2016-09-15 18:01:36 | ****CORRECTIONS**** |
| |
| SAMANTHA HILL |
| BUILDING PLANS EXAMINER |
| [email protected] |
| 561-805-6724 |
| |
| 1. UPDATE PLANS WITH THE CHANGES MADE TO PERMIT |
| 16040755, STRUCTURE PERMIT. SOME OF THE COMMENTS IN |
| THIS LIST HAVE ALREADY BEEN CORRECTED IN THE STRUCTURE |
| PERMIT AND HAVE BEEN FOUND CODE COMPLIANT. |
| |
| 2. FOR C.O. INFORMATION, PROVIDE THE FOLLOWING: |
| TOTAL NUMBER OF BEDROOMS |
| TOTAL NUMBER OF BATHROOMS |
| TOTAL NUMBER OF ROOMS |
| |
| 3. FBC TABLE 705.8. SHEET A100 SHOWS THE NORTH |
| ELEVATION (PARTIAL) AS 12FT 1IN FROM THE BUILDING TO |
| THE CENTER LINE OF THE ALLEY; SHEET A200 INCLUDES THE |
| LIMITATION OF 45 PERCENT UNPROTECTED OPENINGS ALLOWED. |
| REVISE THE PLAN TO INCLUDE THE PERCENTAGE OF |
| UNPROTECTED OPENINGS FOR THIS BUILDING, NORTH |
| ELEVATION. |
| |
| 4. A100 SITE PLAN SHOWS THE APPROX CENTER OF ALLEY. |
| REVISE TO INCLUDE EXACT DIMENSION BASED ON THE SURVEY |
| OR PLAT SO COMPLIANCE WITH FBC TABLE 602, 705.8 CAN BE |
| DETERMINED. |
| |
| 5. FBC TABLE 602, BASED ON FIRE SEPARATION DISTANCE |
| (CHAPTER 2), THE NORTH WALL REQUIRES A 1 HOUR RATING. |
| A. REVISE TO INCLUDE ON SHEET A201 AND ALL OTHER SHEETS |
| AFFECTED OR REVISE SITE PLAN ON A100 TO CLARIFY FIRE |
| SEPARATION DISTANCE. |
| B. REVISE DOOR SCHEDULE TO COMPLY WITH FBC TABLE 716.5 |
| FOR AFFECTED DOORS. |
| |
| 6. FBC TABLES 601, 602, PROVIDE DETAILS FOR THE FIRE |
| RATED ELEMENTS, INCLUDING THE NORTH WALL WHICH HAS A |
| FIRE SEPARATION DISTANCE LESS THAN 30FT, FBC 703, 704. |
| |
| 7. A200, STRUCTURAL FIRE RESISTANCE RATING |
| REQUIREMENTS, REVISE STRUCTURE AND ROOF REQUIREMENTS TO |
| BE CONSISTENT WITH TABLE 601 OR REVISE PLAN TO INCLUDE |
| APPLICABLE EXCEPTION. |
| |
| 8. A200, STRUCTURAL FIRE RESISTANCE RATING |
| REQUIREMENTS, A TABLE FROM THE FBC WAS INCLUDED BUT |
| DOES NOT INDICATE HOW THE TABLE APPLIES TO THIS |
| PROJECT. REVISE TO INCLUDE THE WALLS AFFECTED, FBC |
| TABLE 602, FBC 107. |
| |
| 9. FBC 403.5.3 AND 403.5.3(1), REVISE PLAN TO CLARIFY |
| PROPOSED EXIT STAIR DOOR OPERATION (OR ADVISE WHERE |
| THIS INFORMATION CAN BE FOUND). |
| |
| 10. A200 SPECIFIES BOTH OCCUPANCY SEPARATION AND NON |
| SEPARATED OCCUPANCIES. REVISE PLAN TO CLARIFY WHICH OF |
| THE TWO METHODS IS PROPOSED, FBC 508. THIS INFORMATION |
| IS ALSO REQUIRED FOR THE TENANT BUILD OUTS, FBC 107. |
| |
| 11. A200 OCCUPANCY SEPARATION REFERS TO ASSEMBLY WITHIN |
| EDUCATIONAL OCCUPANCIES (NOTE 1), REMOVE THIS AND OTHER |
| NOTES WHICH DO NOT APPLY TO THIS PROJECT, OR CLARIFY |
| WHERE THIS IS OR MAY BE APPLICABLE. |
| |
| 12. A200 OCCUPANCY CLASSIFICATION INCLUDES A1 THEATER; |
