Plan Review Notes
Plan Review Notes For Permit 16070697
Permit Number 16070697
Review Stop FIRE
Sequence Number 3
Notes
Date Text
2016-09-09 11:01:57217 BUTLER STREET
 PERMIT #16070697
 REVIEW COMMENTS - FIRE DEPARTMENT
 3RD REVIEW
  
 ***A FIRE ALARM PERMIT WILL NOT BE ISSUED UNTIL A
 MASTER BUILDING PERMIT IS APPLIED FOR INDICATING A
 CHANGE OF USE FROM APARTMENTS TO A PLACE OF
 REHABILITATION***
  
 THE ORIGINAL PLANS SUBMITTED ON 07/19/16 ARE COMPLETELY
 DIFFERENT FROM THE PLANS SUBMITTED FOR THIS REVIEW ON
 09/07/16. WHICH FLOOR PLANS ARE ACCURATE? HAS THIS BEEN
 FIELD VERIFIED?
  
 THE ENGINEER'S SIGN/SEAL IS A PHOTO COPY OR PRINTED
 VERSION.
  
 THE ORIGINAL PLANS SHOWED A SCOPE OF WORK FOR
 INSTALLING 3 NOTIFICATION DEVICES AND 3 INITIATING
 DEVICES; HOWEVER, THE LATEST PLANS INDICATE 16
 NOTIFICATION APPLIANCES, AND 28 INITIAING DEVICES. THE
 ORIGINAL JOB VALUE OF $2400 NEEDS TO BE INCREASED TO
 MATCH THE SCOPE OF WORK.
  
 ALL DEVICES ARE MISSING AN ADDRESS PER THE FLORIDA
 ADMINISTRATIVE CODE.
  
 THE PLANS DO NOT SHOW WEATHERPROOF DEVICES FOR THE
 EXTERIOR INSTALLATION.
  
 THE SLEEPING AREA SMOKE ALARMS SHALL NOT BE TIED INTO
 THE BUILDING FIRE ALARM SYSTEM.
  
 THE CITY OF WEST PALM BEACH DOES NOT ALLOW NEW FIRE
 ALARM SYSTEMS TO BE TIED INTO THE BUILDING SECURITY
 SYSTEM. A CERTIFICATE OF COMPLETION AND A THIRD PARTY
 MONITORING/VERIFICATION (UL OR ETL) CERTIFICATE PER
 NFPA 72 SHALL BE PROVIDED AT TIME OF FINAL FIRE ALARM
 INSPECTION.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
  