2016-09-13 08:17:11 | 3RD ELECTRICAL REVIEW NOTES, |
| REVIEWED FOR COMPLIANCE WITH: |
| 5TH EDITION FBC 2014 & NFPA 70 2011 (NEC) |
| |
| JOB DESCRIPTION: FIRE ALARM PER PLANS |
| |
| BELOW PLEASE FIND A LIST OF REQUIRED CORRECTIONS. |
| ADDITIONAL CORRECTIONS MAY BE REQUIRED AFTER REVIEW OF |
| SUBMITTED CORRECTIONS. |
| |
| 1. AS INDICATED IN THE PREVIOUS REVIEW, THE OCCUPANCY |
| CLASSIFICATION FOR THIS PROPOSED WILL FALL UNDER I1 AND |
| THUS THE FIRE ALARM INSTALLED ON SITE SHALL BE IN |
| ACCORDANCE WITH SAME. |
| 2. THIS FACILITY?S OCCUPANCY CLASSIFICATION IS OFFICE; |
| A CHANGE OF OCCUPANCY PERMIT SHALL BE SECURED PRIOR TO |
| PROCEEDING. |
| 3. ON NOV. 26TH OF 2013 A CHANGE OF OCCUPANCY PERMIT TO |
| CHANGE FROM OFFICE TO LIVING WAS APPLIED FOR BUT THE |
| PERMIT EXPIRED BEFORE IT WAS PICKED UP AND THEREFORE |
| THE PROCESS WAS NEVER COMPLETED. |
| 4. SECURE A CHANGE OF OCCUPANCY PERMIT BEFORE WE CAN |
| PROCEED WITH THIS PERMIT. |
| |
| WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR |
| RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER |
| (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER |
| WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD |
| CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID |
| AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR |
| COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE |
| GREATLY APPRECIATED. |
| |
| IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO |
| CONTACT ME DIRECTLY. |
| |
| THANK YOU, |
| MIKE ALBARRAN |
| ELECTRICAL PLANS EXAMINER |
| PH: 561-805-6746 |
| EMAIL: [email protected] |
| |