2017-02-22 14:54:555TH REVIEW FBC-2014 MECHANICAL
 PERMIT #16070628
 2/22/17
  
 1) THE REAR EGRESS CORRIDOR SHALL NOT BE USED AS A
 RETURN AIR DUCT PER SECTION 601.2. PLEASE REMOVE THE
 TRANSFER GRILLS AND PROVIDE DUCTED RETURNS FROM THE
 AEROBICS, SPINNING, AND BREAK ROOMS
  