2016-09-15 18:01:36****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. UPDATE PLANS WITH THE CHANGES MADE TO PERMIT
 16040755, STRUCTURE PERMIT. SOME OF THE COMMENTS IN
 THIS LIST HAVE ALREADY BEEN CORRECTED IN THE STRUCTURE
 PERMIT AND HAVE BEEN FOUND CODE COMPLIANT.
  
 2. FOR C.O. INFORMATION, PROVIDE THE FOLLOWING:
 TOTAL NUMBER OF BEDROOMS
 TOTAL NUMBER OF BATHROOMS
 TOTAL NUMBER OF ROOMS
  
 3. FBC TABLE 705.8. SHEET A100 SHOWS THE NORTH
 ELEVATION (PARTIAL) AS 12FT 1IN FROM THE BUILDING TO
 THE CENTER LINE OF THE ALLEY; SHEET A200 INCLUDES THE
 LIMITATION OF 45 PERCENT UNPROTECTED OPENINGS ALLOWED.
 REVISE THE PLAN TO INCLUDE THE PERCENTAGE OF
 UNPROTECTED OPENINGS FOR THIS BUILDING, NORTH
 ELEVATION.
  
 4. A100 SITE PLAN SHOWS THE APPROX CENTER OF ALLEY.
 REVISE TO INCLUDE EXACT DIMENSION BASED ON THE SURVEY
 OR PLAT SO COMPLIANCE WITH FBC TABLE 602, 705.8 CAN BE
 DETERMINED.
  
 5. FBC TABLE 602, BASED ON FIRE SEPARATION DISTANCE
 (CHAPTER 2), THE NORTH WALL REQUIRES A 1 HOUR RATING.
 A. REVISE TO INCLUDE ON SHEET A201 AND ALL OTHER SHEETS
 AFFECTED OR REVISE SITE PLAN ON A100 TO CLARIFY FIRE
 SEPARATION DISTANCE.
 B. REVISE DOOR SCHEDULE TO COMPLY WITH FBC TABLE 716.5
 FOR AFFECTED DOORS.
  
 6. FBC TABLES 601, 602, PROVIDE DETAILS FOR THE FIRE
 RATED ELEMENTS, INCLUDING THE NORTH WALL WHICH HAS A
 FIRE SEPARATION DISTANCE LESS THAN 30FT, FBC 703, 704.
  
 7. A200, STRUCTURAL FIRE RESISTANCE RATING
 REQUIREMENTS, REVISE STRUCTURE AND ROOF REQUIREMENTS TO
 BE CONSISTENT WITH TABLE 601 OR REVISE PLAN TO INCLUDE
 APPLICABLE EXCEPTION.
  
 8. A200, STRUCTURAL FIRE RESISTANCE RATING
 REQUIREMENTS, A TABLE FROM THE FBC WAS INCLUDED BUT
 DOES NOT INDICATE HOW THE TABLE APPLIES TO THIS
 PROJECT. REVISE TO INCLUDE THE WALLS AFFECTED, FBC
 TABLE 602, FBC 107.
  
 9. FBC 403.5.3 AND 403.5.3(1), REVISE PLAN TO CLARIFY
 PROPOSED EXIT STAIR DOOR OPERATION (OR ADVISE WHERE
 THIS INFORMATION CAN BE FOUND).
  
 10. A200 SPECIFIES BOTH OCCUPANCY SEPARATION AND NON
 SEPARATED OCCUPANCIES. REVISE PLAN TO CLARIFY WHICH OF
 THE TWO METHODS IS PROPOSED, FBC 508. THIS INFORMATION
 IS ALSO REQUIRED FOR THE TENANT BUILD OUTS, FBC 107.
  
 11. A200 OCCUPANCY SEPARATION REFERS TO ASSEMBLY WITHIN
 EDUCATIONAL OCCUPANCIES (NOTE 1), REMOVE THIS AND OTHER
 NOTES WHICH DO NOT APPLY TO THIS PROJECT, OR CLARIFY
 WHERE THIS IS OR MAY BE APPLICABLE.
  
