Plan Review Notes For Permit 16070628 |
Permit Number |
16070628 |
|
Review Stop |
M |
Sequence Number |
4 |
|
Notes |
Date |
Text |
2017-02-10 08:08:29 | 4TH REVIEW FBC-2014 MECHANICAL | | PERMIT #16070628 | | 2/9/17 | | | | 1) THE NEW 48X16 RETURN TRANSFER FROM THE AEROBICS ROOM | | TO THE EGRESS CORRIDOR IS PROHIBITED PER SECTION 601.2. | | | | 2) AS PREVIOUSLY REQUESTED PROVIDE AN AIR DEVICE | | SCHEDULE LISTING THE MAKES AND MODELS OF ALL NEW AND | | EXISTING AIR DEVICES. | | | | 3) PROVIDE DUCT HANGING AND CONNECTION DETAILS PER | | SMACNA HVAC DUCT CONSTRUCTION STANDARDS 2005. | | | | 4) PLACE A NOTE ON THE PLANS IN ACCORDANCE WITH SECTION | | C408.2.2 TO INDICATE THE SYSTEMS WILL BE TESTED AND | | BALANCED BY EITHER A LICENSED ENGINEER OR AN INDIVIDUAL | | HOLDING A CURRENT CERTIFICATION FROM A RECOGNIZED | | TESTING AND BALANCING AGENCY ORGANIZATION. | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 561-805-6719 | | [email protected] | | |
|