Plan Review Notes For Permit 16070710 |
Permit Number |
16070710 |
|
Review Stop |
G |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2016-07-22 05:47:47 | 1) INDICATE ON THE PLANS WHICH SIZING TABLE FROM THE | | 2014 FUEL GAS CODE IS BEING USED FOR THE SIZING OF THIS | | SYSTEM. | | 2) IF TABLE 402.4 (21) IS BEING USED, SECTIONS OF THIS | | SYSTEM ARE UNDERSIZED. | | 3) SHOW THE PIPE SIZE FOR THE LINE SUPPLYING THE BBQ & | | THE POOL HEATER. | | NOTE: COULD NOT DO A COMPLETE REVIEW DUE TO LACK OF | | INFO ON PLANS. | | | | PLUMBING PLAN REVIEW | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | 561-805-6692 | | [email protected] | | |
|