2016-07-25 15:04:48REVIEW 2014 5TH FBC ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 561-805-6713
 [email protected]
  
 - WEST PALM BEACH CITY AMENDMENTS REQUIRE PLANS TO BE
 SIGNED AND DATED BY DESIGN PROFFESIONAL RESPONSIBLE FOR
 THE DRAWINGS.
  
 - PLEASE IDENTIFY CIRCUITS FEEDING NEW EQUIPMENT ON THE
 FLOOR PLANS AND PROVIDE A PANEL SCHEDULE MATCHING IN
 ORDER TO VERIFY OCPD,CONDUCTOR, AND CONDUIT SIZES TO BE
 IN ACCORDANCE WITH NAME PLATE RATING. FBC 107 MINIMUM
 PLAN REVIEW.
  
 - NEC 210.63 HVAC EQUIPMENT SERVICE OUTLET. A 125 VOLT,
 SINGLE-PHASE, 15 OR 20-AMPERE-RATED RECEPTACLE OUTLET
 SHALL BE INSTALLED AT AN ACCESSIBLE LOCATION FOR THE
 SERVICING OF HVAC EQUIPMENT. THE RECEPTACLE SHALL BE
 LOCATED WITHIN 25 FT. OF THE EQUIPMENT.
 THE OUTDOOR RECEPTACLE OUTLET BY THE CONDENSING UNITS
 SHALL BE GFCI PROTECTED PER NEC 210.8(B)(4).
  
 - ELECTRICAL SUB PERMIT REQUIRED !