 12. A200 OCCUPANCY CLASSIFICATION INCLUDES A1 THEATER;
 ADVISE WHERE THIS CAN BE LOCATED, OR IS THIS A FUTURE
 IMPROVEMENT? FBC 107. REMOVE IF NOT APPLICABLE.
  
 13. A200 AND OTHER PAGES, FIRE RESISTANCE REQUIREMENTS
 WALLS, ITEM C, IS NOT CLEAR WHERE THIS IS APPLICABLE.
 REVISE TO REFLECT THE REQUIREMENT FOR THIS PROJECT. IT
 WOULD BE HELPFUL IF THE ACTUAL FIRE RATING REQUIREMENTS
 SPECIFIC TO THIS PROJECT WERE INCORPORATED INTO THIS
 TABLE (SUGGESTED, NOT REQUIRED).
  
 14. SPECIFY ACCESSIBLE MEANS OF EGRESS SELECTED, FBC
 BUILDING 1007, FBC ACCESSIBILITY 207. REVISE PLAN TO
 SHOW COMPLIANCE WITH METHOD SELECTED IF ALL ITEMS ARE
 NOT IMMEDIATELY APPARENT (FOR EXAMPLE, IBC2000 ELEVATOR
 AS MEANS OF EGRESS COMPONENT).
  
 15. A200 REGARDING SIGNAGE ITEM 2; CLARIFY ACCESSIBLE
 MEANS OF EGRESS SELECTED AND REVISE NOTE IF APPLICABLE.
  
 16. A200, SIGNAGE NOTE 3, THE LANGUAGE, LOCATION AND
 CODE REFERENCE ARE NOT CONSISTENT WITH FBC 703.7;
 REVISE OR CLARIFY. VERIFY THAT ALL NOTES HAVE
 SPECIFICATIONS AND CODE REFERENCES CONSISTENT WITH FBC
 2014, FBC 107. IT APPEARS THAT SEVERAL REFERENCES ARE
 FROM A PREVIOUS CODE VERSION.
  
 17. A200 FIRE EXTINGUISHER NOTES DO NOT REFERENCE FBC
 906, REVISE.
  
 18. A200 INCIDENTAL USE AREAS AND NON PROTECTED SHAFT
 DO NOT APPEAR TO BE APPLICABLE. EITHER REMOVE OR REVISE
 TO CLARIFY LOCATIONS PROPOSED, FBC 107.
  
 19. FOR C.O., AN ACCURATE OCCUPANT LOAD FOR THE
 BUILDING IS REQUIRED. SEE A202; GARAGE OCC LOAD IN THE
 CHART IS NOT CONSISTENT WITH THE GARAGE OCC LOAD ON THE
 PLAN. THE TOTAL OCCUPANTS PER LEVEL AND OCCUPANT LOAD
 CATEGORY ARE LACKING SEVERAL FLOORS (15 TO 23),
 PLEASE CORRELATE AND UPDATE TO REFLECT CORRECTED
 OCCUPANT LOAD ON THE POOL DECK AND ANY OTHER CHANGES.
  
 20. FBC 406.4, CLASSIFY THE PARKING GARAGE AS EITHER
 ENCLOSED OR OPEN. IT IS SUGGESTED THAT THIS BE
 INCORPORATED WITH THE BUILDING GENERAL DATA A201. IF
 OPEN, PROVIDE PERCENTAGE OF OPENINGS PROVIDED TO SHOW
 COMPLIANCE WITH FBC 406.5. IF ENCLOSED, PROVIDE
 VENTILATION 406.6.2.
  
 21. A202, LIFE SAFETY TCO NOTES INCLUDES FOUR TCO
 PHASES; PLAN SHOWS TWO, PLEASE CORRELATE.
  
 22. A202, THE LIFE SAFETY PLAN LACKS STAIR NUMBER
 DESIGNATIONS. PROVIDE IN ORDER TO CORRELATE WITH
 DETAILS ON A701-A712, FBC 107. CHECK ALL SHEETS.
  
 23. IT IS NOT CLEAR WHERE THE EXIT DISCHARGE IS LOCATED
 FOR STAIR LOCATED AT GRIDLINES H3 SHEET A202, FBC 107.
 (ITEM ADDRESSED IN STRUCTURE PERMIT, PLEASE UPDATE.)
  
