2016-07-22 05:47:471) INDICATE ON THE PLANS WHICH SIZING TABLE FROM THE
 2014 FUEL GAS CODE IS BEING USED FOR THE SIZING OF THIS
 SYSTEM.
 2) IF TABLE 402.4 (21) IS BEING USED, SECTIONS OF THIS
 SYSTEM ARE UNDERSIZED.
 3) SHOW THE PIPE SIZE FOR THE LINE SUPPLYING THE BBQ &
 THE POOL HEATER.
 NOTE: COULD NOT DO A COMPLETE REVIEW DUE TO LACK OF
 INFO ON PLANS.
  