2016-12-29 11:43:303RD REVIEW FBC-2014 MECHANICAL
 PERMIT #16070628
 12/18/16
  
 1) THE OUTDOOR AIR CALCULATIONS ARE INCORRECT PER TABLE
 403.3 AND ASHRAE 62.1-2010. THE HEALTH GYM, AEROBICS
 ROOM, AND SPIN ROOM SHALLL BE CALCULATED AT 40 PERSONS
 PER 1000 SF.
  
 2) BASED ON THE O/A CALCULATIONS ENERGY RECOVERY
 SYSTEMS MUST BE INSTALLED FOR RTU'S 2 & 3- REFER TO
 TABLE C403.2.6 FBC-14 ENERGY CONSERVATION. PLEASE
 REVISE THE PLANS ACCORDINGLY.
  
 3) PLEASE CORRELATE THE IDENTIFICATION NUMBERS OF THE
 RTU'S IN THE SXCHEDULE TO MATCH THE PLANS.
  
 4) PROVIDE AN AIR DEVICE SCHEDULE FOR BOTH THE NEW AND
 EXISTING DIFFUSERS AND GRILLS. IT APPEARS THAT THE
 EXISTING SUPPLY DIFFUSERS FOR THE RTU'S SERVING THE GYM
 ARE UNDERSIZED FOR THE SPECIFIED CFMS. PLEASE PROVIDE
 MANUFACTURER'S ENGINEERING DATA FOR THE EXISTING
 DIFFUSERS THAT INDICATES THE CFM CAPACITIES BASED ON
 THE PRESSURE LOSS OF THE SYSTEMS AND FACE VELOCITIES.
  
 5) THE REQUESTED ENERGY COMPLIANCE SUBMITTAL WAS NOT
 PROVIDED.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  