 24. AS301 LEVEL 1, THE ACCESSIBLE ROUTE FOR THE
 ACCESSIBLE VAN PARKING SPACE IS NOT CLEAR; THIS WAS
 ADDRESSED IN STRUCTURE PERMIT, PLEASE UPDATE PLANS.
  
 25. AVIS, LEASING OFFICE, RETAIL/RESTAURANT, AND
 PASSENGER PARKING MINIMUM REQUIREMENTS ARE COVERED BY
 FBC 5TH EDITION ACCESSIBILITY 208, RESIDENTIAL PARKING
 MINIMUM REQUIREMENTS DETERMINED BY FBC 5TH EDITION
 ACCESSIBILITY FAIR HOUSING.
  
 A100, PARKING SCHEDULE, AND OTHER PAGES, REVISE TO SHOW
 COMPLIANCE WITH THE FOLLOWING ITEMS:
  
 THE OPERATION OF THE AVIS BUSINESS AND SPACES IS NOT
 CLEAR. REVISE THE PLAN TO CLARIFY HOW THIS BUSINESS
 WILL OPERATE. WILL CUSTOMERS PICK UP THE CARS, OR WILL
 THE CAR BE BROUGHT TO THE CUSTOMER? IT APPEARS THAT AN
 ACCESSIBLE AVIS SPACE OR A PASSENGER LOADING ZONE MAY
 BE REQUIRED. REVISE PLAN TO DEMONSTRATE COMPLIANCE (OR
 EXEMPTION), INCLUDING APPLICABLE DETAILS. IF THE
 PARKING SPACES ARE FOR AUTO STORAGE ONLY, REVISE PLAN
 TO INCLUDE THIS INFORMATION AS WELL AS DETAILS FOR THE
 PASSENGER LOADING ZONE (FBC ACCESSIBILITY 208.1, 503),
 OR REVISE PLAN TO INCORPORATE INFORMATION REGARDING
 FUNCTION OF THE AUTO RENTAL AREA AND HOW THIS AREA
 COMPLIES WITH (OR IS EXEMPT FROM) ACCESSIBILITY.
  
 26. FBC ACCESSIBILITY 208, PARKING FOR THE RETAIL AND
 RESTAURANT AREAS IS NOT CLEAR. REVISE PLAN TO INDICATE
 NUMBER OF SPACES, ACCESSIBLE SPACES, VAN SPACES, AND
 LOCATION OR NOTE IF NONE OF THE PARKING SPACES IN THIS
 STRUCTURE ARE FOR THE RETAIL/RESTAURANT AREAS.
  
 27. SEE PLUMBING COMMENTS REGARDING ACCESSIBILITY AND
 REVISE PLAN TO SHOW COMPLIANCE.
  
 28. A212, CLARIFY USE OF THE AMENITIES ROOM, FBC 107.
  
 29. LEASING OFFICE PARKING PROVIDED IS NOT CLEAR.
 REVISE PLAN TO DESIGNATE NUMBER OF PARKING SPACES
 DEDICATED TO LEASING, ACCESSIBLE AND VAN SPACES (NUMBER
 AND LOCATIONS), FBC ACCESSIBILITY 208. IT MAY BE
 HELPFUL TO DESIGNATE WHICH FLOORS OR AREAS ARE FOR
 RESIDENTS, RETAIL VISITORS, AND TRANSIT.
  
 30. ONE GUEST SPACE IS SHOWN ON THE PARKING SCHEDULE.
 REVISE TO DESIGNATE WHETHER THIS IS FOR PASSENGER,
 LEASING, RETAIL OR RESIDENT PARKING AND NOTE LOCATION
 ON PLAN, FBC ACCESSIBILITY 208.
  