| ADVISE WHERE THIS CAN BE LOCATED, OR IS THIS A FUTURE |
| IMPROVEMENT? FBC 107. REMOVE IF NOT APPLICABLE. |
| |
| 13. A200 AND OTHER PAGES, FIRE RESISTANCE REQUIREMENTS |
| WALLS, ITEM C, IS NOT CLEAR WHERE THIS IS APPLICABLE. |
| REVISE TO REFLECT THE REQUIREMENT FOR THIS PROJECT. IT |
| WOULD BE HELPFUL IF THE ACTUAL FIRE RATING REQUIREMENTS |
| SPECIFIC TO THIS PROJECT WERE INCORPORATED INTO THIS |
| TABLE (SUGGESTED, NOT REQUIRED). |
| |
| 14. SPECIFY ACCESSIBLE MEANS OF EGRESS SELECTED, FBC |
| BUILDING 1007, FBC ACCESSIBILITY 207. REVISE PLAN TO |
| SHOW COMPLIANCE WITH METHOD SELECTED IF ALL ITEMS ARE |
| NOT IMMEDIATELY APPARENT (FOR EXAMPLE, IBC2000 ELEVATOR |
| AS MEANS OF EGRESS COMPONENT). |
| |
| 15. A200 REGARDING SIGNAGE ITEM 2; CLARIFY ACCESSIBLE |
| MEANS OF EGRESS SELECTED AND REVISE NOTE IF APPLICABLE. |
| |
| 16. A200, SIGNAGE NOTE 3, THE LANGUAGE, LOCATION AND |
| CODE REFERENCE ARE NOT CONSISTENT WITH FBC 703.7; |
| REVISE OR CLARIFY. VERIFY THAT ALL NOTES HAVE |
| SPECIFICATIONS AND CODE REFERENCES CONSISTENT WITH FBC |
| 2014, FBC 107. IT APPEARS THAT SEVERAL REFERENCES ARE |
| FROM A PREVIOUS CODE VERSION. |
| |
| 17. A200 FIRE EXTINGUISHER NOTES DO NOT REFERENCE FBC |
| 906, REVISE. |
| |
| 18. A200 INCIDENTAL USE AREAS AND NON PROTECTED SHAFT |
| DO NOT APPEAR TO BE APPLICABLE. EITHER REMOVE OR REVISE |
| TO CLARIFY LOCATIONS PROPOSED, FBC 107. |
| |
| 19. FOR C.O., AN ACCURATE OCCUPANT LOAD FOR THE |
| BUILDING IS REQUIRED. SEE A202; GARAGE OCC LOAD IN THE |
| CHART IS NOT CONSISTENT WITH THE GARAGE OCC LOAD ON THE |
| PLAN. THE TOTAL OCCUPANTS PER LEVEL AND OCCUPANT LOAD |
| CATEGORY ARE LACKING SEVERAL FLOORS (15 TO 23), |
| PLEASE CORRELATE AND UPDATE TO REFLECT CORRECTED |
| OCCUPANT LOAD ON THE POOL DECK AND ANY OTHER CHANGES. |
| |
| 20. FBC 406.4, CLASSIFY THE PARKING GARAGE AS EITHER |
| ENCLOSED OR OPEN. IT IS SUGGESTED THAT THIS BE |
| INCORPORATED WITH THE BUILDING GENERAL DATA A201. IF |
| OPEN, PROVIDE PERCENTAGE OF OPENINGS PROVIDED TO SHOW |
| COMPLIANCE WITH FBC 406.5. IF ENCLOSED, PROVIDE |
| VENTILATION 406.6.2. |
| |
| 21. A202, LIFE SAFETY TCO NOTES INCLUDES FOUR TCO |
| PHASES; PLAN SHOWS TWO, PLEASE CORRELATE. |
| |
| 22. A202, THE LIFE SAFETY PLAN LACKS STAIR NUMBER |
| DESIGNATIONS. PROVIDE IN ORDER TO CORRELATE WITH |
| DETAILS ON A701-A712, FBC 107. CHECK ALL SHEETS. |
| |
| 23. IT IS NOT CLEAR WHERE THE EXIT DISCHARGE IS LOCATED |
| FOR STAIR LOCATED AT GRIDLINES H3 SHEET A202, FBC 107. |
| (ITEM ADDRESSED IN STRUCTURE PERMIT, PLEASE UPDATE.) |
| |
| 24. AS301 LEVEL 1, THE ACCESSIBLE ROUTE FOR THE |
| ACCESSIBLE VAN PARKING SPACE IS NOT CLEAR; THIS WAS |
