2016-08-10 10:11:02217 BUTLER STREET
 PERMIT #16070697
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 NEW COMMENT - THE CITY OF WEST PALM BEACH DOES NOT
 ALLOW NEW FIRE ALARM SYSTEMS TO BE TIED INTO THE
 BUILDING SECURITY SYSTEM.
  
 REPEAT COMMENT - NOTE: A CHANGE OF OCCUPANCY PERMIT IS
 NEEDED TO CONVERT THE BUILDING FROM APARTMENTS TO A
 PLACE OF REHABILITATION.
  
 REPEAT COMMENT - NO NOTIFICATION DEVICES INSTALLED IN
 BEDROOMS. HOW WILL 75 DB AT THE PILLOW BE OBTAINED?
  
 REPEAT COMMENT - NO NOTIFICATION DEVICES INSTALLED IN
 FIRST FLOOR COMMON KITCHEN, DINING, RESTROOMS, LAUNDRY
 AND SECOND FLOOR LARGE OFFICE AREA.
  
 NO BATTERY CALCULATIONS OR VOLTAGE DROP CALCULATIONS
 SUBMITTED.
  
 REPEAT COMMENT - A CERTIFICATE OF COMPLETION AND A
 THIRD PARTY MONITORING/VERIFICATION (UL OR ETL)
 CERTIFICATE SHALL BE PROVIDED AT TIME OF FINAL FIRE
 ALARM INSPECTION.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
  