Plan Review Notes
Plan Review Notes For Permit 16070628
Permit Number 16070628
Review Stop P
Sequence Number 3
Notes
Date Text
2017-01-23 09:30:133RD REVIEW
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
 PLUMBING COMMENTS:
  
 1. PLEASE PROVIDE TWO COMPLETE PLAN SETS. ONE THAT WAS
 PROVIDED IS MISSING SGN-1 ONE IS MISSING P-1. PLEASE
 CLARIFY WPB AMEND TO FBC 107.2.1
  
 2. PROVIDE TEMPERED WATER TO ALL LAVATORY'S. PER FBC PL
 416.5 TEMPERED WATER FOR PUBLIC HAND-WASHING
 FACILITIES.
 TEMPERED WATER SHALL BE DELIVERED FROM LAVATORIES AND
 GROUP WASH FIXTURES LOCATED IN PUBLIC TOILET FACILITIES
 PROVIDED FOR CUSTOMERS, PATRONS AND VISITORS. TEMPERED
 WATER SHALL BE DELIVERED THROUGH AN APPROVED
 WATER-TEMPERATURE LIMITING DEVICE THAT CONFORMS TO ASSE
 1070 OR CSA B125.3
  