 31. A212, POOL DECK OCCUPANT LOAD SHOULD BE CALCULATED
 AT 15SF GROSS PER PERSON, PLEASE REVISE TABLES AND
 OCCUPANT LOAD FOR THE POOL DECK. IT DOES NOT APPEAR
 THAT EXITING IS ADEQUATE FOR THIS ASSEMBLY AREA; FBC
 5TH EDITION TABLE 1004.1.2. THIS ITEM WAS ADDRESSED IN
 THE STRUCTURE PERMIT; PLEASE REVISE TO BE CONSISTENT
 WITH 16040755.
 32. REVISE PLAN TO SHOW THE 18IN MANEUVERING CLEARANCE,
 PULL SIDE (FBC ACCESSIBILITY 404.2.4), DOOR LOCATED ON
 SHEET A301, DOOR R03H (FBC 5TH ED. ACCESSIBILITY
 206.4.5), OR OTHERWISE INDICATE THAT THIS WILL NOT BE
 THE ONLY DOOR SERVING A TENANT SPACE, OR PROVIDE AN
 OPENER.
  
 33. SHEET AS212A, DOORS TO LOBBY FROM POOL AREA SWING
 AGAINST PATH OF TRAVEL, FBC 1008.1.2.
  
 34. ADVISORY; SHEET AS203, THE SOUTH ACCESSIBLE PARKING
 SPACE (GRIDLINE G4) REQUIRES THE OCCUPANT TO TRAVEL
 BEHIND THE VAN PARKING SPACE TO ACCESS THE LOBBY, AVIS,
 AND RESIDENTIAL LOBBY. THIS WILL BE REQUIRED TO BE
 CORRECTED ON THE BUILDING PERMIT.
  
 35. FBC 505, LEVEL 12.5 IS NOT SHOWN AS A STORY ON THE
 BUILDING DATA. EITHER REVISE PLAN TO SHOW COMPLIANCE
 WITH REQUIREMENTS FOR MEZZANINES, OR REVISE BUILDING
 DATA INFORMATION.
  
 36. COMPLIANCE WITH FBC 5TH EDITION ACCESSIBILITY, FAIR
 HOUSING IS NOT CLEAR. IF DESIGNING USING THE FAIR
 HOUSING ACT DESIGN MANUAL, PROVIDE UNIT LAYOUTS WITH
 UNIT TYPE AND DIMENSIONS SHOWING COMPLIANCE.
  
 IF USING ANOTHER METHOD, PROVIDE DETAILS AND DIMENSIONS
 TO SHOW COMPLIANCE.
  
 37. F202 AND E202 SHOW A MEZZANINE, PROVIDE AN
 ARCHITECTURAL FLOOR PLAN; LOCATION IS NOT CLEAR, AND IS
 THIS A MEZZANINE PER FBC505? INCLUDE ALL INFORMATION
 REQUIRED TO DETERMINE CODE COMPLIANCE FOR THIS AREA,
 FBC 107. IF THIS IS NOT A MEZZANINE, IT IS SUGGESTED
 THAT THE NAME OF THE AREA BE REVISED FOR CLARITY.
  
 38. UNIT NAMES ON LIFE SAFETY SHEETS ARE NOT THE SAME
 AS FLOOR PLANS (FOR INSTANCE, SEE A202 AND A302),
 CORRELATE.
  
 39. A FIRE ALARM SYSTEM IN COMPLIANCE WITH FBC
 907.2.13.1 IS REQUIRED PER FBC 403.4.2. SMOKE DETECTORS
 IN COMPLIANCE WITH FBC 907.2.13.1 IS REQUIRED PER FBC
 403.4.1. REVISE PLAN TO INCLUDE NOTES, OR ADVISE WHERE
 COMPLIANCE WITH THESE STANDARDS CAN BE LOCATED ON THE
 PLAN. BOTH ITEMS REQUIRE SEPARATE APPLICATIONS,
 PERMITS, PLANS AND FEES, FBC 107, AND WILL BE REVIEWED
 AT THAT TIME.
  
 40. FBC 403.4.5, EMERGENCY RESPONDER RADIO COVERAGE,
 REVISE PLAN TO INCLUDE A NOTE TO SHOW COMPLIANCE WITH
 THIS SECTION.
  