| ADDRESSED IN STRUCTURE PERMIT, PLEASE UPDATE PLANS. |
| |
| 25. AVIS, LEASING OFFICE, RETAIL/RESTAURANT, AND |
| PASSENGER PARKING MINIMUM REQUIREMENTS ARE COVERED BY |
| FBC 5TH EDITION ACCESSIBILITY 208, RESIDENTIAL PARKING |
| MINIMUM REQUIREMENTS DETERMINED BY FBC 5TH EDITION |
| ACCESSIBILITY FAIR HOUSING. |
| |
| A100, PARKING SCHEDULE, AND OTHER PAGES, REVISE TO SHOW |
| COMPLIANCE WITH THE FOLLOWING ITEMS: |
| |
| THE OPERATION OF THE AVIS BUSINESS AND SPACES IS NOT |
| CLEAR. REVISE THE PLAN TO CLARIFY HOW THIS BUSINESS |
| WILL OPERATE. WILL CUSTOMERS PICK UP THE CARS, OR WILL |
| THE CAR BE BROUGHT TO THE CUSTOMER? IT APPEARS THAT AN |
| ACCESSIBLE AVIS SPACE OR A PASSENGER LOADING ZONE MAY |
| BE REQUIRED. REVISE PLAN TO DEMONSTRATE COMPLIANCE (OR |
| EXEMPTION), INCLUDING APPLICABLE DETAILS. IF THE |
| PARKING SPACES ARE FOR AUTO STORAGE ONLY, REVISE PLAN |
| TO INCLUDE THIS INFORMATION AS WELL AS DETAILS FOR THE |
| PASSENGER LOADING ZONE (FBC ACCESSIBILITY 208.1, 503), |
| OR REVISE PLAN TO INCORPORATE INFORMATION REGARDING |
| FUNCTION OF THE AUTO RENTAL AREA AND HOW THIS AREA |
| COMPLIES WITH (OR IS EXEMPT FROM) ACCESSIBILITY. |
| |
| 26. FBC ACCESSIBILITY 208, PARKING FOR THE RETAIL AND |
| RESTAURANT AREAS IS NOT CLEAR. REVISE PLAN TO INDICATE |
| NUMBER OF SPACES, ACCESSIBLE SPACES, VAN SPACES, AND |
| LOCATION OR NOTE IF NONE OF THE PARKING SPACES IN THIS |
| STRUCTURE ARE FOR THE RETAIL/RESTAURANT AREAS. |
| |
| 27. SEE PLUMBING COMMENTS REGARDING ACCESSIBILITY AND |
| REVISE PLAN TO SHOW COMPLIANCE. |
| |
| 28. A212, CLARIFY USE OF THE AMENITIES ROOM, FBC 107. |
| |
| 29. LEASING OFFICE PARKING PROVIDED IS NOT CLEAR. |
| REVISE PLAN TO DESIGNATE NUMBER OF PARKING SPACES |
| DEDICATED TO LEASING, ACCESSIBLE AND VAN SPACES (NUMBER |
| AND LOCATIONS), FBC ACCESSIBILITY 208. IT MAY BE |
| HELPFUL TO DESIGNATE WHICH FLOORS OR AREAS ARE FOR |
| RESIDENTS, RETAIL VISITORS, AND TRANSIT. |
| |
| 30. ONE GUEST SPACE IS SHOWN ON THE PARKING SCHEDULE. |
| REVISE TO DESIGNATE WHETHER THIS IS FOR PASSENGER, |
| LEASING, RETAIL OR RESIDENT PARKING AND NOTE LOCATION |
| ON PLAN, FBC ACCESSIBILITY 208. |
| |
| 31. A212, POOL DECK OCCUPANT LOAD SHOULD BE CALCULATED |
| AT 15SF GROSS PER PERSON, PLEASE REVISE TABLES AND |
| OCCUPANT LOAD FOR THE POOL DECK. IT DOES NOT APPEAR |
| THAT EXITING IS ADEQUATE FOR THIS ASSEMBLY AREA; FBC |
| 5TH EDITION TABLE 1004.1.2. THIS ITEM WAS ADDRESSED IN |
| THE STRUCTURE PERMIT; PLEASE REVISE TO BE CONSISTENT |
| WITH 16040755. |
| 32. REVISE PLAN TO SHOW THE 18IN MANEUVERING CLEARANCE, |
| PULL SIDE (FBC ACCESSIBILITY 404.2.4), DOOR LOCATED ON |
| SHEET A301, DOOR R03H (FBC 5TH ED. ACCESSIBILITY |
