Plan Review Notes For Permit 16070628 |
Permit Number |
16070628 |
|
Review Stop |
P |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2017-01-23 09:30:13 | 3RD REVIEW | | | | GEORGE JOHNSON | | PLUMBING PLANS EXAMINER LL | | CITY OF WEST PALM BEACH | | DEVELOPMENT SERVICES | | BUILDING DIVISION | | 561-805-6711 | | [email protected] | | | | PLUMBING COMMENTS: | | | | 1. PLEASE PROVIDE TWO COMPLETE PLAN SETS. ONE THAT WAS | | PROVIDED IS MISSING SGN-1 ONE IS MISSING P-1. PLEASE | | CLARIFY WPB AMEND TO FBC 107.2.1 | | | | 2. PROVIDE TEMPERED WATER TO ALL LAVATORY'S. PER FBC PL | | 416.5 TEMPERED WATER FOR PUBLIC HAND-WASHING | | FACILITIES. | | TEMPERED WATER SHALL BE DELIVERED FROM LAVATORIES AND | | GROUP WASH FIXTURES LOCATED IN PUBLIC TOILET FACILITIES | | PROVIDED FOR CUSTOMERS, PATRONS AND VISITORS. TEMPERED | | WATER SHALL BE DELIVERED THROUGH AN APPROVED | | WATER-TEMPERATURE LIMITING DEVICE THAT CONFORMS TO ASSE | | 1070 OR CSA B125.3 | | |
|