACLE OUTLET. THIS INCLUDES THE DISTANCE FROM THE
 EDGE OF THE WALL. A FLOOR BOX IS REQUIRED ALONG THE
 WALL WITH ALL THE WINDOWS IN THE LIVING ROOM OF UNIT 18
 34. NEC 210.52(H): IN DWELLING UNITS, HALLWAYS OF 10 FT
 OR MORE IN LENGTH SHALL HAVE AT LEAST ONE RECEPTACLE
 OUTLET. SEE THE MASTER BEDROOM CORRIDOR OF UNIT 18
 35. NEC 210.52(A)(2): WALL SPACE. ANY WALL SPACE 2 FT.
 OR MORE IN WIDTH SHALL REQUIRE A RECEPTACLE. SEE WALL
 BEHIND MASTER BEDROOM SINK OF UNIT 18
 36. NEC 110.26(D): ILLUMINATION SHALL BE PROVIDED FOR
 ALL WORKING SPACES ABOUT SERVICE EQUIPMENT,
 SWITCHBOARDS, AND PANELBOARDS. THIS LIGHT SHALL NOT BE
 CONTROLLED BY AUTOMATIC MEANS ONLY. SEE AREA IN FRONT
 OF ELECTRICAL PANEL OF UNIT 18.
 SHEET E504, UNIT L1
 37. FBC-RE3901.4: IF THE AREA ADJACENT TO THE
 REFRIGERATOR IS COUNTER SPACE, AN OUTLET IS REQUIRED.
 38. FBC-ER3901.4.1: KITCHEN RECEPTACLE REQUIRED
 39. ARE YOU SURE THAT YOU WANT THE SWITCH FOR THE
 DISPOSAL THAT FAR AWAY FROM THE SINK
 40. FBC-RE3901.2.1: A RECEPTACLE IS REQUIRED NO MORE
 THAN 6? FROM THE WALL EDGE OF THE KITCHEN TO THE LR.
 41. FBC-RE3901.2.1: THE LINEAR WALL SPACE BETWEEN THESE
 TWO OUTLETS EXCEEDS THE 12? RULE OF THE CODE. THIS
 APPLIES TO THE BEDROOM OUTLETS.
 SHEET E504, UNIT L2
 42. SEE UNIT L1 KITCHEN COMMENTS.
 SHEET E504, UNIT L3
 43. SEE UNIT L1 KITCHEN COMMENTS.
 44. SEE UNIT L1 COMMENT 41.
 45. SEE COMMENTS 40 & 41 FOR UNIT L1.
  
 SHEET E505, UNIT L4
 46. SEE COMMENT 37 ABOVE FOR UNIT L1.
 47. SEE COMMENTS 41 ABOVE FOR UNIT L1. LOWER BEDROOM.
 48. PLEASE ABIDE BY THE 6 - 12 RECEPTACLE SPACING RULE
 AND RELOCATE YOUR RECEPTACLES ACCORDINGLY. (UPSTAIRS
 SITTING AREA).
 49. SEE COMMENT 41 ABOVE. UPPER BEDROOM.
 SHEET E505, UNIT L5
 50. SEE COMMENT 39 ABOVE. KITCHEN DISPOSAL
 51. SEE COMMENT 41 ABOVE FOR UNIT L1. LOWER BEDROOM.
 52. SEE COMMENT 41 ABOVE FOR UNIT L1. UPPER BEDROOM.
 53. SEE COMMENT 48 ABOVE FOR UNIT L4. UPPER SITTING
 AREA.
 SHEET E506, UNIT L6
 54. FBC-RE3901.2.1SPACING. RECEPTACLES SHALL BE
 INSTALLED SUCH THAT NO POINT MEASURED HORIZONTALLY
 ALONG THE FLOOR LINE IN ANY WALL SPACE IS MORE THAN 6
 FT. FROM A RECEPTACLE OUTLET. THIS INCLUDES THE
 DISTANCE FROM THE EDGE OF THE WALL. LOWER BEDROOM
 55. FBC-RE3903.4 STORAGE OR EQUIPMENT SPACES. AT LEAST
 ONE LIGHTING OUTLET CONTAINING A SWITCH OR CONTROLLED
 BY A WALL SWITCH SHALL BE INSTALLED WHERE THESE SPACES
 ARE USED FOR STORAGE OR CONTAIN EQUIPMENT REQUIRING
 SERVICING. THE LIGHTING OUTLET SHALL BE PROVIDED AT OR
 NEAR THE EQUIPMENT REQUIRING SERVICING. EWH CLOSET
 56. CAREFUL NOT TO PLACE THIS SWITCH BEHIND THE DOOR TO
 THIS BEDROOM. DOOR TO ROOM NOT DRAWN PLAN. UPPER
 BEDROOM.
 57. FBC-RE3901.2.1: RELOCATE THIS OUTLET TO MEET CODE
 SPACING REQUIREMENTS. UPPER SITTING AREA.
 58. SEE NOTE 54 ABOVE. UPPER BEDROOM.
 SHEET E506, UNIT L7
 59. SEE COMMENT 55 ABOVE. EWH CLOSET
 60. FBC-ER3901.4.4/NEC 210.52(C)(4) COUNTERTOP SPACES
 SEPARATED BY RANGETOPS, REFRIGERATORS, OR SINKS SHALL
 BE CONSIDERED AS SEPARATE COUNTERTOP SPACES IN APPLYING
 THE REQUIREMENTS OF 210.52(C)(1). THEREFORE AN OUTLET
 IS MISSING FROM THIS END OF THE PENINSULA.
 61. SEE COMMENT 57 ABOVE.
  
