Plan Review Notes For Permit 16070634 |
Permit Number |
16070634 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2016-08-02 07:24:57 | 1ST REVIEW FBC-2014 MECHANICAL | | PERMIT #16070634 | | 8/2/2016 | | | | 1) SHEETS M2.1 & M6.1: LABEL THE DIFFUSERS AND GRILLS | | IN THE RESTROOMS. IT APPEARS THAT AIR FROM THE | | RESTROOMS IS BEING RECIRCULATED WHICH IS PROHIBITED PER | | TABLE 403.3 FOOTNOTE G- PLEASE CLARIFY. | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 561-805-6719 | | [email protected] | | |
|