 NFPA 1, CHAPTER 11, BUILDING SERVICES; 11.10 TWO-WAY
 RADIO ENHANCEMENT SERVICES.
 11.10.1 IN ALL NEW AND EXISTING BUILDINGS, MINIMUM
 RADIO SIGNAL STRENGTH FOR FIRE DEPARTMENT
 COMMUNICATIONS SHALL BE MAINTAINED AT A LEVEL
 DETERMINED BY THE AHJ.
 MAINTAIN A MINIMUM RADIO SIGNAL STRENGTH OF 102.0 DBM
 FOR THE RADIO SYSTEM USED BY WEST PALM BEACH FIRE
 RESCUE. IF THE MINIMUM CANNOT BE MAINTAINED, A
 BI-DIRECTIONAL AMPLIFIED SYSTEM SHALL BE INSTALLED WITH
 A MINIMUM 2-HOUR RUN TIME BATTERY BACK-UP.
  
 41. STANDBY POWER, FBC 403.4.8, EMERGENCY POWER 403.4.9
 REQUIRED. REVISE PLAN TO SHOW COMPLIANCE OR ADVISE AS
 TO WHERE THIS CAN BE LOCATED. CLARIFY WHICH ITEMS WILL
 BE ON EMERGENCY POWER. WHICH ELEVATOR(S) WILL BE
 INCLUDED (FBC 1007)?
  
 42. FBC 403.5.4 SMOKEPROOF EXIT, THE NEW STAIR (5?)
 DOES NOT APPEAR ON THE MECHANICAL SHEETS (MEZZANINE
 LEVEL AS SHOWN ON FIRE AND ELEC PAGES, M704, OTHER
 PAGES).
  
 43. FBC 905.4, STANDPIPE REQUIRED IN STAIRS, UNABLE TO
 LOCATE THIS FOR THE NEW STAIR.
  
 44. FBC 403.6.1, COMPLIANCE WITH FIRE SERVICE ACCESS
 ELEVATOR REQUIREMENTS IS NOT CLEAR. SHEET A202 (AND
 OTHER LIFE SAFETY SHEETS) SHOW A FIRE SERVICE LOBBY ON
 THE WEST SIDE WHICH IS NOT INCLUDED IN TCO AREA 1. ALL
 LIFE SAFETY SYSTEMS ARE TO BE IN PLACE FOR TCO.
  
 THE ELEVATORS DESIGNATED AS FIRE SERVICE IS NOT CLEAR.
 FOR INSTANCE, SEE LEVEL 8. IT APPEARS THAT ONLY THE
 NORTH ELEVATOR, WEST SIDE IS DESIGNATED AS THE FIRE
 SERVICE ELEVATOR, BUT AT LEAST TWO ARE REQUIRED PER FBC
 403.6.1.
 REVISE PLAN TO SHOW COMPLIANCE WITH THE FIRE SERVICE
 ELEVATORS REQUIREMENT, INCLUDING THE WEIGHT CAPACITY
 REQUIREMENT. FIRE SERVICE ELEVATORS ARE TO COMPLY WITH
 FBC 3007. REVISE PLAN TO SHOW COMPLIANCE WITH 3007.2
 RECALL, 3007.7.5 SIGNAGE, 3007.3 SPRINKLERS, 3007.4
 WATER PROTECTION, 3007.6.1, 3007.6.2 HOISTWAY LIGHTING,
 3007.7.2 1 HOUR SMOKE BARRIER FOR LOBBY, 3007.7.3 LOBBY
 DOORS, 3007.8 MONITORING, 3007.9 ELECTRICAL POWER,
 3007.9.1 PROTECTION OF WIRING AND CABLES.
  
 45. SOME LEVELS (FOR INSTANCE, LEVELS 12.5, 13) LACK A
 FIRE SERVICE ELEVATOR FBC 403.
  
 46. FBC 3004, HOISTWAY VENTING NOT CLEAR, REVISE PLAN
 TO SHOW COMPLIANCE.
  
 47. FBC 3002.4, SHOW LOCATION OF STRETCHER ELEVATOR
 SIGNAGE.
  
 48. FBC 908.7, CARBON MONOXIDE DETECTORS ARE REQUIRED,
 REVISE.
  
 49. PRODUCT APPROVALS FOR COMPONENTS AND CLADDING HAVE
 NOT BEEN SUBMITTED. THEY MAY BE A DEFERRED SUBMITTAL.
 THEY MAY BE SUBMITTED, PRIOR TO INSTALLATION, AS A
 REVISION, PRIOR TO INSTALLATION.
  