 62. SHEET E506, UNIT L8
 63. SEE COMMENT 55 ABOVE.
 64. SEE COMMENT 57 ABOVE. BEDROOM & LIVING ROOM
 SHEET E506, UNIT L9
 65. SEE COMMENT 55 ABOVE
 66. SEE COMMENT 57 ABOVE. BEDROOM & LIVING ROOM
 SHEET E507, PENTHOUSE
 67. THIS IS AN INTERIOR BATHROOM AND IT REQUIRES AN
 EXHAUST FAN. IF A NON-CONTINUOUS UNIT IS USED, IT SHALL
 BE CONTROLLED WITH THE LIGHT SWITCH. HALF BATH
 68. ADJUST OUTLETS ALONG THESE WALLS TO MEET CODE
 COMPLIANCE. CURTAIN WALL LIVING ROOM & DINING ROOM.
 69. IN THE INTEREST OF LIFE SAFETY, CONVENIENCE AND
 ENERGY CONSERVATION THESE LIGHTS SHOULD BE ON A 3 WAY
 SWITCH.
 SHEET E507, UNIT 8B
 70. SEE COMMENT 55 ABOVE.
 71. FBC-RE3901.2.2: ANY WALL SPACE 2 FT. OR MORE IN
 WIDTH SHALL REQUIRE A RECEPTACLE. ROOM ADJACENT TO
 KITCHEN
 SHEET E601, E602, E610, APPROVED W/PROVISO
 72. NEC110.26 (D) ILLUMINATION: ILLUMINATION SHALL BE
 PROVIDED FOR ALL WORKING SPACES ABOUT ELECTRICAL
 SERVICE EQUIPMENT INSTALLED INDOORS AND SHALL NOT BE
 CONTROLLED BY AUTOMATIC MEANS ONLY. THIS APPLIES TO ALL
 ROOMS ENLARGED ON THIS SHEET.
 SHEET E701
 73. NEC 110.24: ALL SERVICE EQUIPMENT SHALL BE LEGIBLY
 MARKED IN THE FIELD WITH THE MAXIMUM AVAILABLE FAULT
 CURRENT. THE FIELD MARKING(S) SHALL INCLUDE THE DATE
 THE FAULT CURRENT CALCULATION WAS PERFORMED AND BE OF
 SUFFICIENT DURABILITY TO WITHSTAND THE ENVIRONMENT
 INVOLVED.
 74. CLARIFY FEEDER LABELED AS E702D'S DESTINATION. I
 CAN?T FIND IT ON SHEET E702.
 SHEET E703, APPROVED W/PROVISO
 75. FIRE ALARM WORK UNDER SEPARATE PERMIT
 SHEET E1401
 76. THE PANEL SCHEDULE OF N1MSBHA DOES NOT MATCH THE
 RISER DIAGRAM OF SHEET E701.
 77. CORRECT CKT. 17, 19. 21 OF LS1DPH TO MATCH SHEET
 E702 (LS21HA)
 78. PANEL SCHEDULE OF E1DPH DOES NOT MATCH RISER
 DIAGRAM OF SHEET E702
 SHEET E1406
 79. OCP FOR UNIT PENT PANEL DOES NOT MATCH WHAT IS
 REFLECTED ON RISER OF SHEET E701
  
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER
 (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER
 WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD
 CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID
 AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR
 COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE
 GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
 THANK YOU,
 MIKE ALBARRAN
 ELECTRICAL PLANS EXAMINER
 PH: 561-805-6746
 EMAIL: [email protected]
  