2016-08-02 07:24:571ST REVIEW FBC-2014 MECHANICAL
 PERMIT #16070634
 8/2/2016
  
 1) SHEETS M2.1 & M6.1: LABEL THE DIFFUSERS AND GRILLS
 IN THE RESTROOMS. IT APPEARS THAT AIR FROM THE
 RESTROOMS IS BEING RECIRCULATED WHICH IS PROHIBITED PER
 TABLE 403.3 FOOTNOTE G- PLEASE CLARIFY.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  