 50. FLOORING UNDERLAYMENT IS TO COMPLY WITH FBC 1207.2,
 1207.3, AND 603.1. THIS MAY BE A DEFERRED SUBMITTAL. IF
 DEFERRED, THE TEST REPORTS ARE TO BE SUBMITTED AS A
 REVISION PRIOR TO INSTALLATION. AS STRUCTURAL PLANS
 SHOW AN 8 INCH SLAB, PRODUCTS TESTED WITH EITHER A 6
 INCH OR AN 8 INCH SLAB ARE ACCEPTABLE.
  
 A. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR
 BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90.
 THE TEST REPORT CANNOT INCLUDE A DROPPED GYPSUM
 CEILING. PROVIDE A COPY OF THE TEST REPORT.
  
 B. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN
 DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC
 OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN
 IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN
 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH
 ASTM E 492. THE TEST REPORT CANNOT INCLUDE A DROPPED
 GYPSUM CEILING. PROVIDE A COPY OF THE TEST REPORT.
  
 C. FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE
 BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE
 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84
 OR UL 723.
  
 51. SMOKE CONTROL REFERENCED, BUT REPORT NOT PROVIDED,
 FBC 909.4.
  
 52. A SPOT CHECK ON THE ENERGY CALCS WAS DONE. PLEASE
 CLARIFY THE FOLLOWING:
 EXTERNAL LIGHTING SHOWS NO ENTRY.
  
 53. THIS PERMIT WILL BE ISSUED WITH THE FOLLOWING
 PROVISOS:
  
 A. PROVISO: TCO AT EACH PHASE IS SUBJECT TO APPROVAL OF
 THE BUILDING OFFICIAL (OR HIS REPRESENTATIVE) AND FIRE
 DEPARTMENT, AND MAY INCLUDE ITEMS NOT WITHIN THE SCOPE
 OF THIS REVIEW. A TCO REQUEST FORM AND FEE WILL BE
 REQUIRED. THIS FORM IS AVAILABLE UPON REQUEST BY EMAIL.
  
 C. SEPARATE PERMITS (APPLICATION, PLANS, REVIEWS, AND
 FEES) REQUIRED FOR ALL ITEMS OTHER THAN MECHANICAL,
 ELECTRICAL, AND PLUMBING FOR THE BUILDING AS SHOWN ON
 THE PLANS. THIS INCLUDES SIGNS, FIRE ALARM, FIRE
 SPRINKLERS, LANDSCAPING.
  
 SUB PERMITS (APPLICATION, SUB PERMIT FEE) ARE REQUIRED
 FOR MECHANICAL, ELECTRICAL, AND PLUMBING PRIOR TO
 COMMENCEMENT OF WORK.
  
 A ROOFING SUB PERMIT IS REQUIRED PRIOR TO COMMENCEMENT
 OF ROOFING WORK. AS ROOF DOCUMENTS HAVE NOT BEEN
 PROVIDED, THIS IS A DEFERRED SUBMITTAL. PRODUCT
 APPROVALS REVIEWED BY DESIGNER OF RECORD, SELECTED
 ASSEMBLY, ENGINEERING IF APPLICABLE ARE TO BE SUBMITTED
 AS A REVISION WITH A ROOF PERMIT APPLICATION.
  
 D. COMPONENTS AND CLADDING PRODUCT APPROVALS ARE TO BE
 REVIEWED BY DESIGNER OF RECORD AND SUBMITTED AS A
 REVISION PRIOR TO INSTALLATION.
  
 E. PROVISO, THIS STUCTURE SERVES A BUILDING WHICH HAS
 NOT BEEN REVIEWED BY THIS DEPARTMENT (TRAIN STATION).
 ACCESSIBLE ROUTE IN COMPLIANCE WITH FBC 5TH EDITION
 ACCESSIBILITY IS REQUIRED AND WILL BE VERIFIED IN THE
 FIELD.
  
  