2016-11-10 10:32:282223 PALM BEACH LAKES BOULEVARD
 PERMIT #16070628
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 REPEAT COMMENT: THE NORTH GATE OF THE FRONT
 ENTRANCE/FRONT DESK AREA SWINGS AGAINST THE FLOW OF
 EGRESS. GATES SHALL BE EQUIPPED WITH PANIC HARDWARE.
  
 REPEAT COMMENT: OVER THE YEARS, EMERGENCY LIGHTING HAS
 BEEN INSTALLED AND REMOVED FROM THIS SUITE. PROVIDE AN
 ELECTRICAL PHOTOMETRICS PLAN SHOWING AT LEAST 1-FT
 CANDLE IS BEING PROVIDED ALONG ALL EGRESS PATHS.
  
 REPEAT COMMENT: THE ONLY FLOORING MATERIAL INDICATED IN
 THIS SPACE IS THE "TURF" AREA. PROVIDE PRODUCT DATA FOR
 THIS MATERIAL. FLOORING SHALL BE AT LEAST CLASS I. PER
 NFPA 10.2.7.4 CLASS I INTERIOR FLOOR FINISH SHALL BE
 CHARACTERIZED BY A CRITICAL RADIANT FLUX NOT LESS THAN
 0.45 W/CM2.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE