Plan Review Notes For Permit 16070697 |
Permit Number |
16070697 |
|
Review Stop |
FIRE |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2016-09-09 11:01:57 | 217 BUTLER STREET | | PERMIT #16070697 | | REVIEW COMMENTS - FIRE DEPARTMENT | | 3RD REVIEW | | | | ***A FIRE ALARM PERMIT WILL NOT BE ISSUED UNTIL A | | MASTER BUILDING PERMIT IS APPLIED FOR INDICATING A | | CHANGE OF USE FROM APARTMENTS TO A PLACE OF | | REHABILITATION*** | | | | THE ORIGINAL PLANS SUBMITTED ON 07/19/16 ARE COMPLETELY | | DIFFERENT FROM THE PLANS SUBMITTED FOR THIS REVIEW ON | | 09/07/16. WHICH FLOOR PLANS ARE ACCURATE? HAS THIS BEEN | | FIELD VERIFIED? | | | | THE ENGINEER'S SIGN/SEAL IS A PHOTO COPY OR PRINTED | | VERSION. | | | | THE ORIGINAL PLANS SHOWED A SCOPE OF WORK FOR | | INSTALLING 3 NOTIFICATION DEVICES AND 3 INITIATING | | DEVICES; HOWEVER, THE LATEST PLANS INDICATE 16 | | NOTIFICATION APPLIANCES, AND 28 INITIAING DEVICES. THE | | ORIGINAL JOB VALUE OF $2400 NEEDS TO BE INCREASED TO | | MATCH THE SCOPE OF WORK. | | | | ALL DEVICES ARE MISSING AN ADDRESS PER THE FLORIDA | | ADMINISTRATIVE CODE. | | | | THE PLANS DO NOT SHOW WEATHERPROOF DEVICES FOR THE | | EXTERIOR INSTALLATION. | | | | THE SLEEPING AREA SMOKE ALARMS SHALL NOT BE TIED INTO | | THE BUILDING FIRE ALARM SYSTEM. | | | | THE CITY OF WEST PALM BEACH DOES NOT ALLOW NEW FIRE | | ALARM SYSTEMS TO BE TIED INTO THE BUILDING SECURITY | | SYSTEM. A CERTIFICATE OF COMPLETION AND A THIRD PARTY | | MONITORING/VERIFICATION (UL OR ETL) CERTIFICATE PER | | NFPA 72 SHALL BE PROVIDED AT TIME OF FINAL FIRE ALARM | | INSPECTION. | | | | WESLEY JOLIN | | ASSISTANT FIRE MARSHAL | | WEST PALM BEACH FIRE RESCUE | | [email protected] | | |
|