Plan Review Notes For Permit 16070628 |
Permit Number |
16070628 |
|
Review Stop |
M |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2016-12-29 11:43:30 | 3RD REVIEW FBC-2014 MECHANICAL | | PERMIT #16070628 | | 12/18/16 | | | | 1) THE OUTDOOR AIR CALCULATIONS ARE INCORRECT PER TABLE | | 403.3 AND ASHRAE 62.1-2010. THE HEALTH GYM, AEROBICS | | ROOM, AND SPIN ROOM SHALLL BE CALCULATED AT 40 PERSONS | | PER 1000 SF. | | | | 2) BASED ON THE O/A CALCULATIONS ENERGY RECOVERY | | SYSTEMS MUST BE INSTALLED FOR RTU'S 2 & 3- REFER TO | | TABLE C403.2.6 FBC-14 ENERGY CONSERVATION. PLEASE | | REVISE THE PLANS ACCORDINGLY. | | | | 3) PLEASE CORRELATE THE IDENTIFICATION NUMBERS OF THE | | RTU'S IN THE SXCHEDULE TO MATCH THE PLANS. | | | | 4) PROVIDE AN AIR DEVICE SCHEDULE FOR BOTH THE NEW AND | | EXISTING DIFFUSERS AND GRILLS. IT APPEARS THAT THE | | EXISTING SUPPLY DIFFUSERS FOR THE RTU'S SERVING THE GYM | | ARE UNDERSIZED FOR THE SPECIFIED CFMS. PLEASE PROVIDE | | MANUFACTURER'S ENGINEERING DATA FOR THE EXISTING | | DIFFUSERS THAT INDICATES THE CFM CAPACITIES BASED ON | | THE PRESSURE LOSS OF THE SYSTEMS AND FACE VELOCITIES. | | | | 5) THE REQUESTED ENERGY COMPLIANCE SUBMITTAL WAS NOT | | PROVIDED. | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 561-805-6719 | | [email protected] | | |
|