Plan Review Notes
Plan Review Notes For Permit 16070695
Permit Number 16070695
Review Stop E
Sequence Number 3
Notes
Date Text
2016-08-03 14:35:26REVIEW 2014 5TH FBC ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 561-805-6713
 [email protected]
  
  
 PASSED WITH THE FOLLOWING PROVISO ( RED LINED ON PLANS
 )
  
 1) NEC 210.63 HVAC EQUIPMENT SERVICE OUTLET. A 125
 VOLT, SINGLE-PHASE, 15 OR 20-AMPERE-RATED RECEPTACLE
 OUTLET SHALL BE INSTALLED AT AN ACCESSIBLE LOCATION FOR
 THE SERVICING OF HVAC EQUIPMENT. THE RECEPTACLE SHALL
 BE LOCATED WITHIN 25 FT. OF THE EQUIPMENT.