Plan Review Notes
Plan Review Notes For Permit 16070697
Permit Number 16070697
Review Stop E
Sequence Number 2
Notes
Date Text
2016-08-11 10:05:21ELECTRICAL REVIEW NOTES
 REVIEWED FOR COMPLIANCE WITH:
 5TH EDITION FBC 2014 & NFPA 70 2011 (NEC)
  
 PROJECT NAME: REHAB HOUSE
 JOB ADDRESS: 217 BUTLER ST.
 DESCRIPTION: FIRE ALARM PER PLANS
 MASTER PERMIT: 16070697
 REVISION:
  
 BELOW ARE COMMENTS RELATED TO THE FAILED ELECTRICAL
 REVIEW:
  
 IN ADDITION TO THE FIRE REVIEWER?S COMMENTS, BELOW ARE
 ADDITIONAL ELECTRICAL REVIEW COMMENTS. THE FIRE ALARM
 SYSTEM AS DESIGNED DOES NOT MEET THE MINIMUM FIRE ALARM
 SYSTEM FBC REQUIREMENTS AS INDICATED BELOW:
  
 1. FBC-B 308.3: ACCORDING TO THIS CODE AND CONFIRMED BY
 YOUR LETTER THE OCCUPANCY CLASSIFICATION OF THESE
 PREMISES IS I1.
 2. FBC-B 907.2.6: THIS SECTION REQUIRES THAT A FIRE
 ALARM SYSTEM IN ACCORDANCE WITH FBC-B 907.5 BE
 INSTALLED. THIS FURTHER REQUIRES SMOKE DETECTOR
 COMPLIANCE PER FBC-B 907.2.6.1, 907.2.6.2, 907.2.6.3.3.
 3. FBC-B 907.1.2: BELOW AS SPECIFIC SUBMITTAL
 REQUIREMENTS MISSING FROM YOUR PLANS:
 A) INDICATE THE USE OF THE ROOM BEHIND THE LAUNDRY ROOM
 ON THE FIRST FLOOR, THE ROOM INSIDE OF THE KITCHENS OF
 UNITS 3 & 6. PROVIDE A FLOOR PLAN FOR THE TWO
 APARTMENTS SHOWN ON THE DETACHED STRUCTURE. SHOW THE
 INTER-CONNECTION OF THE FIRE ALARM CONDUCTORS BETWEEN
 BOTH BLDGS.
 B) PER OCCUPANCY CLASSIFICATION REQUIREMENTS THERE ARE
 ADDITIONAL INITIATION AND NOTIFICATION DEVICES MISSING
 FROM THE SYSTEM AS DESIGNED.
 C) SHOW THE LOCATION OF THE ELECTRICAL PANEL PROVIDING
 THE ELECTRICAL POWER FOR THE FIRE ALARM SYSTEM.
 D) PROVIDE VOLTAGE DROP CALCULATIONS.
  
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER
 (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER
 WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD
 CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID
 AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR
 COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE
 GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
 THANK YOU,
 MIKE ALBARRAN
 ELECTRICAL PLANS EXAMINER
 PH: 561-805-6746
 EMAIL: [email protected]
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved