Plan Review Notes
Plan Review Notes For Permit 16070628
Permit Number 16070628
Review Stop P
Sequence Number 2
Notes
Date Text
2016-11-28 09:55:402ND REVIEW
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
 PLUMBING COMMENTS: 2ND REQUEST
  
  
 NOT COMPLIED 3) SUBMIT EXPANDED SANITARY AND WATER
 RISERS FOR REVIEW. IT IS DIFFICULT TO REVIEW THE RISERS
 AS DRAWN. WPB AMEND. TO FBC SEC. 107.2.1.
  
 NOT COMPLIED 5) THE SINK LOCATED AT THE FRONT DESK
 SHALL COMPLY WITH THE FBC - ACCESS. SEC. 212 7 606.
 NOT COMPLIED 6) IF THIS IS A CHANGE OF OCCUPANCY THE
 LAVATORIES SHALL BE SUPPLIED WITH HOT OR TEMPERED WATER
 PER 2014 FBC PLUMBING SEC. 607.1.
 NOT COMPLIED 7) SUBMIT ENLARGED FLOOR PLANS FOR THE
 TOILET ROOMS AND SHOWERS.THE SHOWERS, SEATS, CONTROLS,
 GRAB BARS SHALL COMPLY WITH 2014 FBC-ACCESS. SECS.608,
 610 & 612.
  
  
  
  
  