Plan Review Notes For Permit 16070628 |
Permit Number |
16070628 |
|
Review Stop |
M |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2016-11-10 16:44:41 | 2ND REVIEW FBC-2014 MECHANICAL | | PERMIT #16070628 | | 11/10/16 | | | | 1) REVISE THE EXISTING EQUIPMENT SCHEDULE TO INCLUDE | | THE TOTAL SUPPLY CFMS FOR EACH RTU. | | | | 2) SHOW THE RETURN DUCT SIZES FROM THE AEROBICS ROOM, | | SPINNING ROOM, AND BREAKROOM, AND THE POINTS OF | | CONNECTION TO THE MAIN RETURN TRUNK AND TRUNK SIZE. | | | | 3) THERE ARE LARGE OPEN AREAS IN THE HEALTH GYM | | INCLUDING THE FRONT DESK WHERE NO AC AIR DISTRIBUTION | | IS SHOWN ON THE PLANS. HOW ARE THESE AREAS BEING | | CONDITIONED AND SUPPLIED WITH O/A IN ACCORDANCE WITH | | THE CALCULATIONS? A) SHOW THE ENTIRE DUCT LAYOUTS FOR | | RTU-2 & 3 WITH DUCT, DIFFUSER AND RETURN GRILL SIZES | | SHOWN, AND THE SUPPLY CFMS AT EACH DIFFUSER INDICATED. | | | | 4) THERE ARE 3 EXISTING FANS IN THE HEALTH GYM SHOWN ON | | THE PLAN. CLARIFY THE PURPOSE OF THE FANS AND PROVIDE | | INFORMATION INCLUDING THE MAKES AND MODELS, CFM | | CAPACITIES AND THEIR INDIVIDUAL CONTROL OPERATIONS. | | | | 5) THE PROJECT IS NOW BEING CLASSIFIED AS A "CHANGE OF | | OCCUPANCY" PER THE NEW NOTE ON SHEET A-1. REFER TO | | SECTION C101.4.4 FBC-14 ENERGY CONSERVATION AND PROVIDE | | ENERGY CALCULATIONS- SEE SECTION C401.2 FOR COMPLIANCE | | PATH OPTIONS. | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 561-805-6719 | | [email protected] | | |
|