Date |
Text |
2016-08-11 10:05:21 | ELECTRICAL REVIEW NOTES |
| REVIEWED FOR COMPLIANCE WITH: |
| 5TH EDITION FBC 2014 & NFPA 70 2011 (NEC) |
| |
| PROJECT NAME: REHAB HOUSE |
| JOB ADDRESS: 217 BUTLER ST. |
| DESCRIPTION: FIRE ALARM PER PLANS |
| MASTER PERMIT: 16070697 |
| REVISION: |
| |
| BELOW ARE COMMENTS RELATED TO THE FAILED ELECTRICAL |
| REVIEW: |
| |
| IN ADDITION TO THE FIRE REVIEWER?S COMMENTS, BELOW ARE |
| ADDITIONAL ELECTRICAL REVIEW COMMENTS. THE FIRE ALARM |
| SYSTEM AS DESIGNED DOES NOT MEET THE MINIMUM FIRE ALARM |
| SYSTEM FBC REQUIREMENTS AS INDICATED BELOW: |
| |
| 1. FBC-B 308.3: ACCORDING TO THIS CODE AND CONFIRMED BY |
| YOUR LETTER THE OCCUPANCY CLASSIFICATION OF THESE |
| PREMISES IS I1. |
| 2. FBC-B 907.2.6: THIS SECTION REQUIRES THAT A FIRE |
| ALARM SYSTEM IN ACCORDANCE WITH FBC-B 907.5 BE |
| INSTALLED. THIS FURTHER REQUIRES SMOKE DETECTOR |
| COMPLIANCE PER FBC-B 907.2.6.1, 907.2.6.2, 907.2.6.3.3. |
| 3. FBC-B 907.1.2: BELOW AS SPECIFIC SUBMITTAL |
| REQUIREMENTS MISSING FROM YOUR PLANS: |
| A) INDICATE THE USE OF THE ROOM BEHIND THE LAUNDRY ROOM |
| ON THE FIRST FLOOR, THE ROOM INSIDE OF THE KITCHENS OF |
| UNITS 3 & 6. PROVIDE A FLOOR PLAN FOR THE TWO |
| APARTMENTS SHOWN ON THE DETACHED STRUCTURE. SHOW THE |
| INTER-CONNECTION OF THE FIRE ALARM CONDUCTORS BETWEEN |
| BOTH BLDGS. |
| B) PER OCCUPANCY CLASSIFICATION REQUIREMENTS THERE ARE |
| ADDITIONAL INITIATION AND NOTIFICATION DEVICES MISSING |
| FROM THE SYSTEM AS DESIGNED. |
| C) SHOW THE LOCATION OF THE ELECTRICAL PANEL PROVIDING |
| THE ELECTRICAL POWER FOR THE FIRE ALARM SYSTEM. |
| D) PROVIDE VOLTAGE DROP CALCULATIONS. |
| |
| WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR |
| RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER |
| (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER |
| WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD |
| CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID |
| AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR |
| COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE |
| GREATLY APPRECIATED. |
| |
| IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO |
| CONTACT ME DIRECTLY. |
| THANK YOU, |
| MIKE ALBARRAN |
| ELECTRICAL PLANS EXAMINER |
| PH: 561-805-6746 |
| EMAIL: [email protected] |
| |