| 206.4.5), OR OTHERWISE INDICATE THAT THIS WILL NOT BE |
| THE ONLY DOOR SERVING A TENANT SPACE, OR PROVIDE AN |
| OPENER. |
| |
| 33. SHEET AS212A, DOORS TO LOBBY FROM POOL AREA SWING |
| AGAINST PATH OF TRAVEL, FBC 1008.1.2. |
| |
| 34. ADVISORY; SHEET AS203, THE SOUTH ACCESSIBLE PARKING |
| SPACE (GRIDLINE G4) REQUIRES THE OCCUPANT TO TRAVEL |
| BEHIND THE VAN PARKING SPACE TO ACCESS THE LOBBY, AVIS, |
| AND RESIDENTIAL LOBBY. THIS WILL BE REQUIRED TO BE |
| CORRECTED ON THE BUILDING PERMIT. |
| |
| 35. FBC 505, LEVEL 12.5 IS NOT SHOWN AS A STORY ON THE |
| BUILDING DATA. EITHER REVISE PLAN TO SHOW COMPLIANCE |
| WITH REQUIREMENTS FOR MEZZANINES, OR REVISE BUILDING |
| DATA INFORMATION. |
| |
| 36. COMPLIANCE WITH FBC 5TH EDITION ACCESSIBILITY, FAIR |
| HOUSING IS NOT CLEAR. IF DESIGNING USING THE FAIR |
| HOUSING ACT DESIGN MANUAL, PROVIDE UNIT LAYOUTS WITH |
| UNIT TYPE AND DIMENSIONS SHOWING COMPLIANCE. |
| |
| IF USING ANOTHER METHOD, PROVIDE DETAILS AND DIMENSIONS |
| TO SHOW COMPLIANCE. |
| |
| 37. F202 AND E202 SHOW A MEZZANINE, PROVIDE AN |
| ARCHITECTURAL FLOOR PLAN; LOCATION IS NOT CLEAR, AND IS |
| THIS A MEZZANINE PER FBC505? INCLUDE ALL INFORMATION |
| REQUIRED TO DETERMINE CODE COMPLIANCE FOR THIS AREA, |
| FBC 107. IF THIS IS NOT A MEZZANINE, IT IS SUGGESTED |
| THAT THE NAME OF THE AREA BE REVISED FOR CLARITY. |
| |
| 38. UNIT NAMES ON LIFE SAFETY SHEETS ARE NOT THE SAME |
| AS FLOOR PLANS (FOR INSTANCE, SEE A202 AND A302), |
| CORRELATE. |
| |
| 39. A FIRE ALARM SYSTEM IN COMPLIANCE WITH FBC |
| 907.2.13.1 IS REQUIRED PER FBC 403.4.2. SMOKE DETECTORS |
| IN COMPLIANCE WITH FBC 907.2.13.1 IS REQUIRED PER FBC |
| 403.4.1. REVISE PLAN TO INCLUDE NOTES, OR ADVISE WHERE |
| COMPLIANCE WITH THESE STANDARDS CAN BE LOCATED ON THE |
| PLAN. BOTH ITEMS REQUIRE SEPARATE APPLICATIONS, |
| PERMITS, PLANS AND FEES, FBC 107, AND WILL BE REVIEWED |
| AT THAT TIME. |
| |
| 40. FBC 403.4.5, EMERGENCY RESPONDER RADIO COVERAGE, |
| REVISE PLAN TO INCLUDE A NOTE TO SHOW COMPLIANCE WITH |
| THIS SECTION. |
| |
| NFPA 1, CHAPTER 11, BUILDING SERVICES; 11.10 TWO-WAY |
| RADIO ENHANCEMENT SERVICES. |
| 11.10.1 IN ALL NEW AND EXISTING BUILDINGS, MINIMUM |
| RADIO SIGNAL STRENGTH FOR FIRE DEPARTMENT |
| COMMUNICATIONS SHALL BE MAINTAINED AT A LEVEL |
| DETERMINED BY THE AHJ. |
| MAINTAIN A MINIMUM RADIO SIGNAL STRENGTH OF 102.0 DBM |
| FOR THE RADIO SYSTEM USED BY WEST PALM BEACH FIRE |
| RESCUE. IF THE MINIMUM CANNOT BE MAINTAINED, A |
| BI-DIRECTIONAL AMPLIFIED SYSTEM SHALL BE INSTALLED WITH |
| A MINIMUM 2-HOUR RUN TIME BATTERY BACK-UP. |
| |
| 41. STANDBY POWER, FBC 403.4.8, EMERGENCY POWER 403.4.9 |
| REQUIRED. REVISE PLAN TO SHOW COMPLIANCE OR ADVISE AS |
| TO WHERE THIS CAN BE LOCATED. CLARIFY WHICH ITEMS WILL |
| BE ON EMERGENCY POWER. WHICH ELEVATOR(S) WILL BE |
| INCLUDED (FBC 1007)? |
| |
| 42. FBC 403.5.4 SMOKEPROOF EXIT, THE NEW STAIR (5?) |
| DOES NOT APPEAR ON THE MECHANICAL SHEETS (MEZZANINE |
| LEVEL AS SHOWN ON FIRE AND ELEC PAGES, M704, OTHER |
| PAGES). |
| |
| 43. FBC 905.4, STANDPIPE REQUIRED IN STAIRS, UNABLE TO |
| LOCATE THIS FOR THE NEW STAIR. |
| |
| 44. FBC 403.6.1, COMPLIANCE WITH FIRE SERVICE ACCESS |
| ELEVATOR REQUIREMENTS IS NOT CLEAR. SHEET A202 (AND |
| OTHER LIFE SAFETY SHEETS) SHOW A FIRE SERVICE LOBBY ON |
| THE WEST SIDE WHICH IS NOT INCLUDED IN TCO AREA 1. ALL |
| LIFE SAFETY SYSTEMS ARE TO BE IN PLACE FOR TCO. |
| |
| THE ELEVATORS DESIGNATED AS FIRE SERVICE IS NOT CLEAR. |
| FOR INSTANCE, SEE LEVEL 8. IT APPEARS THAT ONLY THE |
| NORTH ELEVATOR, WEST SIDE IS DESIGNATED AS THE FIRE |
| SERVICE ELEVATOR, BUT AT LEAST TWO ARE REQUIRED PER FBC |
| 403.6.1. |
| REVISE PLAN TO SHOW COMPLIANCE WITH THE FIRE SERVICE |
| ELEVATORS REQUIREMENT, INCLUDING THE WEIGHT CAPACITY |
| REQUIREMENT. FIRE SERVICE ELEVATORS ARE TO COMPLY WITH |
| FBC 3007. REVISE PLAN TO SHOW COMPLIANCE WITH 3007.2 |
| RECALL, 3007.7.5 SIGNAGE, 3007.3 SPRINKLERS, 3007.4 |
| WATER PROTECTION, 3007.6.1, 3007.6.2 HOISTWAY LIGHTING, |
| 3007.7.2 1 HOUR SMOKE BARRIER FOR LOBBY, 3007.7.3 LOBBY |
| DOORS, 3007.8 MONITORING, 3007.9 ELECTRICAL POWER, |
| 3007.9.1 PROTECTION OF WIRING AND CABLES. |
| |
| 45. SOME LEVELS (FOR INSTANCE, LEVELS 12.5, 13) LACK A |
| FIRE SERVICE ELEVATOR FBC 403. |
| |
| 46. FBC 3004, HOISTWAY VENTING NOT CLEAR, REVISE PLAN |
| TO SHOW COMPLIANCE. |
| |
| 47. FBC 3002.4, SHOW LOCATION OF STRETCHER ELEVATOR |
| SIGNAGE. |
| |
| 48. FBC 908.7, CARBON MONOXIDE DETECTORS ARE REQUIRED, |
| REVISE. |
| |
| 49. PRODUCT APPROVALS FOR COMPONENTS AND CLADDING HAVE |
| NOT BEEN SUBMITTED. THEY MAY BE A DEFERRED SUBMITTAL. |
| THEY MAY BE SUBMITTED, PRIOR TO INSTALLATION, AS A |
| REVISION, PRIOR TO INSTALLATION. |
| |
| 50. FLOORING UNDERLAYMENT IS TO COMPLY WITH FBC 1207.2, |
| 1207.3, AND 603.1. THIS MAY BE A DEFERRED SUBMITTAL. IF |
| DEFERRED, THE TEST REPORTS ARE TO BE SUBMITTED AS A |
| REVISION PRIOR TO INSTALLATION. AS STRUCTURAL PLANS |
| SHOW AN 8 INCH SLAB, PRODUCTS TESTED WITH EITHER A 6 |
| INCH OR AN 8 INCH SLAB ARE ACCEPTABLE. |
| |
| A. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING |
| DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR |
| SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS |
| (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR |
| BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90. |
| THE TEST REPORT CANNOT INCLUDE A DROPPED GYPSUM |
| CEILING. PROVIDE A COPY OF THE TEST REPORT. |
| |
| B. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN |
| DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC |
| OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN |
| IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN |
| 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH |
| ASTM E 492. THE TEST REPORT CANNOT INCLUDE A DROPPED |
| GYPSUM CEILING. PROVIDE A COPY OF THE TEST REPORT. |
| |
| C. FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE |
| BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL |
| INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID |
| DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED |
| TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE |
| 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84 |
| OR UL 723. |
| |
| 51. SMOKE CONTROL REFERENCED, BUT REPORT NOT PROVIDED, |
| FBC 909.4. |
| |
| 52. A SPOT CHECK ON THE ENERGY CALCS WAS DONE. PLEASE |
| CLARIFY THE FOLLOWING: |
| EXTERNAL LIGHTING SHOWS NO ENTRY. |
| |
| 53. THIS PERMIT WILL BE ISSUED WITH THE FOLLOWING |
| PROVISOS: |
| |
| A. PROVISO: TCO AT EACH PHASE IS SUBJECT TO APPROVAL OF |
| THE BUILDING OFFICIAL (OR HIS REPRESENTATIVE) AND FIRE |
| DEPARTMENT, AND MAY INCLUDE ITEMS NOT WITHIN THE SCOPE |
| OF THIS REVIEW. A TCO REQUEST FORM AND FEE WILL BE |
| REQUIRED. THIS FORM IS AVAILABLE UPON REQUEST BY EMAIL. |
| |
| C. SEPARATE PERMITS (APPLICATION, PLANS, REVIEWS, AND |
| FEES) REQUIRED FOR ALL ITEMS OTHER THAN MECHANICAL, |
| ELECTRICAL, AND PLUMBING FOR THE BUILDING AS SHOWN ON |
| THE PLANS. THIS INCLUDES SIGNS, FIRE ALARM, FIRE |
| SPRINKLERS, LANDSCAPING. |
| |
| SUB PERMITS (APPLICATION, SUB PERMIT FEE) ARE REQUIRED |
| FOR MECHANICAL, ELECTRICAL, AND PLUMBING PRIOR TO |
| COMMENCEMENT OF WORK. |
| |
| A ROOFING SUB PERMIT IS REQUIRED PRIOR TO COMMENCEMENT |
| OF ROOFING WORK. AS ROOF DOCUMENTS HAVE NOT BEEN |
| PROVIDED, THIS IS A DEFERRED SUBMITTAL. PRODUCT |
| APPROVALS REVIEWED BY DESIGNER OF RECORD, SELECTED |
| ASSEMBLY, ENGINEERING IF APPLICABLE ARE TO BE SUBMITTED |
| AS A REVISION WITH A ROOF PERMIT APPLICATION. |
| |
| D. COMPONENTS AND CLADDING PRODUCT APPROVALS ARE TO BE |
| REVIEWED BY DESIGNER OF RECORD AND SUBMITTED AS A |
| REVISION PRIOR TO INSTALLATION. |
| |
| E. PROVISO, THIS STUCTURE SERVES A BUILDING WHICH HAS |
| NOT BEEN REVIEWED BY THIS DEPARTMENT (TRAIN STATION). |
| ACCESSIBLE ROUTE IN COMPLIANCE WITH FBC 5TH EDITION |
| ACCESSIBILITY IS REQUIRED AND WILL BE VERIFIED IN THE |
| FIELD. |
| |
| |